manualshive.com logo in svg
background image

4

2.0 Control System Requirements

Turndown Method

Input is normally controlled by a motorized butterfly valve in the gas line to the burner.

Regulator Loading Lines

Connect the top diaphragm chambers of the main gas and pilot gas regulators to the
duct approximately 10" downstream of the burner. This will allow the regulators to
maintain a constant supply pressure to the burner regardless of varying pressures in
the duct.

Piloting

Pilot gas flow is adjusted as shown in Figure 6.

Ignition

Ignition voltage should be 6000 VAC.

Check Valve

See Figure 3. At high fire, the gas pressure at the burner inlet is higher than the air
pressure, and the check valve is closed. At low fire, gas pressure falls below the air
pressure, and the check valve opens, permitting a small amount of air to mix with the
gas. This premix at low fire stabilizes the flame and helps distribute the flame evenly
down the length of the burner.

Pressure Switch Connection

See Figure 4 for typical connection of a circulating fan limit switch.

Limit Controls & Saftey Equipment

Limit controls and safety equipment should comply with current NFPA Stan-
dards* 86 and 86C, and all applicable local codes and/or standards.

*Available from:
National Fire Protection Association

American National Standard Institute

Batterymarch Park

1430 Broadway

Quincy, MA 02269

New York, New York 10018

Warning

Do not install any valve or controlling device in the gas line between the burner
and the check valve tee, Figure 3. Because this section of the gas line carries a
partial pemix at low fire, it is possible under unusual conditions for the flame to
travel back through the pipe to the tee. Devices installed in this section may be
damaged and may melt, releasing gas to the atmosphere and causing fires or
explosions.

Figure 3–Check Valve Operation

Figure 4–Pressure Switch Location

Gas Inlet

Manifold

Check Valve Opens When

Gas Inlet Pressure Is at Low Fire

Process Air

WARNING!

Do Not Install Any Valves Here!

See Section 2.0

Tee

P

Lo

Hi

Circulating Air

Pressure Switch

Tube Points

Upstream

Tube Points

Downstream

Profile Plate

5

Figure 5–Profile Plates & Duct Design

where

A

G

= Area in of the gap between the profile plate

and the burner.

Flow

T

= Total air flow around and through the

burner.

Flow

R

= Air flow required per unit of open area to

produce the specified pressure drop.

A

NF

= Burner net free area, from page 2

L

F

= Burner length.

A

=

–  (A

NF

 x L

F

)

Flow

R

Flow

T

Example

–Size a profile plate for a seven foot long burner

to fire at 800,000 Btu/hr.  Air flow around and through
the burner will be 60,000 scfm.

Flow

T

= 60,000 scfm

Flow

R

= 21.5 scfm per sq. in. (from page 2)

A

NF

= 10 sq. in. per ft. (from page 2)

L

F

= 7 ft.

To calculate the open area between the burner perime-
ter and the edge of the profile plate opening, solve the
following equation:

A

=

– (10 x 7) = 2720 sq. in.

60,000

21.5

The profile opening must provide uniform air flow down
the length of the burner.

If the exact air flow is in doubt, provide adjustable profile
plates so that final settings can be made in the field.

Profile plates should be positioned flush with the firing end
of the burner. If necessary the plates can be located up
to l/2" back from the firing end, but 

under no circum-

stances

 should they be in front of the burner.

Center the burner in the duct.

Allow a minimum of 46" (1168 mm) from burner to near-
est point of possible flame impingement at an input of
800,000 Btu/hr/ft (770 kW/m).

Profile Plate Design & Mounting Guidelines

Profile

Plate

Burner

As

Required,

Top & Bottom

6" Min.

Top &

Bottom

Duct

Width

Duct

Height

3" Min.

4" Max.

Both Ends

6" Min.

Both

Ends

Duct Lengths

Minimum Distance Before

Possible Flame Impingement = 46"

AH-O

Burner

Minimum Distance Before Transition

Rectangular Ducts: One Height or Width, Whichever is Greater

Round Ducts: One Diameter

7.5°

Maximum

Air Flow

Содержание AH-O Series

Страница 1: ...tor should be use second pilot 1 PSIG maximum regulator b Bolts which fasten pilot b Check tightness of bolts b Tighten bolts casting to burner are not c Clean impulse line of any tight enough c Check...

Страница 2: ...combustion air Access Provide access to the burner for inspection and maintenance Figure 1 Ignition Flame Monitoring and Pilot Components Scanner Connection 1 2 N P T Mount In Place of Peepsight 3 4...

Страница 3: ...flow across burner face If flame length is not critical then these figures may vary Air at 70 F and sea level Required flow per unit area of combined profile opening and burner net free area to produc...

Страница 4: ...alve Operation Figure 4 Pressure Switch Location Gas Inlet Manifold Check Valve Opens When Gas Inlet Pressure Is at Low Fire Process Air WARNING Do Not Install Any Valves Here See Section 2 0 Tee P Lo...

Страница 5: ...alve Operation Figure 4 Pressure Switch Location Gas Inlet Manifold Check Valve Opens When Gas Inlet Pressure Is at Low Fire Process Air WARNING Do Not Install Any Valves Here See Section 2 0 Tee P Lo...

Страница 6: ...flow across burner face If flame length is not critical then these figures may vary Air at 70 F and sea level Required flow per unit area of combined profile opening and burner net free area to produc...

Страница 7: ...combustion air Access Provide access to the burner for inspection and maintenance Figure 1 Ignition Flame Monitoring and Pilot Components Scanner Connection 1 2 N P T Mount In Place of Peepsight 3 4...

Страница 8: ...tor should be use second pilot 1 PSIG maximum regulator b Bolts which fasten pilot b Check tightness of bolts b Tighten bolts casting to burner are not c Clean impulse line of any tight enough c Check...

Отзывы: