Echoflex Installation Guide
Dual Tech Ceiling-mount Vacancy Sensor
Soft Ceiling Tile Installation
Ceiling tile
adapter
Ceiling tile
Ceiling tile adapter
1.
Pull the Belden 8471 (or equivalent) and 14 AWG (2.5 mm
2
) ground
wire to the mounting location and strip each wire to the appropriate
length. The strip length is dependant on the wire nut or other
termination connector used (wire nuts are not provided).
2.
Temporarily remove the sensor cover to gain access to the
configuration switches and mounting access holes. Hold the sensor in
one hand while gently twisting the cover clockwise.
3.
Prepare the ceiling tile.
a.
Align the flat side of the sensor to the finished side of the ceiling
tile and mark the access hole for wire pass-through.
b.
Remove the ceiling tile material from marked access hole.
c.
Pull the sensor wires through the access hole.
4.
Insert the soft ceiling tile adapters through the provided pinholes in
the sensor mounting plate, one set located on each side of the sensor
near the mounting keyholes. Push the adapters through the ceiling
tiles, then bend each tine over in opposite directions for a secure fit on
the unfinished side of the ceiling tile.
5.
Connect the EchoConnect wires from the sensor to the installed wires.
a.
Connect the data - (typically black) EchoConnect wire from
sensor to the incoming EchoConnect (typically black) wire using a
WAGO wire termination connector.
b.
Repeat the above step for the data + (typically white)
EchoConnect wire and for the ESD ground wire, using a new
WAGO connector for each termination type.
Dual Tech Ceiling-mount Vacancy Sensor
Page 5 of 12