ECR International AMB-4 Скачать руководство пользователя страница 21

21

PN 240013666 REV. A [06/30/2022]

AMB-4 Multiple Boiler Control (MBC) Application

1. 

Sequence of Operation

 – The control will drive the boilers to a target water temperature based on 

demand from:

A�  Boiler Demand: A target water temperature is calculated based on a programmable heating curve� 

i�  The control can receive boiler demand either from 20 – 260V (ac) to terminals 21 and 22, or 

from an Energy Management System (EMS) by applying 0-10 or 2-10 V (dc) signal to terminals 

2 & 3 when the DIP switch is set to EMS� 

ii�  Supply water target temperature is determined by a signal from building energy management 

system or outdoor reset�

iii�  Heating curve may also adjust supply temperature based on building heat distribution (radiant 

floor, fan-coil, baseboard, etc.)

iv�  It is recommended minimum supply temperature be such that corresponding return water 

temperature be at least 120 degrees F to prevent condensation in the boiler� Generally, this will 

require minimum supply water temperature of at least 140°F, or provide boilers with bypass as 

describe in boiler instructions�

v�  Optional warm weather shutdown is available�
vi�  The Hydrolevel control will not allow a supply temperature setting above 220° F�
vii� 

The MBC may operate up to four on/off boilers as a heat source. For proper operation of 

the boilers, the MBC must be the only control that determines when a boiler is to fire.              

*Important note:

 

The boiler control (Hydrolevel 3200) must remain in the burner circuit and 

act as a secondary upper limit on the boiler temperature� The Hydrolevel 3200 temperature 

setting must be adjusted above the MBC’s boiler maximum setting to prevent short cycling of 

the burner�

viii� 

The MBC includes a rotate feature to change the firing order of the boilers. Various boiler 

sequencing options are available as described in the MBC instructions�

B�  Domestic Hot Water: DHW demand may be driven by either an aquastat or DHW sensor�

i�  When DHW demand is present, the control will specify the higher of either the DHW supply 

temperature or calculated CH supply temperature�

ii�  DHW is provided by providing power to the DHW loop circulator�
iii�  DHW demand may be assigned priority, or not�  If DHW is given priority, and the total demand 

exceeds boiler capacity, the CH circulator will shut off.  DHW priority period time may be set to 

automatically calculate and vary depending upon outdoor temperature at the time�

iv�  DHW loop may be piped in parallel with primary circuit�

C�  Setpoint Operation: Not available if DHW mode is in use�

i�  The control will select the higher of the setpoint temperature or current target water 

temperature�

ii�  Setpoint demand is generated from a 20 to 260V signal applied across the appropriate 

terminals�

iii�  Operating mode can be varied depending upon piping arrangement�

Argo AMB Controls

Содержание AMB-4

Страница 1: ...IDE FOR MULTIPLE GAS FIRED HOT WATER BOILER INSTALLATIONS UP TO 4 UNITS Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Tel 800 325 5479 www ecrinternational com PN 240013666 RE...

Страница 2: ...IONAL DATA 6 BOILER RATINGS CAPACITIES 7 TYPICAL LAYOUTS FOR HOT WATER HEATING SYSTEMS 8 12 COMBUSTION AIR REQUIREMENTS 13 COMMON VENTING REQUIREMENTS 14 VENTILATION AND COMBUSTION 15 VENT INSTALLATIO...

Страница 3: ...s excess of water or other liquid shall be replaced Failure to follow these directions will result in a Hazardous Situation FOR YOUR SAFETY READ BEFORE OPERATING Hot Water Can Scald Water heated to te...

Страница 4: ...acturers and phone numbers are also listed on this website Wear long sleeved loose fitting clothing gloves and eye protection Apply enough water to the combustion chamber lining to prevent dust Wash p...

Страница 5: ...o installation by licensed plumber or gas fitter WARNING Fire explosion asphyxiation and electrical shock hazard Improper installation could result in death or serious injury Read this instruction and...

Страница 6: ...fied per Installation Operation Maintenance Manual provided with each boiler Figure 1 Dimensional Data MULTIPLE GAS FIRED HOT WATER BOILER ENGINEERING AND DIMENSIONAL DATA Boiler Size NUMBER OF BOILER...

Страница 7: ...HT 8 Section 2 525 442 384 7 12 12 x 20 9 Section 2 598 504 438 7 12 12 x 20 8 Section 3 787 5 663 576 7 14 14 x 20 9 Section 3 897 756 657 7 14 14 x 20 8 Section 4 1050 884 768 7 16 16 x 20 9 Section...

Страница 8: ...Systems Figure 3 Room Sizing Parallel Reverse Return 3 Boilers shown Note Access is minimum 24 service clearance Vent position relief valve location supply and return piping will vary depending on ty...

Страница 9: ...arance Vent position relief valve location supply and return piping will vary depending on type of units LEGEND PIPE SIZING S R 1 NPT BOILER SUPPLY AND RETURN B HEADER REFER TO TABLE 3 Typical Layouts...

Страница 10: ...R 4 L T1 HIGH LIMIT 5 B HEADER 3 LEGEND Locate temperature sensor within 3 to 5 feet after supply header Maximum overall length is based on using 4 boilers having largest footprint and 24 minimum serv...

Страница 11: ...CSD 1 High Limit Shall be within 1 1 foot of nearest boiler 2 3 BOILER 1 BOILER 2 BOILER 3 BOILER 4 T SYSTEM TEMPERATURE SENSOR UP TO MAX INLINE OF 163 2 TO FLOOR DRAIN TYP SYSTEM SUPPLY SYSTEM RETUR...

Страница 12: ...3 HYDRONIC PIPE SIZING GUIDE COMBINED BOILER INPUT MBTUH Fig 4 Fig 6 ONLY MINIMUM PIPE SIZE NPT S R HEADER B 525 1 1 4 2 600 790 900 1 1 4 2 1 2 1 1 4 2 1 2 1 1 4 3 1 050 1 200 1 1 4 3 1 1 4 3 Typical...

Страница 13: ...0 8 Section 3 787 5 200 800 200 400 9 Section 3 897 225 900 225 450 8 Section 4 1050 275 1100 275 550 9 Section 4 1196 300 1200 300 600 Unconfined Area A space whose volume is not less than 50 cubic f...

Страница 14: ...252 16 24 0 288 18 27 0 324 Table 5 based on TYPE B Double Wall vent using un assisted Common Vent system Reference is NFPA 54 ANSI Z223 1 National Fuel Gas Code Consult NFPA 54 ANSI Z223 1 National F...

Страница 15: ...of rectangular air ducts shall be not less than 3 x 3 inches or 9 square inches A When installing two openings one must commence within A 12 inches from the top and the other within 12 inches from the...

Страница 16: ...pipe or reduce size of flue outlet except as provided by the latest revision of ANSI Z223 1 Protect combustible ceiling and walls near flue pip with fireproof insulation Where two or more appliances...

Страница 17: ...d and other spaces of the building Turn on clothes dryers and any other appliance not connected to the common venting system Turn on any exhaust fans such as range hoods and bathroom exhausts so they...

Страница 18: ...00 2 00 2 00 2 50 2 50 8 Section 4 1050 1 50 2 00 2 00 2 00 2 00 2 50 2 50 2 50 9 Section 4 1196 2 00 2 00 2 00 2 00 2 50 2 50 2 50 2 50 See individual unit s Installation Operation Maintenance Manua...

Страница 19: ...t to run each boiler equally and extend boiler life Setpoint reset ratio rotation and many other features are easily programmed in the filed through the four button user interface Operation When used...

Страница 20: ...2 Argo AMB Controls Consult ARGO AMB installation manual for additional information Model Number Domestic International Transformer Voltage ARGO AMB 4 Domestic 120V 60Hz 40Va Figure 12 Wiring ARGO AMB...

Страница 21: ...lers the MBC must be the only control that determines when a boiler is to fire Important note The boiler control Hydrolevel 3200 must remain in the burner circuit and act as a secondary upper limit on...

Страница 22: ...ack to zero press and hold the up and down button while viewing this item Note once primary pump sequencing is selected DHW operation is not available Setpoint operation however is available if primar...

Страница 23: ...23 PN 240013666 REV A 06 30 2022 NOTES...

Страница 24: ...All specifications subject to change without notice 2022 ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Tel 800 325 5479 www ecrinternational com...

Отзывы: