background image

Eclipse ThermAir T/A Series v1.10, Installation Guide No. 114, 4/7/06

Step 3b:  Ignite the burner 
(Option 2: Burner equipped 
with bypass start gas.)

   

Warning:
This procedure assumes that a flame monitoring 
control system is installed and is serviceable.  It 
also assumes that normal low-fire start is being 
used.

1. 

Drive the gas control valve to low fire.

2. 

Make sure the combustion air blower is running.

3. 

Verify that the adjusting screw on the ratio-regulator is six 
full (360°) turns down from the top.

4. 

Open the flow adjusting valve in the bypass gas line.

5. 

Open the manual gas valve in the bypass gas line.

6. 

Initiate the ignition sequence through the flame monitoring 
control system.

7. 

Verify that the burner has ignited.

  If the burner does not ignite:

a) 

Try to ignite again to purge the air out of the gas piping.

b) 

If the burner does not ignite after one or two additional 
ignition attempts, see the Trouble shooting Guide 
contained in the Maintenance & Troubleshooting section 
of this guide. 

  If the burner has ignited:

a) 

Adjust the bypass flow adjusting valve such that the 
burner is able to maintain a stable flame and an adequate 
flame signal.

b) 

Open all remaining manual gas valves feeding the burner.

Main Gas

Valve Train

2. 

Make sure the combustion air blower is running.

3. 

Open all manual gas valves feeding the burner.

4. 

Initiate the ignition sequence through the flame monitoring 
control system.

5. 

Verify that the burner has ignited.

If the burner does not ignite:
a) 

Try to ignite again to purge the air out of the gas piping.

b) 

If the burner does not ignite after one or two additional 
ignition attempts, see the Trouble shooting Guide 
contained in the Maintenance & Troubleshooting section 
of this guide.

Содержание TA 015

Страница 1: ...Installation Guide 114 4 7 06 ThermAir Burners TA Series version 1...

Страница 2: ...e material itself does not infringe any United States patents No further warranty is expressed or implied We have made every effort to make this manual as accurate and complete as possible Should you...

Страница 3: ...quipment Installation Guide No 114 This document ThermAir Data Sheets Series 114 Available for individual TA models Required to complete design selection Design Guide No 114 Used with Data Sheet to de...

Страница 4: ...at care and follow the instructions Warning Indicates hazards or unsafe practices which could result in severe personal injury or damage Act with great care and follow the instructions Caution Indicat...

Страница 5: ...and Storage 11 Approvals of Components 11 Electrical Wiring 12 Where to get standards 12 Pre installation Checklist 13 Burner 13 Gas Piping 14 Installing the flame sensor 15 Check List After Installa...

Страница 6: ...ion Factors 30 Key to System Schematics 31 Parts Drawing 32 Parts List 33 Parts List continued 34 5 Adjustment Start Stop Cont 21 System 2 Burner adjustment without a ratio regulator 21 Step 1 Reset t...

Страница 7: ...fixed combustion air over a wide gas turndown range An integral gas orifice is provided to ease burner setup The burner is designed to facilitate fixed air operation direct spark ignition simple gas c...

Страница 8: ...Eclipse ThermAir T A Series v1 10 Installation Guide No 114 4 7 06 Blank page...

Страница 9: ...not bypass any safety feature fire or explosion could result Never try to light a burner if it shows signs of damage or malfunction Warning The burner might have HOT surfaces Always wear protective c...

Страница 10: ...ert and trained operator Train new operators thoroughly and have them demonstrate an adequate understanding of the equipment and its operation A regular retraining schedule should be administered to e...

Страница 11: ...inal shipping container Do not drop 3 Protect the components from excessive temperatures and humidity 4 Use appropriate support equipment i e harnesses straps chains etc when lifting burner components...

Страница 12: ...otection Agency Batterymarch Park Quincy MA 02269 The ANSI Standards are available from American National Standard Institute 1430 Broadway NewYork NY 10018 The UL Standards are available from 333 Pfin...

Страница 13: ...ecifications Check the following items voltage frequency and stability of electrical power fuel type and fuel supply pressure adequate fresh clean combustion air humidity altitude and temperature of t...

Страница 14: ...factory assembled and shipped as ordered Note If it is necessary to redirect piping be sure the ratio regulator spring column is pointing up arrow on the ratio regulator points in the direction of gas...

Страница 15: ...be delivered with the flame rod already installed on the burner Note Only specific burner sizes are capable of using a flame rod These models areTA015 025 040 075 and 100 For detailed information on...

Страница 16: ...the main gas valve train 3 Set the high gas pressure switch at 20 above the gas pressure measured at the inlet to the main gas valve train 4 Close all manual valves feeding the burner 5 Try to ignite...

Страница 17: ...e of producing fires and explosions if improperly applied installed adjusted controlled or maintained Do not bypass any safety feature fire or explosion could result Never try to light a burner if it...

Страница 18: ...TA 300 400 500 Note A pressure tap is open when the screw inside the tap is unscrewed approximately half a turn Note Chamber pressure will directly influence air flow from the blower Air flows should...

Страница 19: ...able It also assumes that a normal low fire start is being used 1 Drive the gas control valve to low fire 2 Make sure the combustion air blower is running 3 Verify that the adjusting screw on the rati...

Страница 20: ...orifice differential pressure based upon the desired amount of excess air in the burner 7 Readjust the control valve linkage to achieve the desired high fire gas flow Note TheThermAir gas orifice is...

Страница 21: ...s are still the same after cycling the system several times between high and low fire You must provide a constant pressure to the burner to insure proper burner operation If you are not using a burner...

Страница 22: ...r not bypass start gas is installed on the burner Each procedure is unique and both are outlined below 1 Drive the gas control valve to low fire Note AllThermAir burners are limited to ignition at inp...

Страница 23: ...ry to ignite again to purge the air out of the gas piping b If the burner does not ignite after one or two additional ignition attempts see the Trouble shooting Guide contained in the Maintenance Trou...

Страница 24: ...nd the differential gas pressure needed at high fire Note It is very difficult to measure the very low gas pressures experienced at low fire and it may be necessary to rely on visual inspection of the...

Страница 25: ...ss 2 Check for proper air gas pressures Refer to the ThermAir Data Sheets Series 114 3 Test all the system alarms for proper response signals 4 Check and clean igniter electrodes 5 Check valve motors...

Страница 26: ...omponents are not damaged or distorted the burner nozzle the igniter the flame sensors the combustion tube The nozzle and combustion tube can be inspected without removing the burner from the chamber...

Страница 27: ...gas Gas valve does not open Start up sequence runs but burner does not light Restore the power to the ignition transformer Repair or replace the wiring to the igniter Clean the igniter Clean the threa...

Страница 28: ...Air filter is blocked When equipped with Ratio Regulator Gas pressure going into the burner is too low PROBLEM POSSIBLE CAUSE SOLUTION Check ThermAir Data Sheets Series 114 for fuel orifice and the g...

Страница 29: ...lame sensor or electrical noise in the sensor line No power to the control unit Main power is off Check incoming gas pressure Adjust gas pressure if necessary Check pressure switch setting and operati...

Страница 30: ...pounds sq in psi 14 5 x 10 3 millimeter mm inch in 3 94 x 10 2 MJ m3 normal BTU ft3 standard 2 491 x 10 2 Metric to Metric kiloPascals kPa millibar mbar 10 meter m millimeter mm 1000 millibar mbar kil...

Страница 31: ...s Adjustable limiting orifices are used for fine adjustment of gas flow NC Key to System Schematics These are the symbols used in the schematics 756 710 760 684 742 Symbol Appearance Name Remarks Bull...

Страница 32: ...es v1 10 Installation Guide No 114 4 7 06 32 30 31 32 39 29 17 21 15 16 18 13 5 12 14 11 21 9 7 8 3 1 5 2 23 22 4 37 5 38 35 34 21 20 47 46 48 41 42 36 34 19 40 33 10 6 21 50 49 43 44 24 25 28 26 27 4...

Страница 33: ...2 11 14802 9 10039 1 10039 4 20152 3 23 1 Combustor alloy 14887 6 14887 6 14887 6 20400 20716 1 20716 1 100236 101279 101278 24 1 Block and holder N A N A N A N A N A N A 100013 10013 101161 25 1 Comb...

Страница 34: ...200754 44 1 Filter square 20x20 N A N A N A 101010 101010 101010 202731 202731 202731 44 1 Filter silencer 15405 15405 15405 20505 20505 20505 15407 15407 15407 45 1 Mtr 115 208 230 1 TEFC N A N A N A...

Страница 35: ...Offered By Power Equipment Company 2011 Williamsburg Road Richmond Virginia 23231 Phone 804 236 3800 Fax 804 236 3882 www peconet com...

Отзывы: