Echoflex Installation Guide
Elaho Vacancy Sensor
DIP Switch Settings
DIP switches on the rear panel of the Vacancy Sensor
provide for additional configuration options including
Use Custom Config, Vacancy Timeout, Enable/Disable
PIR detection LED, and the ability to restore the sensor
to its factory defaults.
DIP Switch 2
DIP switch 2 enables “Custom Config” which
instructs the sensor to use settings that are configured using the ElahoAccess
Mobile App. This setting is Off by default.
•
When “Custom Config” is set to Off, the default position, local DIP
switch settings for Vacancy Timeout and Enable PIR LED are used.
Sensor actions can be adjusted using the program [Mode] button.
•
When “Custom Config” is set to On, all other local DIP switch settings
are ignored. Instead, the settings made by the ElahoAccess Mobile
App for Vacancy Timeout and Enable PIR LED are used.
DIP Switch 3&4
DIP switch 3 & 4 set the “Vacancy Timeout” to 5, 15, 30 minutes, or Auto.
See
Vacancy Timeout on the next page
.
•
5 min = Switches 3 and 4 are Off.
•
15 min = Switch 3 is Off and Switch 4 is On (default).
•
30 = Switch 3 is On and Switch 4 is Off.
•
Auto = Both switches are On. See
Auto Vacancy Timeout on the next
page
.
DIP Switch 5
DIP switch 5 enables/disables the red PIR detection LED. When the switch is
Off, the PIR LED disables unless it is in Walk Test mode. When set to On, the
red PIR LED will illuminate the sensor lens when movement is detected. The
default position is On.
DIP Switch 8
DIP switch 8 provides a “Restore Defaults at Boot” function. The factory
defaults are restored by setting this DIP switch On, and cycling power to the
station. The default position is Off.
Note:
DIP switches 1, 6, and 7 are not currently used and are reserved
for future development. Leave them at their default Off setting.
Elaho Vacancy Sensor
Page 7 of 12
Echoflex Solutions, Inc.