ECON actuator Fig. 7907, type ELA80
–
3000
Rev.19
–
April 2, 2021
12
4.3
Limit Switch Setting
•
Rotate the hand wheel of the actuator manually to the fully closed position of the valve.
•
Use an Allen key, loosen the set screw of the CLOSE limit switch cam
•
Rotate the CLOSE cam CW until the limit switch
‘
click
s’
(see Figure 1)
•
Tighten the set screw with the Allen key
•
Manually rotate the hand wheel of the actuator to the fully opened position of the valve
•
Use an Allen key to loosen the set screw of the OPEN limit switch cam
•
Rotate the OPEN cam CCW until the limit switch
‘
click
s’
(see Figure 2)
•
Tighten the set screw with the Allen key
.
DANGER:
H
AZARDOUS VOLTAGE.
Make sure all incoming power is disconnected before setting the limit switches