ECR International AMB-4 Скачать руководство пользователя страница 15

15

PN 240013666 REV. A [06/30/2022]

1. 

Ventilation of the boiler room must be adequate to 

provide suf1. ficient air to properly support combustion 

per the latest revision of the National Fuel Gas Code, 

ANSI Z223�1/ NFPA-54�

2. 

When a boiler is located in an unconfined space in a 

building or conventional construction frame, masonry 

or metal building, infiltration normally is adequate to 

provide air for combustion and ventilation� However, 

if the equipment is located in a building of tight 

construction (See the National Fuel Gas Code, ANSI 

Z223�1) the boiler area should be considered as a 

confined space. If there is any doubt, install air supply 

provisions in accordance with the latest revision of the 

National Fuel Gas Code�

3. 

When a boiler is installed in an unconfined space, in a 

building of tight construction, air for combustion and 

ventilation must be obtained from outdoors or from 

spaces freely communicating with the outdoors� A 

permanent opening or openings having a total free area 

of not less than 1 square inch per 5,000 BTU per hour 

of total input rating of all appliances shall be provided� 

Ducts may be used to convey makeup air from the 

outdoors and shall have the same cross-sectional area 

of the openings to which they are connected�

4. 

When air for combustion and ventilation is from inside 

buildings, the confined space shall be provided with two 

permanent openings, one starting 12 inches from the 

top and one 12 inches from the bottom of the enclosed 

space� Each opening shall have a minimum free area 

of 1 square inch per one thousand (1000) BTU per 

hour of the total input rating of all appliances in the 

enclosed space, but must not be less than one hundred 

(100) square inches� These openings must freely 

communicate directly with other spaces of sufficient 

volume so that the combined volume of all spaces 

meets the criteria for an unconfined space.

 See Figure 

#7.

5. 

When the boiler is installed in a confined space and all 

air is provided from the outdoors the confined space 

shall be provided with one or two permanent openings 

according to methods A or B� When ducts are used, 

they shall be of the same cross sectional area as the 

free area of the area of the openings to which they 

connect� The minimum dimension of rectangular air 

ducts shall be not less than 3 x 3 inches or 9 square 

inches�

A�  When installing two openings, one must commence 

within A� 12 inches from the top and the other 

within 12 inches from the bottom of the enclosure� 

The openings shall communicate directly, or by 

ducts, with the outdoors or spaces (crawl or attic) 

that freely communicate with the outdoors� One 

of the following methods must be used to provide 

adequate air for ventilation and combustion�

i�  When directly communicating with the 

outdoors, each opening shall have a minimum 

free area of 1 square inch per 4,000 BTU per 

hour of total input rating of all equipment in 

the enclosure� 

See Figure #8.

ii�  When communicating with the outdoors by 

means of verII� tical ducts, each opening shall 

have a minimum free area 1 square inch per 

4,000 BTU per hour of total input rating of all 

appliances in the enclosed space�

iii�  If horizontal ducts are used, each opening 

and duct shall III� have a minimum free area 

1 square inch per 2,000 BTU per hour of total 

input rating of all appliances in the enclosed 

space�

B�   One permanent opening, commencing within 

12 inches of the top of the enclosure, shall be 

permitted where the equipment has clearances 

of at least 1 inch from the sides, 1 inch from the 

back, and 6 inches from the front of the boiler� 

The opening shall directly communicate with the 

outdoors or shall communicate through a vertical or 

horizontal duct to the outdoors or spaces (crawl or 

attic) that freely communicate with the outdoors� 

The openings must have a minimum free area of 1 

square inch per 3000 Btu per hour of the total input 

rating of all equipment located in the enclosure� 

The free area must be no less than the sum of the 

areas of all vent connectors in the confined space.

6. 

In calculating free area using louvers, grilles or screens 

for the 6� above, consideration shall be given to their 

blocking effect. Screens used shall not be smaller than 

¼ inch mesh� If the free area through a design of 

louver or grill is known, it should be used in calculating 

the size opening required to provide the free area 

specified. If the design and free area is not known, it 

may be assumed that wood louvers will have 20-25% 

free area and metal louvers and grilles will have 60-

75% free area. Louvers and grilles should be fixed in 

the open position or interlocked with the boiler so they 

are opened automatically during the boiler operation�

Ventilation and Combustion

Содержание AMB-4

Страница 1: ...IDE FOR MULTIPLE GAS FIRED HOT WATER BOILER INSTALLATIONS UP TO 4 UNITS Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Tel 800 325 5479 www ecrinternational com PN 240013666 RE...

Страница 2: ...IONAL DATA 6 BOILER RATINGS CAPACITIES 7 TYPICAL LAYOUTS FOR HOT WATER HEATING SYSTEMS 8 12 COMBUSTION AIR REQUIREMENTS 13 COMMON VENTING REQUIREMENTS 14 VENTILATION AND COMBUSTION 15 VENT INSTALLATIO...

Страница 3: ...s excess of water or other liquid shall be replaced Failure to follow these directions will result in a Hazardous Situation FOR YOUR SAFETY READ BEFORE OPERATING Hot Water Can Scald Water heated to te...

Страница 4: ...acturers and phone numbers are also listed on this website Wear long sleeved loose fitting clothing gloves and eye protection Apply enough water to the combustion chamber lining to prevent dust Wash p...

Страница 5: ...o installation by licensed plumber or gas fitter WARNING Fire explosion asphyxiation and electrical shock hazard Improper installation could result in death or serious injury Read this instruction and...

Страница 6: ...fied per Installation Operation Maintenance Manual provided with each boiler Figure 1 Dimensional Data MULTIPLE GAS FIRED HOT WATER BOILER ENGINEERING AND DIMENSIONAL DATA Boiler Size NUMBER OF BOILER...

Страница 7: ...HT 8 Section 2 525 442 384 7 12 12 x 20 9 Section 2 598 504 438 7 12 12 x 20 8 Section 3 787 5 663 576 7 14 14 x 20 9 Section 3 897 756 657 7 14 14 x 20 8 Section 4 1050 884 768 7 16 16 x 20 9 Section...

Страница 8: ...Systems Figure 3 Room Sizing Parallel Reverse Return 3 Boilers shown Note Access is minimum 24 service clearance Vent position relief valve location supply and return piping will vary depending on ty...

Страница 9: ...arance Vent position relief valve location supply and return piping will vary depending on type of units LEGEND PIPE SIZING S R 1 NPT BOILER SUPPLY AND RETURN B HEADER REFER TO TABLE 3 Typical Layouts...

Страница 10: ...R 4 L T1 HIGH LIMIT 5 B HEADER 3 LEGEND Locate temperature sensor within 3 to 5 feet after supply header Maximum overall length is based on using 4 boilers having largest footprint and 24 minimum serv...

Страница 11: ...CSD 1 High Limit Shall be within 1 1 foot of nearest boiler 2 3 BOILER 1 BOILER 2 BOILER 3 BOILER 4 T SYSTEM TEMPERATURE SENSOR UP TO MAX INLINE OF 163 2 TO FLOOR DRAIN TYP SYSTEM SUPPLY SYSTEM RETUR...

Страница 12: ...3 HYDRONIC PIPE SIZING GUIDE COMBINED BOILER INPUT MBTUH Fig 4 Fig 6 ONLY MINIMUM PIPE SIZE NPT S R HEADER B 525 1 1 4 2 600 790 900 1 1 4 2 1 2 1 1 4 2 1 2 1 1 4 3 1 050 1 200 1 1 4 3 1 1 4 3 Typical...

Страница 13: ...0 8 Section 3 787 5 200 800 200 400 9 Section 3 897 225 900 225 450 8 Section 4 1050 275 1100 275 550 9 Section 4 1196 300 1200 300 600 Unconfined Area A space whose volume is not less than 50 cubic f...

Страница 14: ...252 16 24 0 288 18 27 0 324 Table 5 based on TYPE B Double Wall vent using un assisted Common Vent system Reference is NFPA 54 ANSI Z223 1 National Fuel Gas Code Consult NFPA 54 ANSI Z223 1 National F...

Страница 15: ...of rectangular air ducts shall be not less than 3 x 3 inches or 9 square inches A When installing two openings one must commence within A 12 inches from the top and the other within 12 inches from the...

Страница 16: ...pipe or reduce size of flue outlet except as provided by the latest revision of ANSI Z223 1 Protect combustible ceiling and walls near flue pip with fireproof insulation Where two or more appliances...

Страница 17: ...d and other spaces of the building Turn on clothes dryers and any other appliance not connected to the common venting system Turn on any exhaust fans such as range hoods and bathroom exhausts so they...

Страница 18: ...00 2 00 2 00 2 50 2 50 8 Section 4 1050 1 50 2 00 2 00 2 00 2 00 2 50 2 50 2 50 9 Section 4 1196 2 00 2 00 2 00 2 00 2 50 2 50 2 50 2 50 See individual unit s Installation Operation Maintenance Manua...

Страница 19: ...t to run each boiler equally and extend boiler life Setpoint reset ratio rotation and many other features are easily programmed in the filed through the four button user interface Operation When used...

Страница 20: ...2 Argo AMB Controls Consult ARGO AMB installation manual for additional information Model Number Domestic International Transformer Voltage ARGO AMB 4 Domestic 120V 60Hz 40Va Figure 12 Wiring ARGO AMB...

Страница 21: ...lers the MBC must be the only control that determines when a boiler is to fire Important note The boiler control Hydrolevel 3200 must remain in the burner circuit and act as a secondary upper limit on...

Страница 22: ...ack to zero press and hold the up and down button while viewing this item Note once primary pump sequencing is selected DHW operation is not available Setpoint operation however is available if primar...

Страница 23: ...23 PN 240013666 REV A 06 30 2022 NOTES...

Страница 24: ...All specifications subject to change without notice 2022 ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Tel 800 325 5479 www ecrinternational com...

Отзывы: