Echoflex Solutions Installation Guide

Elaho SmartSpace Controller–Gen 2

M a in Offic e Squamish, BC, Canada Phone +1 778 733 0111
E ma il

[email protected]

We b

echoflexsolutions.com

© 2019 Echoflex Solutions, Inc. Trademark and patent info: 

echoflexsolutions.com/ip

Echoflex Solutions intends this document to be provided in its entirety.
Product information and specifications subject to change.
8 1 8 7 M 2 1 0 3 Rev C Released 2019-12

Overview

The Elaho SmartSpace Controller–Gen 2 provides fully-rated 20 A relays for
direct control of individual fixtures or zone power, and offers fully isolated 0–
10 V dimming control for compatible LED drivers and fluorescent ballasts.

Through its 24 V power supply, the Elaho SmartSpace Controller–Gen 2 can
power an auxiliary device, such as an Echoflex Solutions or third-party
occupancy, vacancy, or photo sensor. A dry contact input allows responsive
controls to initiate control events across the Elaho control system.

Single Zone 
model shown

Two models are available:

Single Zone (ESSC-G2)

Dual Zone (EDSSC-G2)

Содержание Elaho SmartSpace Controller-Gen2

Страница 1: ...2019 12 Overview The Elaho SmartSpace Controller Gen 2 provides fully rated 20 A relays for direct control of individual fixtures or zone power and offers fully isolated 0 10 V dimming control for com...

Страница 2: ...onnect EchoConnect is a two wire topology free system that provides the SmartSpace Controller Gen 2 with the flexibility to connect in a system with up to 16 Elaho control products and up to 15 other...

Страница 3: ...el supports Power input 120 277 VAC 60 Hz Load rating 20 A general purpose tungsten or resistive 16 A electronic ballast Dual Zone model supports Power input 120 277 VAC 60 Hz Load rating 20 A general...

Страница 4: ...nect is a bidirectional protocol that uses one pair of wires data and data for both data and power Echoflex Solutions recommends using Belden 8471 or approved equal Class 2 wire The total combined len...

Страница 5: ...osition d arr t et suivez les proc dures de Consignation D consignation prescrites par la norme NFPA 70E WARNING For indoor use only Must install to an electrical junction box or wireway AVERTISSEMENT...

Страница 6: ...ire is pulled appropriately Terminate Cat5 wiring using the EchoConnect Cat5 Station Termination Kit and install it using a bus topology See the installation guide that is provided with the Cat5 Stati...

Страница 7: ...re of the lighting load b Connect the black power input wire 12 AWG to the line input feed wire hot from the breaker panel 2 Connect the relay output wiring A Single Zone controller has one red relay...

Страница 8: ...lack Green Yellow EchoConnect Ground Red Load 1 Red White Load 2 Occupancy Sensor 24 VDC 24 VDC Red Common Black Sensor Input Yellow Dual Zone SmartSpace Occupancy Sensor 24 VDC 24 VDC Red Common Blac...

Страница 9: ...erre avant de raccorder tout c blage de commande 0 10V l appareil The 0 10V dimming output wiring exits the SmartSpace Controller Gen 2 through the top nipple of the enclosure with the power wiring 1...

Страница 10: ...Zone model only do not set the Zone switch setting to a number higher than 15 If set to 16 both circuits in the controller will be assigned to and controlled on Zone 16 2 Set the Space rotary switch...

Страница 11: ...ux Input Mode button to cycle through the available sensor types Troubleshooting Restore Defaults To return the SmartSpace Controller Gen 2 to factory defaults set both rotary switches to 16 and then...

Страница 12: ...ert the microSD card in the SD slot on the side of the SmartSpace Controller Gen 2 enclosure The Dim Mode LED will illuminate amber in a triple blink pattern while the firmware is updating and then wi...

Отзывы: