Echoflex Solutions Installation Guide
SmartSpace Controller–Gen 2
Connect EchoConnect
The EchoConnect wire terminations are bound together and include a black
wire (data -), a white wire (data +), and a green/yellow wire (ESD). Because
EchoConnect is topology free, you can install the wires in any combination of
bus, star, loop, or home-run.
Note:
When using Category5 (or equivalent) cable on the EchoConnect
communication bus, please note the following:
•
Not all topologies are supported using Cat5; plan carefully to
ensure that the proper termination kits are available and the
wire is pulled appropriately.
•
Terminate Cat5 wiring using the EchoConnect Cat5 Station
Termination Kit, and install it using a bus topology. See the
installation guide that is provided with the Cat5 Station
Termination Kit (8186A1707) for information on terminating
Cat5 wiring.
1.
Pull all required wiring (data +, data -, and the ESD ground wire) to the
junction box.
2.
Use the included WAGO connectors to make the following
terminations:
a.
Connect the incoming ground wire to the ESD green/yellow
ground wire on the unit.
b.
Connect the white (data +) wire to the incoming data + (typically
white).
c.
Connect the black (data -) wire to the incoming data - (typically
black).
Terminate EchoConnect
wiring using provided
WAGO connectors.
SmartSpace Controller–Gen 2
Page 6 of 12
Echoflex Solutions