background image

30318 R4 9/9/2005 

7

 

OPTIONAL SIDE WALL VENTING 

Certain WML-C AND MPL-B furnace 
models are manufactured to be installed 
as sidewall vented units. Please refer to 
Direct Venting Instructions, P/N 28888 
included with the Vent Kit for details. 
Sidewall Venting (

Direct Venting

requires the use of specific oil burners; 
the Beckett AFII, or the Riello 40BF. 
Please refer to Appendix A, Tables A2, 
and A4. 

Note: Sidewall venting requires special 
attention to combustion air supply. There 
is no natural draft in the venting system 
between furnace cycles; therefore, if the 
indoor pressure is negative relative to 
the outdoors, the vent terminal becomes 
a point of infiltration. This could lead to 
oil odour control problems. This problem 
is rectified by the use of ducted outdoor 
air for combustion (semi-sealed 
combustion), using the Beckett AFII or 
Riello 40BF oil burner. See Direct Vent 
Instructions supplied with the Vent Kits. 

Table 3: Minimum Chimney Base 

Temperatures (°F) 

Chimney Height (ft.) 

Nozzle 

11 20 28 36 

Chimney Thermal Resistance < R6 

0.50 300 

400 

535 

725 

0.65 275 

340 

430 

535 

0.70 270 

330 

405 

505 

0.75 260 

320 

380 

475 

0.85 250 

300 

355 

430 

1.00 225 

300 

365 

430 

Chimney Height (ft.) 

Nozzle 

11 20 28 36 

Chimney Thermal Resistance > R6 

0.50 185 

200 

220 

250 

0.65 175 

185 

205 

220 

0.70 175 

185 

195 

215 

0.75 175 

185 

195 

210 

0.85 165 

185 

195 

205 

1.00 165 

185 

195 

205 

< - 

less than

,   > - 

greater than

 

OIL TANK 

Oil storage tanks must be selected and 
installed in compliance with applicable 
codes; in the United States, NFPA 31, 

Standard for the Installation of Oil 
Burning Equipment

, Chapter 2. and in 

Canada, CAN/CSA-B139, 

Installation 

Code for Oil Burning Equipment

, Section 

6. Observe all local codes and by-laws. 

In general, the oil tank must be properly 
supported and remain stable in both 
empty and full condition. The oil tank 
must be fitted with vent and supply pipes 
to the outdoors. Refer to the above-
mentioned codes for sizing. The vent 
pipe must be no less than 1¼ inches 
I.P.S., and terminate with an appropriate 
vent cap in a location where it will not be 
blocked. The fill pipe must be no less 
than 2 inches I.P.S., and terminate with 
an appropriate cap in a location where 
debris will not enter the fill pipe during oil 
delivery. 

If located indoors, the tank should 
normally be in the lowest level, (cellar, 
basement, etc.). It must be equipped 
with a shut-off valve at the tank outlet 
used for the oil supply. The oil tank must 
be located as to not block the furnace / 
room exit pathway. Observe all 
clearances specified in the above-
mentioned codes. 

PIPING INSTALLATION 

In the United States, NFPA 31, Standard 
for the Installation of Oil Burning 
Equipment, Chapter 2. 

In Canada, the entire fuel system should 
be installed in accordance with the 
requirements of CAN/CSA B139, and 
local regulations. Use only approved fuel 
oil tanks piping, fittings and oil filters. 

Ensure that all fittings used in a copper 
oil line system are high quality flare 
fittings. Do not use compression fittings. 

Do not use Teflon tape on any fittings. 

Pressurized or gravity feed installations 
must not exceed 3 PSIG. Pressures 
greater than 10 PSIG may cause 
damage to the shaft seal. If the height of 
the oil stored in a tank above the oil 
burner exceeds 11½ feet, it may be 
necessary to use a pressure-regulating 
device approved for this purpose. 

The furnace may be installed with a one-
pipe system with gravity feed or lift. The 
maximum allowable lift on a single line 
system is 8 feet. Lift should be measured 
from the bottom (outlet) of the tank, to 
the inlet of the burner. Sizing a single 
line system is complex because of the 
difficulty estimating the pressure drop 
through each fitting, bend and 
component in the line. In general, keep 
single line systems short as possible. 
The following chart shows the allowable 
line lengths (hori vertical) for 
single and two-line oil piping systems. All 
distances are in feet. 

Table 4: Oil Lines 

Copper Tubing Oil Line Length (Feet) 

Single-Pipe OD 

Two-Pipe OD 

Lift 

(Feet) 

3/8” 

1/2”  

3/8” 

1/2”  

0  53 100 68 100 

1  49 100 65 100 

2  45 100 63 100 

3  41 100 60 100 

4  37 100 58 100 

5  33 100 55 100 

6  29 100 53 100 

7 25 99 50 100 

8 21 83 48 100 

9 17 68 45 100 

10 13 52 42 100 

12 

- - - 

- - - 

37 

100 

14 

- - - 

- - - 

32 

100 

16 

- - - 

- - - 

27 

100 

18 

- - - 

- - - 

22 

88 

In retrofit applications, where an existing 
oil line system is in place, a vacuum 
check will help determine the efficacy of 
the existing oil line system The vacuum 
in a system should not exceed 6” Hg. for 
a single pipe system, nor 12” Hg. for a 
two-pipe system. 

NOTE

: The oil burner requires the use of 

a bypass plug when converting from 
single-pipe to two-pipe oil piping 
systems. See burner manufacturer’s 
instructions. 

All fuel systems should include an oil 
filter between the fuel oil storage tank 
and the oil burner. For best results, 
install the oil filter as close to the burner 
as possible. When using an indoor oil 
tank, the oil filter may be installed at the 
tank downstream from the shut-off valve. 
If firing the furnace under the 0.65 gph 
rate, a 7 to 10 micron line filter should be 
installed as close to the oil burner as 
possible. 

ELECTRICAL CONNECTIONS 

The furnace is listed by the Canadian 
Standards Association (CSA). It is 
factory wired and requires minimal field 
wiring. In the United States, the wiring 
must be in accordance with the National 
Fire Protection Association NFPA-70, 
National Electrical Code, and with local 
codes and regulations. In Canada, all 
field wiring should conform to CAN/CSA 
C22.1 Canadian Electrical Code, Part 1, 
and by local codes, where they prevail.  

The furnace should be wired to a 
separate and dedicated circuit in the 

Содержание MPL-B

Страница 1: ...ow or Horizontal Model ALL INSTALLATIONS MUST MEET ALL LOCAL PROVINCIAL STATE AND FEDERAL CODES WHICH MAY DIFFER FROM THIS MANUAL ECR International Limited OLSEN Division Read this complete manual bef...

Страница 2: ...JUSTMENT 14 A 2 BURNER ELECTRODES 14 A 3 START UP 14 A 4 SPECIAL INSTRUCTIONS FOR UNITS EQUIPPED WITH RIELLO BURNERS 14 TABLE A 6 DIRECT DRIVE BLOWER SET UP 15 TABLE A 8 DIRECT DRIVE BLOWER CHARACTERI...

Страница 3: ...tallation of the furnace and related equipment shall be installed in accordance with the regulations of CAN CSA B139 Installation Code For Oil Burning Equipment as well as in accordance with local cod...

Страница 4: ...suspended by field fabricating a cradle of angle iron and threaded rod Secure the furnace with 2 inch minimum slotted angle or equivalent as shown in Figure 1 The furnace must be supported in such a...

Страница 5: ...ximum temperature for L Vent is 575 F 300 C IMPORTANT The chimney must be capable of providing sufficient draft at all times for the safe removal of the products of combustion The chimney should be te...

Страница 6: ...cape Must be handled by competent masonry contractor G Collection of soot at narrow space in flue opening Lower light on extension cord Clean out with weighted brush or bag of loose gravel on end of l...

Страница 7: ...should be installed in accordance with the requirements of CAN CSA B139 and local regulations Use only approved fuel oil tanks piping fittings and oil filters Ensure that all fittings used in a coppe...

Страница 8: ...point for most of the electrical components in the furnace The Honeywell ST9103 has a fixed fan delay on time of 30 seconds after the burner ignites The United Technologies 1158 120 has an adjustable...

Страница 9: ...fier transformers The unused motor taps auto generate sufficiently high voltages to damage accessory equipment Use the terminals provided on the electronic fan timer Do not start the burner or blower...

Страница 10: ...dard operating pressure is 100 PSIG After reaching steady state take a smoke test If not indicating a trace set the combustion air controls to provide a trace Typically the CO2 reading will range from...

Страница 11: ...that the reset switch is not to be activated more than once without a thorough look for the cause of the problem lack of fuel etc Be sure that the homeowner knows when to quit trying to start the furn...

Страница 12: ...air take off or within the first few inches of the supply air trunk The side mid point of the transition is usually ideal providing that the thermometer probe is beyond the line of sight wherein fals...

Страница 13: ...by ceramic insulator 2 Low Firing Rate Baffle required when using a 0 50 gallon nozzle Table A 2 Beckett AFII Oil Burner Set Up Beckett AFII Series Oil Burners For use with sidewall vented units using...

Страница 14: ...oth start ups and to permit efficient combustion Beckett AF Burner Electrode gap 5 32 inch Distance above horizontal centerline 5 16 inch Older instruction sheets specify 7 16 inch The current specifi...

Страница 15: ...3 MPL 130B GT12 10DD High HP High HP 3 HP 1185 1553 Table A 8 Direct Drive Blower Characteristics CFM External Static Pressure Inches w c Furnace Model Blower Motor HP Motor FLA T Speed 0 20 0 30 0 40...

Страница 16: ...Model Width A Depth B Height C Supply D x E Side Bottom Flue Diameter H Type Size Shipping Weight WML C 22 22 1 8 55 1 4 19 x 19 18 x 18 18 x 18 5 Permanent 20 x 20 x 1 265 MPL B 22 1 4 22 1 4 62 20...

Страница 17: ...30318 R4 9 9 2005 17 APPENDIX B WIRING DIAGRAMS Beckett AF Burner Wiring Diagram...

Страница 18: ...30318 R4 9 9 2005 18 Beckett AFII Burner Wiring Diagram...

Страница 19: ...30318 R4 9 9 2005 19 Riello 40F3 and F5 Burner Wiring Diagram...

Страница 20: ...30318 R4 9 9 2005 20 Riello 40BF3 Burner Wiring Diagram...

Страница 21: ...be made by moving the dipswitch settings on the timer control board for fan off delay To check the operation of the limit switch shut off power to the furnace Temporarily remove the neutral wire from...

Страница 22: ...tate Continues to spark for 10 sec a Provides continuous spark after flame is sensed to assure that burner remains lit b Turns on LED diagnostic light c Starts carryover timer i Flame and call for hea...

Страница 23: ...30318 R4 9 9 2005 23 R7184 INTERRUPTED ELECTRONIC OIL PRIMARY CONTROL FIGURE 7 ELECTRONIC FAN TIMER BOARD ON CONTROL PANEL FIGURE 8...

Страница 24: ...id Valve LED Diagnostic Light RETURNS TO IDLE STATE FLAME FLAME FLAME FLAME NO FLAME NO FLAME FLAME LOST FLAME LOST REMAINS IN IDLE STATE R7184 SEQUENCE of OPERATION LOCKOUT STATE R7184 Shuts off burn...

Страница 25: ...cool G and Y terminals are de energized a Cooling contactor is de energized immediately b Circulator fan turns off immediately Thermostat begins call for fan G terminal is energized a Circulator fan...

Страница 26: ...OTING IMPORTANT Due to the potential hazard of line voltage only a trained experienced service technician should perform the troubleshooting procedure PRELIMINARY STEPS Check the diagnostic light for...

Страница 27: ...alve is closed during the valve on delay period by opening view port and verifying that no flame is present during the 15 second valve on delay Indicator light is on If flame is present replace the oi...

Страница 28: ...is on Remount control onto burner housing Go to step 6 11 Check cad cell a Disconnect line voltage power and open line switch b Remove existing cad cell and replace with new cad cell c Disconnect all...

Страница 29: ...ed or in some manner defective Check fuel oil lines Replace any compression fittings found with high quality flared fittings Check for any signs of oil leaks Any oil leak is a potential source of air...

Страница 30: ...ner or improper draft pressure Adjust the oil burner combustion air band and draft regulator to gain the highest practical CO2 or lowest practical O2 content in the flue gases See Burner Set Up Too mu...

Страница 31: ...ductwork Seal leaky joints and seams Insulate ductwork if necessary FINAL CHECK OUT ENSURE THAT ALL SAFETY DEVICES AND ELECTRICAL COMPONENTS HAVE BEEN SET FOR NORMAL OPERATION ENSURE THAT ALL ELECTRIC...

Страница 32: ...19 Filter Frame 21260 20 Filter Frame End Support 21306 21 Air Filter 20 x 20 x 1 Permanent 2180032 22 Junction Box 28723 23 Channel Wire Retainer 30239 24 Limit Control 60T11BOF L180 F 28654 25 Wire...

Страница 33: ...t 2 per unit 29870 Sight Glass 29876 13 Flue Connector Assembly 6 to 4 90 Elbow 28952 14 Pouch Gasket Second gasket required for Direct Vent 2080175 15 Flue Collar Gasket Second gasket required for Di...

Страница 34: ...30318 R4 9 9 2005 34...

Страница 35: ...ector 28306 14 Pouch Gasket 2080175 15 Flue Pipe Gasket 21994 16 Radiator Cleanout Cover Assembly 1061A Cleanout Cover Gasket 2080176 17 Casing Clean out Cover 3011325A 18 Filter Frame 21260 19 Filter...

Страница 36: ...llary Limit L130 F 60T11 BOF 30388 40 Junction Box Cover 28722 PARTS LISTING COUNTERFLOW HORIZONTAL DIRECT VENT MODEL MPL BB2U Ref No Description PART NO All parts are the same as listed on the previo...

Страница 37: ...30318 R4 9 9 2005 37...

Страница 38: ...odel No Serial No Date Installed Contractor Contact Address Postal Code Telephone No After Hours No FUEL SUPPLIER Fuel Oil Supplier Contact Telephone No After Hours No IF DIFFERENT FROM INSTALLATION C...

Страница 39: ...30318 R4 9 9 2005 39 NOTES...

Страница 40: ...aceburg Ontario N8A 5E5 Can Tel 519 627 0791 Fax 519 627 4719 2201 Dwyer Avenue Utica New York 13504 USA Tel 315 797 1310 Fax 315 724 9319 85 Middle Road Dunkirk New York 14048 USA Tel 716 366 5500 Fa...

Отзывы: