9.4

 

M

AX

.

 CAPACITY ADJUSTMENT

 

 

9.4.1

  To reduce the max. capacity fit a 3 mm hexagon socket screw in the suitable 

seat on the lower part of the valve body and rotate it counterclockwise 

4

 

9.4.2

  The MPV valves are supplied by the factory adjusted for the max. capacity. 

 

 
 

10.

 

START-UP 

 

10.1

  Before starting the system up, carefully check the following points of the MPV 

valve: 
-   correct installation according to the flow direction 
- gas 

outer 

seals 

-  correct electric connections and grounding 
-  perfect electric and mechanical operation by opening and closing with closed 

gas main cock. 

 

Once preliminary conditions compliance, the gas main cock can be opened and 
the operating test can be carried out. 

 

 
11.

 

  MAINTENANCE AND CHECKS 

 

11.1

  The MPV valve does not require any special maintenance.  

 

Both the valve body and the actuator do not need any lubrication. 

 

11.2

 At least once a year, and above all for systems subject to vibrations, it is 

recommended to check the harness for faulty contacts of the terminal board 
and to tighten the screws. 

 
 

12.

 

REPLACEMENT 

 
 

For replacement of MPV valve, operate as follows: 

 

12.1

  Close the gas main cock. 

12.2

  Cut off the supply voltage to the valve. 

12.3

  Remove the actuator cover. 

12.4

  Disconnect all the electric connections, noting the cable numbers. 

12.5

  Remove the valve body from the piping. 

12.6

  Install the new valve according to the instructions of the previous chapters. 

 
 
These instructions can be subject to possible variations without notice. 

 

Содержание MPV Series

Страница 1: ...IC CONNECTIONS 4 5 WIRING 5 5 1 WITHOUT MANUAL AUTOMATIC CONTROL STATION 5 5 2 WITH MANUAL AUTOMATIC CONTROL STATION 6 6 AUXILIARY MICROSWITCHES 7 7 POTENTIOMETER S 7 8 CONTROL STATION 7 9 CALIBRATION...

Страница 2: ...g conditions interchangeable without removing he valve from the plant WARNING Installation wiring adjustment and maintenance of gear motors must be carried out exclusively by skilled and authorized se...

Страница 3: ...ions 3 5 Remove the protection plugs installed on the valve body 3 6 The sealant must be applied only on the piping outer threading and not on the valve inner threading Use gas suitable sealants only...

Страница 4: ...es must comply with local prescriptions and in any case their section must be ranging between 1 and 1 5 mm2 Connection piping recommended H07V U G1 5 mm2 4 6 Wiring diagrams are reported in the attach...

Страница 5: ...ATION TERMINAL BOARD Terminal earthing Terminal N1 N neutral Terminal L2 by tension the valve closes Terminal 3 by tension the valve opens Terminal 4 for manual electric operation Terminal 16 answer s...

Страница 6: ...0 common contact from the auxiliary microswitch S3 Terminal 21 normally open contact of the auxiliary microswitch S3 Terminal 22 normally closed contact of the auxiliary microswitch S3 Terminal 23 com...

Страница 7: ...e does not correspond to the wished one proceed as indicated in paragraph 9 2 of chapter 9 CALIBRATIONS Absorbed power is 2 W for each potentiometer 8 CONTROL STATION 8 1 The control station enables t...

Страница 8: ...rst the lever on its curved side to move the blue cam to a more suitable position to perform adjustment picture 1 Picture 1 9 1 6 To calibrate refer to the mechanical position indicator disc the valve...

Страница 9: ...een terminals n 34 and 35 when the valve is closed picture 2 Picture 2 9 2 4 By rotating the potentiometer clockwise 3 the resistance value increases counter dock wise 4 the resistance value decreases...

Страница 10: ...echanically 9 3 7 Select the AUTO position 9 3 8 Set the adjustment device on 6 mA or on 2 Vdc and wait up the servocontrol moves then take it back to 4 mA or on 0 Vdc and check it reaches 0 degrees 9...

Страница 11: ...cock can be opened and the operating test can be carried out 11 MAINTENANCE AND CHECKS 11 1 The MPV valve does not require any special maintenance Both the valve body and the actuator do not need any...

Отзывы: