2
Basic safety information
WARNING
Humidity
Electric shock
•
The ecoBatterySystem must be positioned in a dry place.
•
The ecoBatterySystem must be protected against the ingress of water.
•
External cables must be protected against the ingress of water.
•
The ecoBatterySystem must not be cleaned using damp substances.
•
The humidity in the room must be between 5-80%.
ATTENTION
Fire safety
•
The ecoBatterySystem must be installed in a fireproof room with zero fire loading and a
category F30 fire door.
•
The ecoBatterySystem must not be installed in rooms with potentially explosive
atmospheres.
ATTENTION
The ecoBatterySystem is switched off
Deep discharge may damage the ecoBatteryModule
•
The ecoBatterySystem must only be switched off briefly for maintenance purposes.
ATTENTION
Floor conditions
The floor must satisfy the following requirements:
Floor loading
°
ecoBatterySystem Small: at least 300 kg / 0.5 m
2
°
ecoBatterySystem Large: at least 600 kg / 0.5 m
2
•
The floor must have a firm surface.
•
The floor must be clean and level.
ATTENTION
Inadequate ventilation
The ecoBatterySystem may overheat
•
Do not obstruct the ventilation slots
•
Maintain clearances
°
Clearance to the rear: min. 10 cm
°
Clearance to the sides: min. 20 cm
°
Clearance above: min. 20 cm
°
Clearance below: determined by the feet
ATTENTION
External heat input
The product may overheat
•
Keep it out of direct sunlight
•
Do not expose to heat sources
4
TM_ecoBatterySystem_2.2_en-UK