Eclipse ImmersoJet v2.20 Design Guide 330, 10/02
P
2
1
4
P
1
2
3
4
Control methodology
ImmersoJet burners use a modulating on-ratio control system
as shown in Figure 3.3. To control the heat delivered by the
burner, adjust the air flow to the burner. The gas flow will
change in proportion to the air flow.
The burner will operate reliably at any input between the low
fire and high fire limits stated on the burner‘s Data Sheet.
S
S
S
S
S
TEP
TEP
TEP
TEP
TEP
3:
3:
3:
3:
3:
C
ONTROL
S
YSTEM
Components
Automatic butterfly valve
Ratio regulator: varies gas flow to
burner in proportion to air flow.
Automatic shut-off valve (optional).
Manual butterfly valve
Safety
valve
train
Figure 3.3 System Schematics
Loading line
Packaged blower
Remote blower with
External air butterfly valve–
Multiple burner zones
Safety
valve
train
Loading
line
Remote blower with
External air butterfly valve
Safety
valve
train
Loading
line
1
2
3
4
to other burners
15
P
1
2
Содержание ImmersoJet Series