30173 Rev B 4/29/2008
11
Table A-3 Riello 40F Series Oil Burner Set-Up
Riello 40F Series Oil Burners
(For use with chimney vented units)
Furnace
Model
Output
BTU/Hr
Burner
Model
Nozzle
Pump
Pressure
Flow Rate
Air Gate
Turbulator
Setting
HML-60CRF
HMLV-60CRF
59,000
40F3
0.50 / 60°W
105
PSIG
0.50
USGPH
2.6
1.0
HML-80CRF
HMLV-80CRF
75,000
40F3
0.60 / 60°W
115
PSIG
0.65
USGPH
2.6
1.5
HML-90CRF
HMLV-90CRF
86,000
40F3
0.65 / 60°W
135
PSIG
0.75
USGPH
3.6
2.0
Riello Balanced Flue Series Oil Burners
(For use with sidewall vented units using outdoor combustion air)
Furnace Model
Output
BTU/Hr
Burner
Model
Nozzle
Pump
Pressure
Flow Rate
Turbulator
Setting
HML-60CRBU
HMLV-60CRBU
59,000
40BF3
0.50 / 60°W
105
PSIG
0.50
USGPH
1.0
HML-80CRBU
HMLV-80CRBU
75,000
40BF3
0.60 / 60°W
115
PSIG
0.65
USGPH
1.5
HML-90CRBU
HMLV-90CRBU
86,000
40BF3
0.65 / 60°W
135
PSIG
0.75
USGPH
2.0
Table A-4 Riello Balanced Flue (BF) Burner Set-Up
NOTE
: Air gate setting may vary for sidewall vented units where air gate must be adjusted to achieve
zero smoke.
A.1 OIL BURNER AIR ADJUSTMENT
For complete details, consult the oil burner instruction
manual provided in the furnace documents envelope.
Beckett AF Burner
Adjust the air shutter by loosening the locking screws
and moving the air shutter, and if necessary, the bulk
air band.
Beckett AFII Burner
Adjust the burner air supply by first loosening the
locking screw located on the black dial to the right of
the burner. Turn the black dial clockwise to increase
the combustion air and counter-clockwise to decrease
the combustion air. Re-tighten the locking screw after
obtaining the proper setting.
Riello 40 Series (Chimney Vented)
Riello burners are factory set with respect to nozzle
size; pump pressure, air gate and turbulator
adjustments for each model and firing rate. By
removing the burner cover and loosening the screws
that secure the air adjustment plate, the combustion air
can be adjusted. Move the adjusting plate to either
increase or decrease combustion air. When the proper
air setting is achieved, retighten the fixing screws.
Riello Balanced Flue (BF) Series
Riello burners are factory set with respect to nozzle
size; pump pressure, and turbulator adjustments for
each model and firing rate. The combustion air can be
adjusted with the burner cover on by first removing the
plastic cover on the top right hand side of the burner
cover. With a Philips head screw driver, turn the
adjustment screw clockwise to increase combustion air
or counter-clockwise to decrease combustion air.
When the combustion air is set, re-insert the plastic
cover.