![Ecoflam MAIOR P 15 AB Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/ecoflam/maior-p-15-ab/maior-p-15-ab_manual_2354148008.webp)
B
LB493
Maior P 15/25/35 AB
HYDRAULIC CIRCUIT
ADJUSTMENT DATA
NOZZLE : DANFOSS H÷S 80°÷60°; DELAVAN W 60°; STEINEN S 60°
NOZZLE
PUMP
OUTPUT
FIRING HEAD SETTING
AIR DAMPER ADJUSTMENT
PRESSURE SIDE
SUCTION
GPH
SPRY
bar
kg/h
Pos.
Pos.
Pos.
2.00
60°
15
9,3
1
MIN
MIN
2.25
60°
15
10,4
2 ÷ 3
2.50
60°
15
11,6
3 ÷ 4
2.75
60°
15
12,8
5 ÷ 6
3.00
60°
16
14,4
6 ÷ 7
MAX
MAX
2 x 1.50
60°
12
12,48
1
MIN
MIN
2 x 1.75
60°
12
14,58
2 ÷ 3
2 x 2.00
60°
12
16,66
4 ÷ 5
2 x 2.25
60°
12
18,74
5 ÷ 6
2 x 2.50
60°
12
20,82
6 ÷ 7
2 x 2.75
60°
12
24,4
7
MAX
MAX
MAIOR P15AB
MAIOR P 25 AB
MAIOR P 35 AB
H
H
ø 8 mm
ø 10 mm
0,5
1
1,5
2
2,5
3
3,5
30
35
40
45
50
55
60
65
70
75
80
85
90
95
ø 8 mm
ø 10 mm
0,5
1
1,5
2
2,5
3
3,5
23
21
19
17
14
9
4
55
50
45
40
34
28
22
H
(m)
H
(m)
MAXIMUM LENGTH OF SUCTION LINES FOR TWO-PIPE SYSTEM
Two-pipe lift system
Two-pipe siphon feed system
Pipe length
To correct length of pipes is calculated by summing up the length of all vertical and horizontal right sections
and bends. The static suction head will be the distance between the non-return valve and the
burner’s pump axle. The depression must not be greater than 0.45 bar; should it be higher, some damages
could occur to the pump, with consequent increase in mechanical noises and ,eventually, a failure.
Pipe length
V2
V1
V2
V1
4
5
4
5
MAIOR P 25-35 AB
MAIOR P 15 AB
1 - HOSE
2 - OIL FILTER
3 - OIL COCK
4 - SUCTION
5 - RETURN
3
2
1
1