OPERATING TROUBLE

In case of operating trouble it should be
checked whether the system is in proper
working order.

Make a check for the following:
1. Availability of fuel. 
Availability of gas in the line at sufficiently
high pressure. 
Correct position of fuel selector switch.
2. Availability of electric power in the
burner system.
3. Proper functional order and setting of all
control and safety instruments such as

temperature controller, safety limiter, water
failure cut-out, electrical limit switches, etc.
If the trouble is not found to be due to any
of the above-mentioned points it will be
necessary to test the burner functions very
carefully.

Prevailing conditions:
The burner will be found to be out of
operation and in faulty and interlocked
position.
Proceed with searching for the cause of
the trouble and eliminate it. Unlock the

control box by pressing the fault eliminate
key and start the burner.
Do not press the fault eliminate key longer
than 10 seconds.
The start-up program will be initiated and
should be carefully monitored. 
The possible cause of the fault may be
quickly found by reference to the fault
indicator of the control box and watching
the start-up and operating program.

Control program in the case of trouble
and fault indicator LFL 1... / LGK 16...

LFL 1... / LGK 16...

a-b   

Starting program

b-b’

In a number of time versions; idle 

steps of the program unit to self-stop after
burner start-up (b’ = operating position of
program unit)

b(b’)-a

After-flushing program after 

regular stop. In the starting position “a” the
program unit will automatically stop or
initiate an immediate restart of the burner,
e.g. after a fault has been eliminated

•   Duration of the safety period for single-
tube burners

••   Duration of the safety period for
burners with ignition gas valve

Basically, any type of trouble will result
in the immediate stop of the fuel supply.

At the same time, the program unit and
consequently the fault indicator will stop.
The type of trouble can be identified by the
symbol opposite to the reading mark of the
indicator:

◄   

No start

, e.g. because the “CLOSED”

signal from the “Air Damper CLOSED” limit
switch is missing or a contact is not closed
between terminals (12) and (4) or (4) and
(5); or the contacts of all control and safety
units in the controlled system are not
closed (e.g. gas pressure or air pressure
switches, temperature or pressure
switches, temperature or pressure
regulators).

▲   

Operating stop

because the “OPEN”

signal from the “Air Damper OPEN” limit
switch is missing. 
Check and adjust the limit switch
concerned.

P   Shut-off on trouble because there is
not air pressure

signal at the beginning of

the air pressure check. 

Any air pressure failure after this time
will also lead to a shut-off on trouble.

■   

Shut-off on trouble

because of a fault

in the flame monitoring circuit.

▼   

Operating stop

because the position

signal of the “Partial Load” limit switch (air
damper in “Partial Load” position) is not
available on terminal (8). Check and adjust
the limit switch concerned.

1   Shut-off on trouble

because a flame

signal is not available on the expiry of the
(1st) safety time.

Any failure of the flame signal on the
expiry of the safety time will also lead
to a shut-off on trouble. 

2   Shut-off on trouble

because the flame

signal has not occurred on the expiry of
the (2nd) safety time (flame signal of main
flame with burners having an ignition gas
valve).

|   Shut-off on trouble

because the flame

signal failed during burner operation or a
lack of air has occurred.

◄   

Shut-off on trouble

during or after the

control program flow due to external light
(e.g. by flame not extinguished, leaking
fuel valves) or a faulty flame signal (e.g.
fault in flame monitoring circuit, or similar);
see flame monitor.

If the shut-off on trouble occurs at any
other time between start and pre-
ignition that is not identified by a
symbol as above, this will normally be
due to an early flame signal which is
considered to be a faulty flame signal.

The control box may be unlocked

immediately after a shut-off on trouble
using the unlock button with integrated
fault signal lamp or an external switch.
After it has been unlocked (and after a
defect with resultant operating stop has
been eliminated and after a voltage
failure), the program unit will in any case
return to its starting position with voltage
being only supplied to terminals 7, 9, 10
and 11 as preset by the control program. It
is only at this stage that the program of the
control box will restart the 
burner.

420010487501

EN

www.ecoflam-burners.com

24

Содержание BLU TS 3000.1 PR HT

Страница 1: ...GAS BURNERS EN BLU TS 3000 1 PR HT BLU TS 4000 1 PR HT Gas train manual is separate www ecoflam burners com BLU TS 3000 1 PR TC SGT HT 230 50 3143084 BLU TS 3000 1 PR TL SGT HT 230 50 BLU TS 4000 1 P...

Страница 2: ...Head loss diagram 13 Pressure loss diagrams 14 Electrical connections 16 Start up checking procedure 17 Exhaust gas test 18 Start up 19 Adjusting the max air flow rate 19 Firing head setting 19 Servo...

Страница 3: ...ral EN676 directives and guidelines must be observed EN676 compulsory kit and accessories in order to comply to the safety regulations Additional accessories and kits shall be installed by the install...

Страница 4: ...gulations For burners over 1700 kW gas train connection pipe must be ordered Kits and accessories are managed and delivered separately Component type BBCH Burner Body with Combustion Head without gas...

Страница 5: ...ixing flange 9 Air flap regulation 12 Lifting eyebolts 13 Mechanical cam gas 15 Servomotor for gas and air 16 Gas train 19 Gas filter 20 Ball valve 23 Antivibration coupling 24 Tightness control GTCP...

Страница 6: ...TRAIN INTO THE BURNER AND CALCULATE THE OVERALL DIMENSIONS refer to the dimension page and thE gas train manual for all detailed information Gas governor Filter FGDR FILTER Compulsory EN676 Tightness...

Страница 7: ...kcal Nm3 G30 L C V 29 320 kcal Nm3 Emission class std Standard Class 2 GAS EN676 120 mg kWh Control unit Type LFL LGK Gas train GT VGD separate gas train Filter KIT Tightness control Other KIT ACS Gas...

Страница 8: ...the boiler backpressure Example Burner thermal output 8000 kW L flame m 5 m medium value D flame m 1 m medium value WARNING Some flame modifications can be done in our FLEXSHOP in the factory in orde...

Страница 9: ...der to be able to extract it during maintenance Burner boiler mounting flange Packaging only burner WARNING Please follow the suggested dimension for the hole on the boiler flange in order to fit the...

Страница 10: ...m will vary the positions of the gas control valve and air damper and thus regulate the gas flow rate in a linked concept with the air flow rate The burner can either be controlled by a 2 stage slidin...

Страница 11: ...be and the boiler lining must be sealed with appropriate insulating material BURNER LINING Check before burner installation 1 Depending on the type of boiler reverse flame or three pass check the burn...

Страница 12: ...es the result of the leak test must be duly certified VENTING Prior to taking the burner into operation or after any repair work make sure to vent the complete gas feed line and the gas valves and ins...

Страница 13: ...ording to the instructions of the gas train separate manual KITPRES Maximum pressure switch assembly Maximum pressure switch is provided as a kit and shall be assembled into the main gas train accordi...

Страница 14: ...LU 3000 1 PR MULTICALOR 300 1 MULTIFLAM 300 1 VGD 40 100 no neutral 20 700 1C FILTER DN 100 22 700 VGD 40 080 no neutral 30 700 FILTER DN 80 35 700 VGD 40 065 no neutral 45 700 FILTER DN 65 55 700 VGD...

Страница 15: ...Inlet gas pressure MIN mbar Inlet gas pressure MAX mbar Diagram BLU 4000 1 PR MULTICALOR 400 1 MULTIFLAM 400 1 VGD 40 100 no neutral 27 700 2C FILTER DN 100 30 700 VGD 40 080 no neutral 40 700 FILTER...

Страница 16: ...be checked by qualifed personnel The manufacturer declines all responsibility for modifcations or connections different from those shown in the electrical scheme Adapters multiple plugs and extension...

Страница 17: ...be available the exhaust gas duct up to the measuring point must be free of leaks to prevent anomalies in the measurement results GAS START UP Connect the measuring instruments for the gas head pressu...

Страница 18: ...to be exceeded DETERMINING THE VOLUMETRIC GAS FLOW RATE The thermal furnace output of a boiler QF is the amount of heat supplied with the gas in a unit of time When taking the burner into operation t...

Страница 19: ...ut the adjusting Firing head setting Servomotor SQM50 Air damper motor pre setting The cams of the servomotor are set from the factory in order to start the burner and reach the maximum output The fol...

Страница 20: ...the adjustment value of the air pressure switch until to have the burner lockout Remove the obstruction from the air intake screw on the cover C and start the burner by pressing the control box rearm...

Страница 21: ...with air periodically replace it if necessary After the cleaning of the components of the gas train perform the leakage test Make visual inspection of the burner s electrical components and eliminate...

Страница 22: ...duction in the ionization current and cause a safety shut off of the burner due to a flame detection failure In this case check the position of the electrode its electric connection and the earthing o...

Страница 23: ...age controller if necessary X YES Leakage Test failure LDU kit Check contacts clean valves or replace leakage controller if necessary X YES SEQUENCE START Servomotor OPEN position switch not reach Che...

Страница 24: ...not closed between terminals 12 and 4 or 4 and 5 or the contacts of all control and safety units in the controlled system are not closed e g gas pressure or air pressure switches temperature or pressu...

Страница 25: ...he reversible actuator is fitted with a synchronous motor which drives a shaft via a gearbox The shaft end carries a coupling to drive the fuel and combustion air controlling element The SQM actuator...

Страница 26: ...FICATION DESCRIPTION ECN MODIFICATION BLU TS 3000 1 4000 1 5000 1 6000 1 PR SGT QUADRO COMANDI A POZZOBON 28 03 2012 2 420110081300 1 A RIGONI LANDIS SQM 50 481A2 ER RBA12CB103 LANDIS LFL 1 333 1 622...

Страница 27: ...E TERMICO MOTORE VENTILATORE FUSIBILE FILTRO ANTIDISTURBO INTERRUTTORE GENERALE CON FUSIBILE KMV HLB FMV FU FUSE Z Q ESPIA DE FUNCIONAMIENTO LAMPE DE FONCTIONNEMENT LAMPADA DI FUNZIONAMENTO HLF WORKIN...

Страница 28: ...DI TENUTA YVGS YVG F 1 E D 2 3 4 C B A 1 2 3 4 5 6 7 8 F E D 5 6 7 C B 8 A 2 1 3 TOT SHEET SHEET DESIGNER DESCRIPTION DATE FIST CREATION CODE SIGNATURE R D DEPARTMENT CONTROLLER Ecoflam Bruciatori SE...

Страница 29: ...ELETTROVALVOLA GAS SPGmin YVGS YVG YVG YVGS T P SPGmin T P SPGmin YVGS YVG NON UTILIZZATA VI CAMMA DI REGOLAZIONE ARIA BASSA FIAMMA LAVORO CAMMA REGOLAZIONE ARIA ACCENSIONE MINIMA POTENZA CAMMA REGOL...

Страница 30: ...APPENDIX Spare parts list 420010487501 EN www ecoflam burners com 30 19 23 24 2 Blu TS 3000 1 4000 1 PR 1 20 3 4 8 7 10 9 16 11 13 14 15 17 12 21 5 6 22 25 18 26...

Страница 31: ...ELECTRODE 65320891 65320891 10 IONIZATION PROBE 65320892 65320892 11 GAS PIPE TC 65321664 65321664 TL 12 ROD TC 65320242 65320242 TL 65320243 65320243 13 FIRING HEAD 65321666 65321666 14 DISC 65320742...

Страница 32: ...ul to its products without affecting their main features Ecoflam Bruciatori S p A si riserva il diritto di apportare ai prodotti le modifiche che riterr necessarie o utili senza pregiudicarne le carat...

Отзывы: