background image

Echoflex Installation Guide

Elaho Vacancy Sensor

DIP Switch Settings

DIP switches on the rear panel of the Vacancy Sensor
provide for additional configuration options including
Use Custom Config, Vacancy Timeout, Enable/Disable
PIR detection LED, and the ability to restore the sensor
to its factory defaults.

DIP Switch 2

DIP switch 2 enables “Custom Config” which
instructs the sensor to use settings that are configured using the ElahoAccess
Mobile App. This setting is Off by default.

When “Custom Config” is set to Off, the default position, local DIP
switch settings for Vacancy Timeout and Enable PIR LED are used.
Sensor actions can be adjusted using the program [Mode] button.

When “Custom Config” is set to On, all other local DIP switch settings
are ignored. Instead, the settings made by the ElahoAccess Mobile
App for Vacancy Timeout and Enable PIR LED are used.

DIP Switch 3&4

DIP switch 3 & 4 set the “Vacancy Timeout” to 5, 15, 30 minutes, or Auto.
See

Vacancy Timeout on the next page

.

5 min = Switches 3 and 4 are Off.

15 min = Switch 3 is Off and Switch 4 is On (default).

30 = Switch 3 is On and Switch 4 is Off.

Auto = Both switches are On. See

Auto Vacancy Timeout on the next

page

.

DIP Switch 5

DIP switch 5 enables/disables the red PIR detection LED. When the switch is
Off, the PIR LED disables unless it is in Walk Test mode. When set to On, the
red PIR LED will illuminate the sensor lens when movement is detected. The
default position is On.

DIP Switch 8

DIP switch 8 provides a “Restore Defaults at Boot” function. The factory
defaults are restored by setting this DIP switch On, and cycling power to the
station. The default position is Off.

Note:

DIP switches 1, 6, and 7 are not currently used and are reserved

for future development. Leave them at their default Off setting.

Elaho Vacancy Sensor

Page 7 of 12

Echoflex Solutions, Inc.

Содержание E-VAC

Страница 1: ...e coverage of the installed location and is available in three models E VAC SR Vacancy Sensor with small room lens covers 450 sq ft at 8 ft 800 sq ft at 10 ft E VAC Vacancy Sensor with standard room lens covers 1 800 sq ft at 8 ft 3 000 sq ft at 10 ft E VAC HC Vacancy Sensor with high ceiling lens covers 300 sq ft at 10 ft 7 000 sq ft at 40 ft Each sensor is available in white or black finish Lens...

Страница 2: ...cable on the EchoConnect communication bus please note the following Cat5 wiring must be terminated using EchoConnect Cat5 Termination Kit and must be installed using a bus topology Refer to the installation guide that is provided with the Cat5 Termination Kit 8186A1207 for information to terminate Cat5 wiring Not all topologies are supported using Cat5 careful planning is required to ensure the p...

Страница 3: ...ire pigtails 3 lens masks Note Follow all local code requirements for terminating wire Use appropriately sized wire nuts not provided to secure each termination The EchoConnect pigtail is only required when the sensor is installed in series with other stations or sensors If you are not continuing the data run direct termination on the control board is recommended Installation The Vacancy Sensor is...

Страница 4: ...ite EchoConnect wire and the ESD ground wire 3 Orient the smooth side of the mounting plate to the junction box and pull the EchoConnect wires or terminated pigtail from the junction box through the provided holes near the center of the mounting plate 4 Secure the mounting plate to the junction box using the screws provided both short and long screws are provided for convenience 5 Strip each wire ...

Страница 5: ...termination used b Twist the data typically black EchoConnect wire the black lead from the EchoConnect pigtail and any continuing EchoConnect typically black wire together and secure with the wire nut c Repeat the above steps for the data typically white EchoConnect wire and for the ESD ground wires 3 Create a hole for wire pass through in the ceiling tile by poking through the center hole or oblo...

Страница 6: ...le using the rotary switches on the rear panel of the sensor Additional DIP switches and the Mode button also located on the rear panel set the sensor functionality and the occupancy detected action Set Space and Address Two rotary switches on the rear panel of the controller provide for assignment of the sensor Space and Address By default these switches are set to Space 1 Address 1 Commands are ...

Страница 7: ...e App for Vacancy Timeout and Enable PIR LED are used DIP Switch 3 4 DIP switch 3 4 set the Vacancy Timeout to 5 15 30 minutes or Auto See Vacancy Timeout on the next page 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 Switch 3 is On and Switch 4 is Off Auto Both switches are On See Auto Vacancy Timeout on the next page DIP Switch 5 DIP switch 5 enables disable...

Страница 8: ... reference the ElahoAccess Mobile App integrated help system Vacancy Timeout Vacancy timeout is the amount of time the sensor waits to take action after no movement is detected By default vacancy timeout is set to 15 minutes indicated by DIP switch 3 set to Off and 4 set to On When the vacancy timeout ends the grace period begins When the sensor detects vacancy the vacancy timeout period begins If...

Страница 9: ...ts sensitivity to eliminate nuisance tripping When the sensor powers on the red PIR LED illuminates for approximately 60 seconds to identify Power Up state Sensor configuration is not allowed During this time no events are triggered Test Vacancy Sensors offer a Walk Test mode which shortens the vacancy timer to ten seconds allowing for simple and quick verification of the sensors coverage and rang...

Страница 10: ...alk Test is enabled and the vacancy no vacancy occupancy timer will be shortened to ten seconds 3 Move throughout the space including corners and areas that may specifically be obscured from line of sight to the sensor Each time the sensor detects movement the lens will illuminate red 4 Adjust the lens masking if installed blocking certain areas of the installed space from sensor detection See Len...

Страница 11: ...0 12 2m 40ft 9 1m 30ft 6 1m 20ft Small Room side view 0 0 1 5m 5ft 1 5m 5ft 3 0m 10ft 3 0m 10ft 4 6m 15ft 4 6m 15ft 6 1m 20ft 6 1m 20ft 8ft 2 4m 10ft 3 0m 12ft 3 7m Large Room side view 0 8ft 2 4m 10ft 3 0m 12ft 3 7m 0 3 0m 10ft 3 0m 10ft 6 1m 20ft 6 1m 20ft 9 1m 30ft 9 1m 30ft 12 2m 40ft 12 2m 40ft Elaho Vacancy Sensor Page 11 of 12 Echoflex Solutions Inc ...

Страница 12: ...Echoflex Installation Guide Elaho Vacancy Sensor Elaho Vacancy Sensor Page 12 of 12 Echoflex Solutions Inc ...

Отзывы: