AR2…SE.. Instructions
12
Form 120127
10.4
E
LECTRONIC
C
ONFIGURATION
AR2…SE5
I
NPUT SIGNAL
4-20
M
A
DIP SWITCH POSITION
D
IP
S
WITCH
D
IP
S
WITCH
O
N
LEFT
O
FF
D
IP
S
WITCH
O
N
RIGHT
O
N
1
Clockwise Rotation
(from Power End side)
Counter-Clockwise Rotation
(from Power End side)
2
Low Resolution 125 steps
High Resolution 200 steps
3
4
Please refer to the below reported scheme
5
N.A.
Input Signal 4 – 20 mA
6
N.A.
DS-6 MUST be turned ON
** For special setting please look here below:
3
•
4
OFF
•
ON
DS-3 turned ON and DS-4 turned OFF. Actuator rotates for 90°
with Mid-Low Input Signal. For example 4-12 mA with rotation of
90°.
3
•
4
OFF
•
ON
DS-3 turned OFF and DS-4 turned ON. Actuator rotates for 90°
with Mid-High Input Signal. For example 12-20 mA with rotation of
90°.