9.2

 

P

OTENTIOMETER

/

S

 

 

9.2.1

  The potentiometer shaft is frictioned and is accessible from the upper side 

inside the gear motor.  

 

9.2.2

  Disconnect the cables connected with the regulation system from the 

respective terminals n. 30, 31 and 32 [Pot. A] and, if necessary, n. 33, 34 and 

35 [Pot. B]. 

 

9.2.3

  By means of a suitable screwdriver with 5 mm cut rotate the potentiometer 

shaft and measure the resistance value of 0 Ohm between terminals n. 31 and 
32 and, if necessary, also between terminals n. 34 and 35 when the valve is 
closed [picture 2]. 

 
 
 
 
 

 
 
 
 
 

 
 
 
 
 
 

 
 
 

 

 

 

   

   Picture 

 

9.2.4

  By rotating the potentiometer: 

 clockwise 

3

 

the resistance value increases 

 counter dock wise 

4

 

the resistance value decreases 

 

9.2.5

  The gearbox between the gear motor shaft and the potentiometer shaft is 

foreseen for a 90° rotation angle between closed valve and totally open valve. 

 

Hence should the gear motor opening be reduced with a rotation angle lower 

than 90°, the variation of the potentiometer resistance value will be 
proportionally reduced. 

 

If, vice versa, the rotation angle had been wrongly adjusted over 90° there 
will be no increase in the resistance value beyond the plate maximum value. 

 

 

Содержание MPV Series

Страница 1: ...IC CONNECTIONS 4 5 WIRING 5 5 1 WITHOUT MANUAL AUTOMATIC CONTROL STATION 5 5 2 WITH MANUAL AUTOMATIC CONTROL STATION 6 6 AUXILIARY MICROSWITCHES 7 7 POTENTIOMETER S 7 8 CONTROL STATION 7 9 CALIBRATION...

Страница 2: ...g conditions interchangeable without removing he valve from the plant WARNING Installation wiring adjustment and maintenance of gear motors must be carried out exclusively by skilled and authorized se...

Страница 3: ...ions 3 5 Remove the protection plugs installed on the valve body 3 6 The sealant must be applied only on the piping outer threading and not on the valve inner threading Use gas suitable sealants only...

Страница 4: ...es must comply with local prescriptions and in any case their section must be ranging between 1 and 1 5 mm2 Connection piping recommended H07V U G1 5 mm2 4 6 Wiring diagrams are reported in the attach...

Страница 5: ...ATION TERMINAL BOARD Terminal earthing Terminal N1 N neutral Terminal L2 by tension the valve closes Terminal 3 by tension the valve opens Terminal 4 for manual electric operation Terminal 16 answer s...

Страница 6: ...0 common contact from the auxiliary microswitch S3 Terminal 21 normally open contact of the auxiliary microswitch S3 Terminal 22 normally closed contact of the auxiliary microswitch S3 Terminal 23 com...

Страница 7: ...e does not correspond to the wished one proceed as indicated in paragraph 9 2 of chapter 9 CALIBRATIONS Absorbed power is 2 W for each potentiometer 8 CONTROL STATION 8 1 The control station enables t...

Страница 8: ...rst the lever on its curved side to move the blue cam to a more suitable position to perform adjustment picture 1 Picture 1 9 1 6 To calibrate refer to the mechanical position indicator disc the valve...

Страница 9: ...een terminals n 34 and 35 when the valve is closed picture 2 Picture 2 9 2 4 By rotating the potentiometer clockwise 3 the resistance value increases counter dock wise 4 the resistance value decreases...

Страница 10: ...echanically 9 3 7 Select the AUTO position 9 3 8 Set the adjustment device on 6 mA or on 2 Vdc and wait up the servocontrol moves then take it back to 4 mA or on 0 Vdc and check it reaches 0 degrees 9...

Страница 11: ...cock can be opened and the operating test can be carried out 11 MAINTENANCE AND CHECKS 11 1 The MPV valve does not require any special maintenance Both the valve body and the actuator do not need any...

Отзывы: