manualshive.com logo in svg
background image

3

Figure 2–Specifications

Inputs & Pressures:

See table below.

Fuels:

Natural gas or 100% propane vapor. Call Eclipse for information on using other fuels.

Airstream Temperatures:

Upstream of Burner:

450

°

F

250

°

C

Downstream of Burner:

1000

°

F

540

°

C

Oxygen Level:

18% oxygen required in the process airstream.

Net Free Area:

10 sq. in. per lineal foot

212 sq. cm per lineal meter

Pilot Input:

Approximately 25,000 Btu/hr.  (7.3 kW)

Piloting:

Integral spark-ignited pilot; ignition plug included.

Flame Monitoring:

Flame rod supplied. UV scanner adaptors are available. For UV scanners, Eclipse

recommends a flame monitoring system that terminates the ignition spark and
proves the pilot flame without spark prior to opening the main gas valves.

CGA requires two flame rods on burners over 36" long (914 mm). Use a flame moni-

toring endplate (see Data 140-6) to mount a second flame rod on the end opposite
the gas inlet.

Materials:

All portions of the burner exposed to flame are cast iron or #321 stainless steel.

Emissions:

Capable of operating at less than 35 ppm NO

x

 or less than 100 ppm CO, depending

upon operating conditions. Emissions performance depends not only on the burner,
but also other factors such as chamber temperature, chamber design, and heat load-
ing. For estimates of emissions performance in your application, call Eclipse.

Packaging Options:

Available with complete valve trains and control systems. AH-O burners and systems

can be supplied mounted on duct sections as specified by the customer. Call Eclipse
for information on custom packaged systems.

Models:

Model

Description

Data Sheet

AH-O

Line-shape

Data 144-1

TAH-O

“I”

-shape

Data 144-2

Inputs, Pressures, & Flame Lengths

CAUTION: It is dangerous to use any fuel burning equipment unless it is equipped with suitable flame sensing devices
and automatic fuel shut-off valves. Eclipse can supply such equipment or information on alternate sources.

Gas Pressure*

Air 

P

Air Flow

Flame

Across

Per Area

Rated Input

Nat. Gas Propane

  Length**

 Burner

 of Opening

††

550,000 Btu/hr/ft

1.2" w.c.

0.5" w.c.

18-24"

0.4" w.c.

13.6 scfm/in.

2

800,000 Btu/hr/ft

2.2" w.c.

0.9" w.c.

24-30"

0.7" w.c.

17.6 scfm/in.

2

1,000,000 Btu/hr/ft

3.5" w.c.

1.3" w.c.

40-46"

1.0" w.c.

21.5 scfm/in.

2

530 kw/m

3.0 mbar

1.2 mbar

46-61 cm 1.0 mbar

3.39 Nm

3

/hr/cm

2

762 kw/m

5.5 mbar

2.2 mbar

61-76 cm 1.7 mbar

3.39 Nm

3

/hr/cm

2

962 kw/m

6.2 mbar

3.2 mbar 102-117 cm 2.5 mbar

5.36 Nm

3

/hr/cm

2

*

Measured between the gas inlet and a tap on the duct wall 10" to 20" (25 to 50 cm) downstream of
the burner.

**

Flame length is a function of burner input, air 

P and air flow across burner face. If flame length is not

critical, then these figures may vary.

Air at 70

°

 F and sea level.

††

Required flow per unit area of combined profile opening and burner net free area to produce the cor-
responding air 

P.

6

3.0 Duct Design and Burner Mounting

Profile Plate & Duct Design

See Figure 5 for typical profile plate and duct designs.

Valve Train Support

Support valve trains independently of the burner.

Gas Piping

Use flexible nipples to allow for thermal expansion of the burner.

Check Valve Piping

Gas flow through the check valve must be horizontal. See Figure 3.

Gas Piping Standards

Gas piping must comply with American National Standard entitled "National Fuel Gas
Code"* (NFPA No. 54 or ANSI Z223.1), or must be acceptable to the authority having
jurisdiction.

Wiring Standards

Electrical wiring must comply with the National Electric Code*, (NFPA Std. 70 or ANSI-
CI 1981), or must be acceptable to the authority having jurisdiction.

*Available from:
National Fire Protection Association

American National Standard Institute

Batterymarch Park

1430 Broadway

Quincy, MA 02269

New York, New York 10018

4.0 Start-Up And Adjustment

Initial Settings

Adjust the linkage of the gas control valve so that when heat is called for, the valve is
10

°

 from fully open, and when cooling is required, the valve is approximately 5

°

 from

fully closed.

Close all manual gas cocks.

With the pilot cock handle in the closed position, remove the top screw and turn the
adjusting screw five turns out from fully closed. See Figure 6.

Start Blower

Start the combustion air blower. Check the rotation to make sure it is correct. If not,
have a qualified electrician rewire the blower for proper rotation.

Start Circulating Fan

Start the duct circulating fan.

Set Air Pressure Drop

Measure the air pressure drop across the
burner as shown in Figure 7.

Adjust the damper on the circulating fan until
the air pressure drop is between 0.4" w.c.
minimum and 1.0" w.c. maximum. See the
table in Figure 1 for maximum and minimum
inputs permitted for various air pressure
drops. For a given input, lower air pressure
drops will produce a longer flame, and
higher drops will produce a shorter flame.

Start Spark

Energize the ignition spark.

 Do not touch

the ignition rod, ignition wire, or trans-
former while the spark is energized, or
you will get a shock.

Set Pilot Flow

Open all pilot gas valves, including the handle of the pilot cock, Figure 6. The pilot
should light.

Turn the pilot adjusting screw to produce a bushy blue flame that provides a flame
monitoring signal strong enough to reliably open the gas shut-off valves.

Figure 6–Pilot Cock

Top Screw

Handle

(Shown in 

Open Position)

Adjusting Screw

(Clockwise for less pilot gas,

Counterclockwise for more pilot gas)

Содержание AH-O Series

Страница 1: ...tor should be use second pilot 1 PSIG maximum regulator b Bolts which fasten pilot b Check tightness of bolts b Tighten bolts casting to burner are not c Clean impulse line of any tight enough c Check...

Страница 2: ...combustion air Access Provide access to the burner for inspection and maintenance Figure 1 Ignition Flame Monitoring and Pilot Components Scanner Connection 1 2 N P T Mount In Place of Peepsight 3 4...

Страница 3: ...flow across burner face If flame length is not critical then these figures may vary Air at 70 F and sea level Required flow per unit area of combined profile opening and burner net free area to produc...

Страница 4: ...alve Operation Figure 4 Pressure Switch Location Gas Inlet Manifold Check Valve Opens When Gas Inlet Pressure Is at Low Fire Process Air WARNING Do Not Install Any Valves Here See Section 2 0 Tee P Lo...

Страница 5: ...alve Operation Figure 4 Pressure Switch Location Gas Inlet Manifold Check Valve Opens When Gas Inlet Pressure Is at Low Fire Process Air WARNING Do Not Install Any Valves Here See Section 2 0 Tee P Lo...

Страница 6: ...flow across burner face If flame length is not critical then these figures may vary Air at 70 F and sea level Required flow per unit area of combined profile opening and burner net free area to produc...

Страница 7: ...combustion air Access Provide access to the burner for inspection and maintenance Figure 1 Ignition Flame Monitoring and Pilot Components Scanner Connection 1 2 N P T Mount In Place of Peepsight 3 4...

Страница 8: ...tor should be use second pilot 1 PSIG maximum regulator b Bolts which fasten pilot b Check tightness of bolts b Tighten bolts casting to burner are not c Clean impulse line of any tight enough c Check...

Отзывы: