Echoflex Installation Guide
Dual Tech Ceiling-mount Vacancy Sensor
DIP Switch Settings
DIP switches on the sensor electronics provide for additional configuration
options including Use Custom Config, Vacancy Timeout, Enable/Disable
detection LEDs, PIR Only, and the ability to restore the sensor to its factory
defaults.
Switch #
Use
1
Unused
2
Enable/Disable Custom Config Mode
•
When “Custom Config” is set to Off (also known as Basic
configuration mode), local DIP switch settings for Vacancy
Timeout, Enable PIR LED, and dual technology features are
used. See
Configuration using Elaho Program Mode on
page 1
.
•
When “Custom Config” is set to On, all other local DIP
switch settings are ignored. Instead, the settings made by
the EchoAccess Mobile App are used.
3 and 4
Vacancy Timeout
•
5 min = Switches 3 and 4 are Off
•
15 min = Switch 3 is Off and Switch 4 is On (default)
•
30 min = Switch 3 is On and Switch 4 is Off
•
Auto = Both switches are On
5
Detection LEDs
•
When set to On (default), the occupancy detection LEDs
illuminate when movement is detected.
•
When set to Off, the occupancy detection LEDs are
disabled unless the unit is in Walk Test mode.
6
PIR Only Mode
•
When set to On, acoustic detection technology is disabled
for the sensor.
•
When set to Off (default), both PIR and acoustic detection
technologies are used by the sensor.
7
Unused
8
Restore to Defaults at boot
•
When set to On, then cycling power to the sensor, the unit
restores to its factory default settings.
•
Off is the default setting.
Dual Tech Ceiling-mount Vacancy Sensor
Page 7 of 12
Echoflex Solutions, Inc.