14
PN 240013666 REV. A [06/30/2022]
Common Venting Requirements
COMBINED
INPUT (BTUH)
x1000
Table 5 - COMMON VENT SIZING (INCHES)
Vertical Vent Height (Ft)
6’
8’
10’
20’
30’
50’
100’
550
12
12
12
10
9
9
8
600
14
12
12
12
10
9
9
790
14
14
14
12
12
10
9
900
16
14
14
12
12
12
10
1,050
16
16
16
14
12
12
12
1,200
18
18
16
14
14
12
12
COMMON VENT
DIAMETER
(INCHES)
MAXIMUM
HORIZONTAL
LENGTH
FEET [INCHES]
8
12�0 [144”]
9
13�5 [162”]
10
15�0 [180”]
12
18�0 [216”]
14
21�0 [252”]
16
24�0 [288”]
18
27�0 [324”]
Table 5 based on TYPE-B Double-Wall vent using
un-assisted
Common Vent system. Reference is NFPA-
54 / ANSI Z223.1 National Fuel Gas Code.
Consult NFPA-54 / ANSI Z223.1 National Fuel Gas Code. for “Mechanical Vent” Sizing and additional vent
information.
Maximum Horizontal Vent Length shall not exceed allowable [Common Header Vent Size x 18”]. See Table 6.
If longer Horizontal Vent Lengths are required – percentage reduction in capacity must be made to Table
values. Consult NFPA-54 / ANSI Z223.1 National Fuel Gas Code.
Table 5 - Common Vent Sizing Table for Multiple Boilers
Table 6 - Maximum Horizontal Length of Common Vent