Overview

The Emergency Bypass Load Controller (EREB) is powered by an
emergency source to provide power to emergency lighting loads. The
EREB ensures the emergency lighting is on during loss of circuit power,
and also tracks the state of controlled lighting loads during normal
operation. The EREB ensures a “lights on” override by using a normally
closed emergency contact closure that interfaces with fire alarm and
emergency systems.

The EREB is available in two models to provide installation options: Power
Pack EREB-AP and DIN rail EREB-AD.

Power Pack: EREB-AP

DIN rail: EREB-AD

This document covers installation of all the EREB models. The product
package includes the controller and lock nut for the EREB-AP model.

Electrical Specifications

Certified by UL and cUL listed Emergency Lighting and Power
Equipment under UL 924 at 120 and 277 VAC line voltages, 60 Hz.

Ballast load rating: 20 A maximum at 120 or 277 VAC.

Incandescent load rating: 10 A maximum at 120 or 277 VAC.

UL 2043 Plenum rated, EREB-AP model only.

Provides remote activation by dry contact closure for connection to a
fire alarm or building management system.

Provides auxiliary contact for 0–10 VDC or fluorescent ballasts,
EREB-AD model only.

Содержание EREB-AP

Страница 1: ...operation The EREB ensures a lights on override by using a normally closed emergency contact closure that interfaces with fire alarm and emergency systems The EREB is available in two models to provi...

Страница 2: ...e c blage du courant alternatif v rifiez que les disjoncteurs pour l alimentation normale et pour l alimentation de secours sont en position d arr t et suivez les proc dures de v rouillage tiquetage p...

Страница 3: ...y to the exterior of the junction box or panel either at the electrical lighting load or before the loads in the circuit See Examples of Use on page 10 Two sets of wire bundles are provided on the top...

Страница 4: ...ow for wiring instructions 7 Replace the cover plate and restore power to the circuits Wiring Diagram Emergency Bypass Load Controller EREB AP Remote LED Option Button Status LED Emergency Power In Bl...

Страница 5: ...ect normal sense and emergency power wires Four screw terminals on the top of the device are used for the following connections The two terminals on the left have a factory installed wire loop jumper...

Страница 6: ...nnect to the terminals labeled 0 10 V FLO See Examples of Use on page 10 for more information 6 Are you are installing a remote triggering device to remotely activate the emergency circuit No Go to In...

Страница 7: ...o your EREB See Initial Test on page 8 2 Remove the wire loop jumper from the Remote Loop In and Remote Loop Out terminals 3 Connect the Remote Loop In and Remote Loop Out terminals on the EREB AD to...

Страница 8: ...ghting is not required 4 Confirm the automatic emergency On functionality by turning Off the circuit breaker in the normal panel The connected emergency lighting should immediately turn On again and t...

Страница 9: ...ntrol circuit thereby illuminating the load and bypassing the normal control signal to the load In a properly operating system the load should illuminate upon pressing the Test button Remote Activatio...

Страница 10: ...Power Sense Black Normal Neutral White Normal Light Fixture Emergency Power Out Red EREB Emerg Light Fixture Switch Backup Arrangement When normal power is present the emergency fixture is turned OFF...

Страница 11: ...ol EREB AD model only When normal power is present and the switch is closed both 0 10 V controlled fixtures dim When normal power is present and the switch is open both 0 10 V controlled fixtures turn...

Страница 12: ...quipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmfu...

Отзывы: