BURNER INSTALLATION
HYDRAULIC CIRCUIT
VS
V2
V1
4
5
1
-
HOSE
2
-
OIL FILTER
3
-
OIL COCK
4
-
SUCTION
5
-
RETURN
1 - BURNER
2 - NUT
3 - WASHER
4 - GASKET
5 - BOLT
6 - BOILER
7 - GASKET
To correct length of pipes is calculated by summing up the length of all vertical and horizontal right sections and bends. The static
suction head will be the distance between the non-return valve and the
burner’s pump axle. The depression must not be greater than 0.45 bar; should it be higher, some damages could occur to the
pump, with consequent increase in mechanical noises and ,eventually, a failure.
MAXIMUM LENGTH OF SUCTION LINES FOR TWO-PIPE SYSTEM
H
H
H (m)
ø 14 mm ø 16 mm
0
0,5
1
2
3
3,5
22
25
30
35
3
8
40
3
8
45
50
60
70
8
0
ø 14 mm ø 16 mm
16
1
8
20
25
29
31
29
33
37
44
52
55
J 7
(m)
H (m)
ø 14 mm ø 16 mm
0
0,5
1
2
3
3,5
25
20
1
8
10
5
2
45
3
8
33
20
10
4
ø 14 mm ø 16 mm
16
14
12
7
3
1
29
26
22
14
7
4
AJ 6
(m)
J 7
(m)
AJ 6
(m)
Two-pipe lift system
Two-pipe siphon feed system
Pipe length
Pipe length
1
1
2
3