Thermostat actuates on call for heat, completing circuit 

to control. Completed circuit to control will first activate 

circulator. Control will first monitor water temperature 

with circulator running to determine if thermostat can be 

satisfed without firing burner; if not it will activate damper 

which closes end switch inside damper. Action completes 

circuit to ignition system and ignition takes place.

In event boiler water temperature exceeds high limit 

setting on boiler mounted high limit control, power is 

interrupted between control system and ignition system. 

Power remains off until boiler water temperature drops 

below high limit setting. Circulator continues to operate 

under this condition until thermostat is satisfied. 

In event flow of combustion products through boiler venting 

system becomes blocked, blocked vent safety switch shuts 

main burner gas off. Similarly, if boiler flue-way becomes 

blocked, flame rollout safety switch shuts main burner 

gas off. See Figure 15

.

 

If either of these conditions occur, 

do not attempt to place boiler back into operation. 

Contact certified service agency

Before seasonal start-up, have certified service agency 

check boiler for soot and scale in flues, clean burners and 

check gas input rate to maintain high operating efficiency.

WARNING

Label all wires prior to disconnection when servicing 

controls. Wiring errors could cause improper and 

dangerous operation.

!

  

Verify proper operation after service.

Service agency will verify system is filled with water to 

minimum pressure and open air vents, if used, to expel any 

air accumulated in the system. Check piping system and, if 

leaks are found, have them repaired immediately.

Check and maintain circulators. Refer to circulator 

manufacturer's instructions.

Inspect venting system at the start of each heating 

season. Check vent pipe from boiler to chimney for signs of 

deterioration by rust or sagging joints. Repair if necessary. 

Remove vent pipe at base of chimney or flue and using 

mirror, check vent for obstruction and verify vent is in good 

working order.

Inspect boiler flue gas passageways by a light and mirror. 

Remove burner door. Place trouble lamp in flue collector 

through draft relief opening. With mirror positioned above 

burners, flue gas passageways can be checked for soot or 

scale. See Figure 15.

Follow the following procedure to clean flue gas 

passageways:

1. 

Remove burners from combustion chamber by raising 

burners up from manifold orifices and pulling toward 

front of boiler. See Figure 17, Page 22.

2. 

Disconnect vent pipe from draft hood.

3. 

Remove top jacket panel.

4. 

Remove combination flue collector and draft hood from 

boiler castings by loosening nuts on hold down bolts 

located on each side of collector. See Figure 15.

5. 

Place sheet of heavy paper or similar material over 

bottom of base and brush down flue passageways. Soot 

and scale will collect on paper and is easily removed 

with the paper. 

6. 

With paper still in place in base, clean top of boiler 

castings of boiler putty or silicone used to seal between 

castings and flue collector. Verify chips are not lodged 

in flue passageways.

When cleaning process is complete, restore boiler 

components to their original position. Use IS-808 GE 

silicone to seal around flue collector and boiler castings.

13 - NORMAL SEQUENCE OF OPERATION

14 - GENERAL INSTRUCTIONS

Figure 15 

- Blocked Vent Safety Switch, Roll-out 

Safety Switch

Rollout Switch 4 

Section Boiler

Rollout  Switch                        

2,3,5,6,7                    

Section Boiler

Содержание PENNCO 15B III Series

Страница 1: ...OPERATION MAINTENANCE MANUAL Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com Models 15B045FE 15B070FE 15B096FE 15B120FE 15B145FE 15B170FE 15B19...

Страница 2: ...17 11 Wiring Diagram 18 12 Lighting Instructions 20 13 Normal Sequence Of Operation 21 14 General Instructions 21 15 Checking Gas Input Rate To Boiler 23 Appendix A Control Module 24 A 1 Installation...

Страница 3: ...R FUTURE REFERENCE WARNING Keep boiler area clear and free from combustible materials gasoline and other flammable vapors and liquids DO NOT obstruct air openings to the boiler room Modification subst...

Страница 4: ...a level United States over 2000 ft 610m above sea level Reduce input rate 4 for every 1 000 ft 304m above sea level 2 Net AHRI Water Ratings shown based on piping and pickup allowance of 1 15 Consult...

Страница 5: ...15B070 15 7 5 28 2015 16 415 16 1 15B096 15 7 5 28 2015 16 415 16 1 15B120 19 9 6 29 217 16 57 16 1 15B145 19 9 6 29 217 16 57 16 1 15B170 22 113 16 7 30 2115 16 515 16 1 15B195 22 113 16 7 30 2115 1...

Страница 6: ...ance operation and service circulator replacement condensate trap control replacement etc 6 Locate boiler on level solid base as near chimney as possible and centrally located with respect to heat dis...

Страница 7: ...if known air infiltration rate is less than 0 40 air changes per hour See Table 3 for space with boiler only Use equation for multiple appliances Volume 50 ft3 x Total Input Mbh Known Air Infiltratio...

Страница 8: ...equal to or greater than that of the relief valve outlet over the entire length of discharge line have no intervening shutoff valve between safety relief valve and discharge to atmosphere do not plug...

Страница 9: ...iler and safety relief valve Systems with automatic fill valves require back flow prevention device Install discharge piping from safety relief valve See Warning Page 8 When boiler is connected to hea...

Страница 10: ...D COOLING ELEMENT CIRCULATOR A PRESSURE REDUCING VALVE PROPER BACKFLOW PROTECTION DEVICE GATE VALVE PURGE VALVE NOTICE Circulators in following illustrations are mounted on system supply side mounting...

Страница 11: ...ss Piping Options Page 9 5 CONNECTING SUPPLY AND RETURN PIPING Figure 3 Bypass Piping Automatic Mixing Valve See Bypass Piping Options Page 9 BOILER WATER INLET ALTERNATE CIRCULATOR LOCATION TO SYSTEM...

Страница 12: ...12 5 CONNECTING SUPPLY AND RETURN PIPING Figure 5 Single Zone System With DHW Priority Figure 6 Multi Zone System with Circulators and DHW Priority...

Страница 13: ...13 5 CONNECTING SUPPLY AND RETURN PIPING Figure 7 Multi zone System With Zone Valves And DHW Priority With Circulator Figure 8 Multi zone System With Zone Valves And DHW Priority With Zone Valve...

Страница 14: ...sizing any portion of the common venting system the common venting system should be re sized to approach the minimum size determined using the appropriate tables in Chapter 13 of the National Fuel Ga...

Страница 15: ...ndicator must be in visible location following installation 5 Thermostat s heat anticipator must be adjusted to match total current draw of all controls associated with boiler during heating cycle 8 V...

Страница 16: ...le 3 Support piping with hooks straps bands brackets hangers or building structure components to prevent or dampen excessive vibrations and prevent strain on gas connection Boiler will not support pip...

Страница 17: ...ion 3 Circulator connection 4 Line power connections 5 LWCO kit 550002998 includes wiring instructions and wiring diagrams If using a different LWCO refer to the specific instructions provided with th...

Страница 18: ...AGRAM I Figure 12 Integrated High Limit Electronic Ignition Control WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal injury...

Страница 19: ...19 11 WIRING DIAGRAM Figure 13 Integrated High Limit Electronic Ignition Control...

Страница 20: ...ctions To Turn Off Gas To Appliance and call qualified service technician or your gas supplier TO TURN OFF GAS TO THE APPLIANCE 1 Set the thermostat to lowest setting 2 Turn off all electric power to...

Страница 21: ...aks are found have them repaired immediately Check and maintain circulators Refer to circulator manufacturer s instructions Inspect venting system at the start of each heating season Check vent pipe f...

Страница 22: ...d pilot for signs of corrosion rust or scale buildup Area around boiler must be kept clear and free of combustible materials gasoline and other flammable vapors and liquids Free flow of combustion and...

Страница 23: ...us 0 3 inches water column from specified pressure Primary air adjustment is not necessary therefore air shutters are not furnished as standard equipment Air shutters can be furnished on request where...

Страница 24: ...well and is not loose Refer to enclosed addendum for wiring instructions when using indirect hot water heater Verify vent damper connection is made See page 15 A 3 Adjusting Settings To discourage una...

Страница 25: ...ial for ignition Appropriate alarm is sent OR Flame signal sensed out of sequence during post purge Appropriate alarm is sent OR Flame signal present when not expected Appropriate alarm is sent 17 Pil...

Страница 26: ...for retry or reset at thermostat Check for correct installation and wiring before replacing any component Control module cannot be repaired If it malfunctions it must be replaced Use only qualified s...

Страница 27: ...larm reason disappears 63 Soft lockout maximum number of recycles exceeded After main burner ignition Soft lockout 64 Soft Lockout electronics failure On board self diagnostics detected error Soft loc...

Страница 28: ...amaged wire Check for cracked ceramic insulator which can cause short to ground and replace igniter sensor if necessary At gas valve disconnect main valve wire from MV terminal Turn on power and set t...

Страница 29: ...29 NOTES...

Страница 30: ...30 NOTES...

Страница 31: ...31 Company Address Phone Company Name Tech Initials Service Performed Date SERVICE RECORD...

Страница 32: ...erride which is provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITION...

Отзывы: