4.1 Limitations UA 400 E / UA 401 E / UA 410 E
Up to max. 4 temperature displays can be connected to the DISPLAY interface.
Max. 30 m cable length (longer distances on request).
Cannot be used simultaneously with
The case controller and the connected VDD 500 can only be configured using a system centre connected
on the CAN bus.
Practical tip:
Configuration of a case controller UA 4xx E with an operator interface BT 300 - if necessary, connection of
BT 30
Procedure
Disconnect power supply from the controller (A).
Detach the connectors for the temperature displays VDD 500 from the controller (B).
Activate DISPLAY interface for the communication with BT 300:
Set DIP switch 7 to OFF (C).
Connect operator interface BT 300 (if necessary BT 30) to the DISPLAY interface (D),
for details, see operating manual
.
Connect controller to the power supply again (A).
The BT 300 can now be used to operate and configure the controller.
Note
: The parameters for the VDD scan and for configuration of the temperature display VDD 500 are now
hidden in menu 6-1 as the DIP switch 7 is set to OFF!
If the configuration has been completed, the operator interface BT 300 is no longer needed:
Disconnect the power supply from the controller (A), disconnect the operator interface BT 300 from the
DISPLAY interface (D),
reactivate the DISPLAY interface for temperature displays VDD 500 (C) - set DIP switch 7 to ON - and
reconnect the connector for the VDD 500 (B).
Connect controller to the power supply again (A).