76
13 - TROUBLE SHOOTING
Is return line warmer than
supply line?
NO
YES
Check wire plugs are
securely connected to
sensors.
NO
YES
Error Code is
accurate.
Correct system
piping.
Assure wire harness plugs
are securely connected to
sensors
Check water pressure. Is water
pressure at least 15 psig?
NO
YES
Troubleshooting Chart 4
Refer to temperature
sensor chart
NO
YES
Replace
control board
Check both sensors are
properly inserted into pipe
lines.
NO
YES
Repair sensor insertion
into pipe lines
E10, E11
- Temperature Difference Between
Supply and Return Too Great
E35 -
Supply and Return Sensors Reversed
Onboard pump operation
properly?
NO
YES
Replace
pump
Possible air
in system.
De-aerate
Are any water valves
partially closed?
NO
YES
Open all
valves
Check wire harness against
wiring diagram. Are Supply
sensor wires green and
Return Sensor wires red?
NO
YES
Wire connections are
reversed. Correct
wiring connections.
Replace
sensor
PN 240011656 REV. K [11/01/2020]