Fault texts
Flame return gate does
not reach CLOSE limit
switch
ڃ
check whether ball valve is jammed, check ball
valve throughway to see if foreign objects are
preventing it from closing
no signal although
closed
ڃ
check cables and flame return gate
Error code:
12
Description:
Both flame return gate limit switches are closed at the same time
Cause and Remedy:
both limit switches
activated
ڃ
check flame return gate, check cables, check
connectors
Display:
Error code:
14
Description:
Container cover open
Cause and Remedy:
Cover open
ڃ
close cover
End-switch defect
ڃ
replace end-switch
Display:
Error code:
15
Description:
DHW sensor fracture, measuring circuit from DHW sensor is open
Cause and Remedy:
sensor not connected
ڃ
connect sensor at input
sensor defect
ڃ
measure sensor (approx. 2k
ˑ
at 25° C) replace if
required
sensor cable defect
ڃ
replace sensor
sensor temperature too
high
ڃ
sensor temperature above measuring range
(1100° C)
Description:
DHW sensor short circuit, measuring circuit from boiler sensor is shorted out
Cause and Remedy:
sensor defect
ڃ
measure sensor (approx. 2k
ˑ
at 25° C) replace if
required
sensor cable defect
ڃ
replace sensor
sensor temperature too
low
ڃ
sensor temperature below measuring range (-
10° C)
200014_EN 1.2
Содержание Easypell 16
Страница 1: ...Installation Manual Easypell 16 32kW ENGLISH 200014_EN 1 2 www easypell com...
Страница 18: ...18 Dismantling the burner casing and burner 200014_EN 1 2...
Страница 55: ...Retrofit motor cleaning device 55 14 2 Retrofit motor cleaning device Installation Manual Easypell 16 32kW...
Страница 56: ...56 Retrofit motor cleaning device 200014_EN 1 2...
Страница 57: ...Retrofit motor cleaning device 57 Installation Manual Easypell 16 32kW...
Страница 63: ......