ELEDR(H) Installation Guide

Installing the Controller 

For best results mount the controller on the outside of the electrical box 

either directly at the electrical load or before the load in the circuit. 
Review these instructions completely before installing the controller.

1. 

Locate the circuit breaker panel and terminate power to the circuit.

2.  Remove all face plates and other hardware from the junction box so 

you can access the high voltage wires.

3.  Mount the controller to the exterior of the junction box or panel with 

the ½” threaded nipple.  

4. 

Refer to the wiring diagram to connect the controller to line 

power, neutral and load wire. Use wire nuts on all connections and 

individually cap any bare wires (except orange antenna wire).

5.  Restore power to the circuit.
6.  If the controller was pre-commissioned you can use one of the pre-

linked devices to test the controller operation. If the controller was not 

pre-commissioned by the factory, refer to the section of this guide 

titled 

Linking the First Switch

. Use this switch to verify the controller 

functionality.

Note:

Always  follow  applicable  NEC  and  local  electrical  code 

requirements when installing and powering the controller

.

i

Note:

The Micro USB port is for factory use only. Do not attach cables 

or accessories to this port

The use of accessory equipment not recommended by the manufacturer 

may cause an unsafe condition.  Do not use this equipment for other than 

its intended use. 
Do not use outdoors.

Electrical Terminations 

The controller has an external orange antenna wire. Do not cut, cap or 

connect this wire. 
Power to the controller is connected between the White (Neutral) and the 

Black Line power: ELEDR (120-277VAC) or ELEDRH (240-347VAC) Use only 

UL approved wire when making connections, see table below.

Controller's Wire Details for ELEDR(H)

Connection 

Color 

Specification

Load 

Red 

14AWG 600V

Neutral 

White

14AWG 600V

Line  

Black 

14AWG 600V

i

Содержание ELEDR

Страница 1: ...and should only be in stalled by qualified personnel in accordance with National Electrical Code and any local regulations CAUTION To avoid electrical overload total connected load should not exceed...

Страница 2: ...orized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Do not use this equipment for other than its intended use Servicing should be performe...

Страница 3: ...1 5 HP 120VAC and 3 0 HP 277VAC Simple Tap technology is included allowing installers and facility operators to manage configuration settings without any specialized tools see wiring diagram on page...

Страница 4: ...es to test the controller operation If the controller was not pre commissioned by the factory refer to the section of this guide titled Linking the First Switch Use this switch to verify the controlle...

Страница 5: ...ation The POWER LED will remain lit for four seconds while it links the new device It will resume toggling allowing you to link another device up to a total of twenty devices 3 To exit link mode press...

Страница 6: ...to factory default settings removing all linked devices press the CLEAR button until the POWER and LEARN LEDs come on solid about 15 seconds then release The POWER LED will stay ON solid indicating t...

Страница 7: ...ELEDR Programming Guide pdf The table below describes the number of LED blinks for each device type RED POWER LED Blink Codes Factory Default ON Solid switch es 1 long blink followed by short blinks c...

Страница 8: ...ZV STM300U IC RSS 210FCC Part 15 231 Contains FCC ID SZV STM300U The enclosed device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions i this device may not c...

Отзывы: