Installation & Operation Manual Proven Quality since 1892
ECON actuator Fig. 7907, type ELA80
–
3000
Rev.19
–
April 2, 2021
7
3.1.3 ELA-Series Options
EXD
Flameproof enclosure
EXTB
Dust ignition proof
WTA
Watertight enclosure (IP68 (10m/72hr) Nema 6P
ATS
Additional torque switches (SPDT x 2ea, 230VAC
–
16A)
EXT
Rotating extension - 120°, 180° or 270° (90° is standard)
ALS
Additional limit switches (SPDT x 2ea, 230VAC
–
16A)
PIU
Potentiometer unit (0~1
KΩ)
PCU
Proportional control unit (input, output 0~10 VDC, 4~20mA DC)
CPT
Current position transmitter (output 4~20mA DC)
ADCM
AC/DC Multi-board
SICU
Semi-Integral Control Unit (LCU-B + IMS + phase protect indicator) (5W max.)
ICU
Intelligent Digital Control Unit (LCU-C + IMS + auto phase discriminator) (5W max.)
PRB
ProfiBus (5VDC, 0.1A max., in redundant configuration, multiplied by 2)
MOB
ModBus (5VDC, 0.1A max., in redundant configuration, multiplied by 2)
3.1.4 Duty Cycle
Duty cycle rating according IEC60034-1 S4. See table in paragraph 3.1.2 for rating figures.
Exceeding the actuator
’
s rated duty cycle may cause thermal overload
.
Intermittent duty S4
The duty is a sequence of identical cycles which consist of starting time, operation time with constant
load and rest period. The rest period allows the machine to cool down so that thermal equilibrium is
not reached. The relative on-time at S4-25% or S4-50% is limited to 25% and 50% respectively.
3.1.5 Space Heater
Condensation in the actuator is possible due to wide fluctuation of the ambient temperature. The
heater integrated in the control unit prevents this in general.
Ceramic housing with thermostat to prevent over heating with 60
℃
set temperature.
Heating Element
Self-regulating
Voltage Range (ELA80~100) (based on the power supply)
115V
5W 4.5K
Ω
J
230V
5W 18K
Ω
J
24V DC
5W 200
ΩJ
12V DC
5W 47
Ω
J
Voltage Range (ELA150~3000) (based on the power supply)
115V
10W 2K
Ω
J
230V
10W 8K
Ω
J
24V DC
10W 100
ΩJ
12V DC
10W 27
ΩJ
3.1.6 Hand Wheel and Declutching
ELA-series actuators are provided with a declutchable manual override
system.
•
In order to manually operate the actuator, pull the manual
override lever towards the hand-wheel until. It will remain in position.
•
Turn the hand-wheel until the valve reaches the required position.
•
Turn clockwise to close and counter-clockwise to open.
Note: The manual override lever returns automatically to auto-position
when the actuator is operated electrically.