7 of 11
6.
AUXILIARY MICROSWITCHES
On request, the valve can be equipped with 2 auxiliary microswitches that can be
adjusted in any position.
Microswitches are voltage-free.
The contact capacity is 5 A/250 Vac with ohmic load and 1 A/250 Vac with inductive
load.
Contact rating is about 5 A/250 with Ohm load and about 1 A/250 with inductive load.
For adjusting the cams of auxiliary microswitches, proceed as for cams of endswitches
as indicated in paragraph 9.1 chapter 9 “CALIBRATIONS”.
7.
POTENTIOMETER/S
On request, the valve can be equipped with 1 or 2 independent potentiometers [pot. A
and
/
or
Pot. B] for the answer signal of the valve position.
Resistance value of the potentiometer is indicated on the identification label.
If the resistance value does not correspond to the wished one, proceed as indicated in
paragraph 9.2 of chapter 9 «CALIBRATIONS».
Absorbed power is 2 W for each potentiometer.
8.
CONTROL STATION
8.1
The control station enables the manual electric activation of the valve.
8.2
Phase L must be connected to the terminal no. 4.
8.3
The AUTO/MAN switch is delivered by the factory in AUTO position .
8.4
Set the AUTO/MAN switch in the manual position indicated by stylized hand
8.5
Activate the Open/Stopped/Closed switch as follows:
8.5.1
Keeping the lever pushed towards the symbol
◄
the valve opens [the cam S2
adjusts the desired final opening position].
8.5.2
Keeping the lever pushed towards the symbol
►
the valve closes [the cam S1
adjusts the desired final closing position].
8.5.3
Positioning the lever to the centre, the valve motor is not activated.
8.5.4
ATTENTION: after the operations for manual electric activation of the valve,
reset the AUTO/MAN switch onto AUTO
position
.