background image

10

System start-up

Make sure all topics in the installation part of this manual is resolved before starting the start-up phase. Depending 
on our specific setup, you might have additional parts to consider.

Step by step

1.

Make sure all relevant parts for your system is installed and ready, as described in the installation section.

2.

Make sure

 

system (9) is not turned on at this time.

3.

Close flow regulation valve (7)

4.

Disconnect hose from bottom of mixing tank (4).

a.

Unscrew the ½ inch hose connection to allow water out of the small tank (4).

5.

Open water connection to system (max 85 psi)

6.

Vent dosing units, by pressing button on top of unit (3&5). Hold down the button until the water

 

flows out in a steady stream.

7.

Prime the dosing unit (3) by running the unit until HCL is socked into the unit body. Dosing unit scale

 

can be adjusted to allow faster filling of hose and unit.

8.

Adjust dosing unit scale to half way position.

9.

Let dosing unit run and check pH level in mixing tank. Allow adequate time for changes to take effect

 

after any changes. Mixing tank pH level should be between pH 1 and 1.5 depending upon feed water

 

pH. The pH level can be adjusted using the scale on dosing unit 1. Moving the ‘Handle” on the scale

 

up, lowers the pH level in the tank (4).

10.

When desired pH level is reached the hose at the bottom of tank (4) can be reattached.

11.

Let tank (4) fill with water at the correct pH level and make sure the float valve controls the level as

 

intended.

12.

Adjust scale on dosing unit 5 to 50 % (half way).

13.

There are two different ways to do the next part.

a.

Run system

b.

Disconnect water inlet (8) from system and let the solution run into a bucket for

 

testing

 

and then 

drain.
For this start up instruction, I have chosen to use option b.

14.

Open flow valve to allow the solution to flow into the bucket.

15.

Let the solution run into the bucket and watch dosing unit 2 suck in the solution from mixing tank (4).

16.

Test the pH level of solution running into the bucket. The pH level at this point should be 1 to 2 pH

 

below the desired final product. The exact pH level depends on the setting of the system.

17.

The pH level can be adjusted using the scale on the second dosing unit. Adjusting the “handle” up

 

towards the unit body will lever the pH level of the solution.

18.

When the correct pH level has been reached close the flow valve to stop the flow.

19.

Reattached the hose to the system inlet (8)

20.

 

Open the flow control valve. The valve can be adjusted to the desired flow rate later on.

The pressure regulator has been adjusted to 45 psi from factory and therefore does not need further adjustments.

Содержание E-1200

Страница 1: ...E 1200 System prebuilt with pH Control Installation OperationManual EcoloxTech Tel 1 954 900 6070 service ecoloxtech com ...

Страница 2: ...w preventer 4 Water filter 4 Dosing unit 4 Holding tank 5 Pressure reduction valve 5 Flow control valve 5 Level pump control 5 Installation 6 6 6 7 7 7 7 8 8 8 9 9 9 System start up 10 Step by step 10 Calibrating the level sensor 11 Pump start up 11 Spare parts list 12 ...

Страница 3: ...g units d Holding tank with float valve e Pressure reducer f Flow control 2 E 240 or 1200 unit 3 Control box Pump level g Level sensor 4 HOCl storage tank option not on picture 5 Distribution pump option not on picture 6 Brine tank option not on picture 6 shows location 7 Hydrochloric acid HCl connection Picture 1 Shows system components arrows shows flow direction ...

Страница 4: ...sing unit c uses the waters pressure to mix in a concentrate The injection rate of the concentrate can be adjusted using the scale at the bottom of the unit The dose of concentrate will be directly proportional to the volume of water entering the unit regardless of variations in flow or pressure The ratio can be adjusted using the scale shown in picture 5 Make sure the locking ring at the bottom o...

Страница 5: ... system The E 1200 E 240 system has a maximum allowed pressure of 50 psi This is to protect the internal parts of the system The pressure reduction valve e is pre adjusted from factory to 45 psi so no action is needed from the customer side Flow control valve The flow control valve f can adjust the flow though the system The flow can be adjusted to anything within the system flow range For the E 1...

Страница 6: ...ndicate additives used in the process Process steps 1 Blue color The blue color is normal water before any changes are made The water inlet splits up into two separate streams The water that goes into dosing unit 3 is a low flow rate The main part of the water goes though dosing unit 5 2 Red color The red color indicates the addition of the purple product HCl The HCl is added to the water in dosin...

Страница 7: ...r is lowered into the tank used for the brine Filter and additional hose is included in the system Additional information on the specific system can be found in the unit s manual E1200 unit https www ecoloxtech com pdf e1200soperationmanual pdf E240 unit http ecoloxtech com pdf e240soperationmanual pdf Power connection Depending on what options have been chosen the power is connected differently T...

Страница 8: ...system using the hose in picture 14 The hose is run out though the hole in the bottom left side of the unit Avoid having height differences in system and brine tank location System pump cannot handle more that 2 3 meters height difference Try to keep the length of the brine hose at a minimum Hydrochloric Acid Hydrochloric Acid is connected at location 11 on picture 10 purple arrow The concentratio...

Страница 9: ... only be installed in one position make sure the M12 connector is connect straight and all the way do not use any tools The ultrasonic level sensor is mounted to the HOCl storage tank in a way that leaves a free line of sight to the measured liquid The sensor has a dead band of 300 mm meaning that the sensor has to be minimum 300 mm from the measured liquid Maximum range of the default sensor is 3...

Страница 10: ...ndle on the scale up lowers the pH level in the tank 4 10 When desired pH level is reached the hose at the bottom of tank 4 can be reattached 11 Let tank 4 fill with water at the correct pH level and make sure the float valve controls the level as intended 12 Adjust scale on dosing unit 5 to 50 half way 13 There are two different ways to do the next part a Run system b Disconnect water inlet 8 fro...

Страница 11: ...we are outside the 3 meter range 2 Install the sensor in the desired location Make sure there are no edge the sensor can see If the sensor sees sharp edges the reading will be off 3 Push and hold the analog button for longer than 2 seconds Power LED off Output LED on 4 Hold a piece of cardboard at the position which equals 100 full tank 5 The red LED signal must be on of flashing 6 Click analog bu...

Страница 12: ...e SKU T 1137 14 3 4 Insert x 3 4 MPT Adapter Elbow SKU P 1029 23 1 4 OD Silicone Tubing SKU T 1126 6 3 4 Socket PVC Union SKU P 4488 15 3 4 Reinforced Tubing 70 psi SKU T 1040 24 Foot Valve Strainer 1 4 OD SKU T 1026 7 3 4 Socket PVC 90 Degree Elbow Sch 40 SKU P 4510 16 3 4 Insert x 3 4 MPT Adapter SKU P 1028 25 Compact Float Valve Yellow Black SKU P 4519 8 3 4 Socket x Socket x FPT PVC Tee Sch 40...

Отзывы: