Table C-3: Oil Primary Control Troubleshooting
continued from previous page
Procedure Status
Corrective
Action
Indicator light turns off.
Eliminate external light source or permanently shield cad cell.
4
. Shield cad cell from external
light.
Indicator light stays on.
Replace cad cell with new cad cell and recheck.
If indicator light does not turn off, remove cad cell lead wires
from oil primary control and recheck.
If indicator light turns off, replace cad cell bracket assembly.
If indicator light does not turn off, replace controller.
Burner starts.
Trouble in thermostat or limit circuit. Check thermostat or limit
wiring connections.
5
. Jumper thermostat (T -T)
terminals on oil primary control
IMPORTANT
First remove one thermostat
lead wire.
Burner does not start.
Disconnect the line voltage power and open line switch.
Check all wiring connections.
Tighten any loose connections and recheck.
If burner does not start, replace oil primary control
Condition: Burner starts then locks out on safety with indicator light flashing at 1 Hz rate (½ second on, ½ second
off)
Indicator light stops flashing.
Go to Step 7.
6
. Reset oil primary control by
pushing in and releasing red
reset button.
Indicator light continues to
flash at 1 Hz rate.
Verify that the control is not in restricted mode. (See notes at
end of this table.). If not in restricted mode, replace oil
primary control
Ignition is off
Spark igniter could be defective. Check for line voltage at
igniter terminals. If line voltage is present, replace oil primary
control.
Ignition is on.
Go to Step 8.
7
. Listen for spark after burner
turns on (after 2 second delay).
Ignition is on but no oil is
being sprayed into the
combustion chamber.
Wait for “Valve ON” delay to complete. Check oil supply, and
oil line valve. Check for filter blockage or seized oil pump.
Indicator light is on until the
control locks out and starts
flashing during lockout.
Replace oil primary control
8
. Check indicator light after
flame is established, but before
oil primary control locks out.
Indicator light stays off.
Go to step 9.
Burner locks out.
Go to step 10.
9
. Check cad cell sighting for
view of flame.
Disconnect line voltage power
and open line switch.
Unplug cad cell and clean cad
cell face with soft clothe. Check
sighting for clear view of flame.
Replace cad cell in socket.
Reconnect line voltage power
and close line switch.
Start burner.
Burner keeps running.
System is OK.
30173 Rev B 4/29/2008
25
Содержание HML-C
Страница 33: ...30173 Rev B 4 29 2008 33...
Страница 34: ...30173 Rev B 4 29 2008 34...
Страница 35: ...30173 Rev B 4 29 2008 35...