Page 4
OPERATING CONDITIONS
The following list provides guidance on the conditions required for successful operation of your
ecoTAC™ system. Use of this equipment outside of these operating conditions may adversely affect the
performance of your system, damage the TAC media, result in system damage including water leaks and
resulting property damage, and may void your warranty.
It is very important to note that the presence of elevated levels of chlorine, iron, manganese, hydrogen
sulfide, copper, and certain other contaminants can damage the TAC media, reducing its effectiveness
and shortening its life. Use authentic ecoTAC™ pre-filters to remove these contaminants before your
TAC filter. Chlorinated city water should generally be filtered through activated carbon to reduce
chlorine prior to TAC treatment.
Water exceeding any of the following levels should be pre-treated to
reduce contaminant levels below the stated level:
Total hardness: <50 grains per gallon (850 ppm)
pH Range: 6.5 to 8.5
Chlorine: max. 3 ppm
Hydrogen peroxide: max. 0.5 ppm
Iron: max. 0.3 ppm
Manganese: max. 0.05 ppm
Copper: max. 1.3 ppm
Hydrogen Sulfide (H2S), Polyphosphates, and Oils: must be removed
Maximum Water Temperature: 43C (110F)
Do not allow TAC media or the water in your ecoTAC™ system to freeze
Pressure Recommended: 15 to 80 psi
CONFIRM THAT YOUR WATER CONDITIONS MEET THE OPERATING CONDITIONS ABOVE BEFORE
COMMENCING THE INSTALLATION PROCESS. IF IN DOUBT, CALL YOUR DEALER FOR ADVICE.
INSTALLATION
While we strongly recommend that a licensed plumber perform all installation work, a mechanically-
inclined homeowner can install an ecoTAC™ system. In all cases, it is critical that the installation be
done in accordance with these instructions and all applicable plumbing codes. Be sure to obtain all
required permits. If these instructions and the applicable codes are in conflict, the relevant
plumbing/electrical code shall be followed. Equipment failure, personal injury, or property damage
can result if this equipment is not installed properly.
You will need the following plumbing supplies: