6
www.ecoflam-burners.com
EN
420010487501
BURNER DESCRIPTION
VGD 20.503 Rp 2” / VGD 40.065 - 40.080 - 40.100 - 40.125
1. Main gas pipe
2. Ball valve
ACS
3. Antivibration coupling
ACS
5. Min gas pressure switch
EXPOR
T
GAS TRAIN
EN676
6. Safety gas valve + 10. Actuator
7. Working gas valve + 11. Actuator
8. Gas leakage control
KITTC *
9. Gas filter
ACS
KIT - MAX Gas pressure switch
KITPRES
ACS - Gas train connection pipe
GTCP **
!
GTCP-...* WARNING:
in order to fit the gas train, the corresponding connection pipe must be ordered (GTCP size and fitting depend on the
burner and the gas train selected).
!
WARNING:
EN676 compulsory kit and accessories in order to comply to the safety regulations. Additional accessories and kits
shall be installed by the installer in accordance to the local safety regulations and codes of practise.
HOW TO INSTALL THE GAS TRAIN INTO THE BURNER AND CALCULATE THE OVERALL DIMENSIONS
:
refer to the dimension page and thE gas train manual for all detailed information
Gas governor / Filter
FGDR - FILTER
Compulsory EN676
Tightness control
KITTC- Model
Compulsory > 1200 kW
Max Pressure switch
KITPRES50
KITPRES150
Other accessories
1
2
3
9
11
8
10
5
6
7
M
Air
Gas
313
160
142
141
120
150
314
349
151
100
143
To be supplied by the installer
To be supplied by the installer
150 Throttle
valve
151 Gas train Siemens VGD....
160
Kit
tightness control (optional)
313 Min.gas pressure switch
314 Max.gas pressure switch (optional)
349 Air/gas damper motor
144
Gas train - Kit - Accessories: assembly to the burner
MATCHING GAS TRAIN WITH DIAGRAM OF PRESSURE DROPS
ARE IN THE DEDICATED SECTION OF THIS MANUAL
Ecoflam gas trains are delivered separately for all gas and dual fuel burners and are available in different configurations:
Double gas valves with actuators and regulator VGD Siemens and min pressure ACS gas filter
Modulation Kit
KITMD-RWF50
Probe-...