B
LB 429
Blu 170 ÷ 350 P /P AB
pag.20
N°of holes
Nat.Gas
8
6
L.P.G.
8
4.5
o
Code
BFT12103/1
BFT12103/2
NOTE:
IN CASE OF CONVERSION, PLEASE
CONTACT THE LOCAL ASSISTAN-
CE SERVICE
Model
Power to
kW
kcal/h
Disk
Ring
be burned
position
position
BLU 170/170 AB
up to:
130
112.000
A
2
over:
130
112.000
B
2
BLU 250/250 AB
up to:
140
120.000
C
2
from:
140
120.000
to:
200
172.000
C
1
over:
200
172.000
D
1
Aperto
Chiuso
Aperto
Chiuso
A
B
C
D
BLU 170
BLU 250
POSITIONING THE FRONT DISK FOR NATURAL GAS AND L.P.G.
POSITION OF THE MOVABLE RING
BLU 170
BLU 250
2
1
To modify the burner from Natural gas into L.P.G. and viceversa, proceed as follows: - remove the blast tube A
(see at “Removing the blast tube”); - remove the combustion head D from the adjusting rod G by loosing screw H,
and pull it out from gas tube F; - loosen screw B, pull out part C from head’s front side and the nozzle E
from the rear side; replace nozzle E with the needed one (recognisable from hole’s diameters, as shown
by the table hereby), then reassemble the whole in reverse order.
Note: When the operation is achieved, stick the label (supplied with) corresponding to the
type of gas used, on the existing one; at the end check again the combustion
and adjusting data as well according to the new type of gas.
A
B
C
D
E
F
G
H
MODIFYING THE BLU 170-250 BURNER FROM NATURAL GAS INTO L.P.G. AND VICEVERSA
Natural gas nozzle
L.P.G. nozzle
Elettrodo di
accensione
BLU 350
CON IL DISCO
TUTTO AVANTI
BLU 170-250
2 mm
2 mm
Elettrodo di
rivelazione
POSITION OF ELECTRODES
Open
Open
Closed
Closed
Ignition
electrode
Ionization
probe
WITH THE
DISK ALL
FORWARD