background image

 

Range 1 

– AMS100 

Operating instructions

 

 

ECOSAFE | Date du document : 29/04/2019 – Version : 01 

 

1.  DESCRIPTION / USE 

 

Flammable products have to be stored in safety cabinets. These have to be equipped with a containment sump and a locking system.  

This range of cabinets possesses (for the big models) CO2 extinguishers, which occur automatically from 65°C. They also have  a big 

retention capacity at the bottom of the cabinet. 

 

2.  TECHNICAL FEATURES 

 

Compliance :  

 

Compliance with the specifications CNPP FSE 98-006 

 

Pictogrammes  normalisés  conformes  aux  normes  ISO  3864,  ISO  7010  et  NF  X08.003,  et  à  la  directive  européenne 

92/58/CEE 

 

Standardized pictograms, compliant with the standards ISO 3864, ISO 7010, NF X08.003 and the directive 92/58/CEE 

 

Technical features :  

 

Construction in 15/10th steel + yellow epoxy paint RAL 1023 

 

Standardized pictogram for flammables provided  

 

Two swing doors 

 

Self-closing doors 

 

Locking-system 

 

CO2 extinguisher provided (500g), automatic triggering by thermal bulb between 65 and 72°C 

 

Sloping roof  

 

High retention capacity 

 

External dimensions : H 1500 x W 800 x D 400 mm 

 

Internal dimensions : H 1250 x W 780 x D 370 mm 

 

Storage capacity : 100 liters 

 

Retention capacity : 112 liters 

 

Loading capacity : 50 KG 

 

Weight : 70 KG 

 

3.  INSTALLATION AND COMMISSIONING 

 

Installation 

 

The safety cabinet has to be installed on a flat surface that can bear its weight with the products inside.  

Ensure  that  the  safety  cabinet  is  correctly  wedged,  as  for  the  cabinet  not  to  topple,  and  for  the  automatic  locking  system  to  work 

correctly. The eventual blocking has to be done by the user.  

 

The correct leveling of the cabinet must cart off any distortion of the frame, allow the doors to be strictly parallel compared to the frame, 

and take away any rubbing of the doors on the cabinet’s frame.  

 

The installation location must guarantee :  

 

That it is not exposed to any heat source 

Содержание AMS100

Страница 1: ...Range 1 AMS100 Operating instructions ECOSAFE Date du document 29 04 2019 Version 01 0 Instruction manual For safety cabinet Model AMS100 ...

Страница 2: ...CONTENT 1 Description Use Page 2 2 Technical features Page 2 3 Installation and commissioning Page 2 4 Internal equipments Page 3 5 Storage Page 3 6 Ventilation Page 3 7 Safety controls Page 4 8 Spare parts Page 5 9 Recycling Page 5 10 Warranty Page 6 11 Control sheet for the user Page 7 ...

Страница 3: ...ram for flammables provided Two swing doors Self closing doors Locking system CO2 extinguisher provided 500g automatic triggering by thermal bulb between 65 and 72 C Sloping roof High retention capacity External dimensions H 1500 x W 800 x D 400 mm Internal dimensions H 1250 x W 780 x D 370 mm Storage capacity 100 liters Retention capacity 112 liters Loading capacity 50 KG Weight 70 KG 3 INSTALLAT...

Страница 4: ... The cabinet is provided with 3 perforated shelves These must be fixed at the chosen height thanks to the rack and pinion Take care not to exceed the loading capacity per shelf of 50 KG The cabinet also has an integrated retention tank provided with a drain plug positioned under the cabinet It should not be used as a storage area Its retention capacity is 112 liters 5 STORAGE Your safety cabinet i...

Страница 5: ...n a healthy fashion Filtration boxes are delivered with the activated carbon filter that you need to renew once a year Running without any mechanic ventilation It is possible for your safety cabinet to run without mechanical ventilation However your cabinet has to be placed in a location that provides its own ventilation system at least 5 times the volume of the location per hour The cabinet itsel...

Страница 6: ... again every 5 years or less in the presence of a DRIRE expert who will stamp his validation after the test We recommend you to check the CO cartridge every year to insure they do not present any traces of oxydation which could lead to their deterioration and that the CO charges are wihtin the indicated limits These verifications must be conducted by your maintenance service If you encouter any pr...

Страница 7: ...house The spare parts are under 3 months warranty upon their settlement The warranty cannot be applied in the following cases The equipment has not been stored used or maintained in accordance with the standards by the user In case of a damage of the equipment by the user or a third party The equipment had a modification or a repair by the user or a third party without any prior written authorizat...

Страница 8: ...he closing of the doors are working correctly The locking system of the doors works correctly The CO2 extinguisher has been controlled The standardized pictogram on the door is in good condition and visible The door hinges are lubricated The locking system is lubricated The shelves and the containment sump are clean Remarks Date By Signature ...

Отзывы: