Pin and Terminal Assignments of CI 3000 / SIOX
64
Version 2.09 09. April 2014
6.2.3
SIOX - Terminal assignment of the interfaces
The interfaces for connection to the store computer or an additional SIOX (
S
erial
IO
E
xtension) are located on
the left side of the device.
Danger of destruction of components!
SIOX extension modules may only be connected to each
other or the store computer when no voltage is present!
In the event of an Ethernet network cable with PoE (Power over Ethernet) being used instead of the
SIOX data cable (RJ45) damage can occur to participating network devices!
Only components approved by Eckelmann AG may be connected to the SIOX extension bus (termi
nals SIOX OUT/SIOX IN i.e. terminals 91..95).
Terminal No.
Function
SIOX power supply (SIOX-SUPPLY)
91
92
93
94
95
Ground von 9 V
+9 V DC
Ground von 24 V
+24 V DC
SHLD (shield)
SIOX 24 V DC - no function
Not suitable for supplying external consumers!
93
94
Ground von 24 V DC
+24 V DC
SIOX data interface
(IN)
RJ45 connector
Data cable input from store computer i.e. previous SIOX
SIOX data interface
(OUT)
RJ45 connector
Data cable output to the next SIOX (max. 4)
Содержание CI 3000
Страница 20: ...Application of CI 3000 14 Version 2 09 09 April 2014 Notice...
Страница 62: ...Installation and Startup of CI 3000 SIOX 56 Version 2 09 09 April 2014 Notice...
Страница 118: ...Menu structure of CI 3000 112 Version 2 09 09 April 2014 Notice...
Страница 120: ...Decommissioning and disposal 114 Version 2 09 09 April 2014 Notice...
Страница 126: ...Alarms and Messages of CI 3000 120 Version 2 09 09 April 2014 Notice...