7
!
!
!
!
operation and service (circulator replacement, con-
trol replacement, etc.).
8. The boiler must be located where ambient room
temperatures (minimum possible temperatures
where boiler is installed assuming boiler is not in
operation and therefore contributes no heat to the
space) are always at or above 32°F to prevent
freezing of liquid condensate.
COMBUSTION AIR AND
VENT PIPE REQUIREMENTS
8" MINIMUM
VERTICAL SEPARATION
BETWEEN COMBUSTION
AIR INTAKE AND VENT
MAINTAIN 12" MINIMUM
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL
3'' MAXIMUM
SEPARATION
15'' MAXIMUM
COMBUSTION
AIR
12''
MIMIMUM
Figure 1 - Roof Vent/Intake Terminations
Figure 2 - Sidewall Vent/Intake Terminations
OVERHANG
12" MINIMUM
90°
VENT
12" SEPARATION
BETWEEN BOTTOM OF
COMBUSTION AIR INTAKE
AND BOTTOM OF VENT
MAINTAIN 12" MINIMUM
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL OR
GRADE
3"
MAXIMUM
SEPARATION
18"
MAXIMUM
15"
MAXIMUM
LESS THAN 12" CLEARANCE
12"
MINIMUM
12"
MINIMUM
12" OR MORE CLEARANCE
90°
BRACKET
VENT
18"
MAXIMUM
MAINTAIN 12" MINIMUM
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL OR
GRADE
12" SEPARATION
BETWEEN BOTTOM OF
COMBUSTION AIR INTAKE
AND BOTTOM OF VENT
12" MINIMUM
OVERHANG
3"
MAXIMUM
SEPARATION
12"
MINIMUM
12"
MINIMUM
This boiler requires a dedicated direct vent system.
In a direct vent system, all air for combustion is
taken directly from outside atmosphere, and all flue
products are discharged to outside atmosphere.
Combustion air and vent pipe connections must
terminate together in the same atmospheric pres-
sure zone, either through the roof or sidewall (roof
termination preferred). See Figures 1 and 2 for re-
quired clearances.
If the concentric vent termination is being used, re-
fer to Figure 3 for proper setup.
CAUTION
Keep boiler area clean of debris and free of
flammable and combustible materials, va-
pors, and liquids.
WARNING
Failure to follow these warnings could result
in fire, property damage, personal injury, or
death.
When vent pipe is exposed to tempera-
tures below freezing, such as when it pass-
es through an unheated space or when a
chimney is used as a chaseway, vent pipe
must be insulated with ½”Armaflex or
equivalent. In extremely cold climate ar-
eas, use ¾”Armaflex or equivalent.
Combustion air must be clean outdoor
air. Combustion air must not be taken
from inside the structure because that air
is frequently contaminated by halogens,
which include fluorides, chlorides, phos-
•
•
ROOF
OVERHANG
12" MINIMUM
VENT
MAINTAIN 12" IN. CLEARANCE
ABOVE HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE
COMBUSTION AIR
1" MAXIMUM
12" MINIMUM
Figure 3 - Concentric Vent Terminations
(Continued on next page)
Содержание Utica Boilers UB95M-200
Страница 2: ......
Страница 21: ...21 XIII BOILER WIRE DIAGRAM...
Страница 22: ...22 XIV PIPING AND WIRING APPENDIX SINGLE ZONE SYSTEM WITH DOMESTIC HOT WATER PRIORITY...
Страница 23: ...23 XIV PIPING AND WIRING APPENDIX SINGLE ZONE SYSTEM WITH DOMESTIC HOT WATER PRIORITY...
Страница 28: ...28 XIV PIPING AND WIRING APPENDIX MULTIZONE SYSTEM WITH CIRCULATORS AND DOMESTIC HOT WATER PRIORITY...
Страница 29: ...29 XIV PIPING AND WIRING APPENDIX MULTIZONE SYSTEM WITH CIRCULATORS AND DOMESTIC HOT WATER PRIORITY...
Страница 30: ...30 XIV PIPING AND WIRING APPENDIX PRIMARY SECONDARY PIPING WITH CIRCULATORS AND DOMESTIC HOT WATER...
Страница 31: ...31 XIV PIPING AND WIRING APPENDIX PRIMARY SECONDARY WIRING WITH CIRCULATORS AND DOMESTIC HOT WATER...
Страница 36: ...36 XIV PIPING AND WIRING APPENDIX BYPASS PIPING AUTOMATIC MIXING VALVE...
Страница 37: ...37 BYPASS PIPING FIXED LOW TEMP ONLY XIV PIPING AND WIRING APPENDIX...
Страница 38: ...38 XIV PIPING AND WIRING APPENDIX BYPASS PIPING 4 WAY VALVE OPTION WITH CIRCULATOR ON SUPPLY...
Страница 39: ......
Страница 40: ......