Echoflex Installation Guide
Elaho Vacancy Sensor
Enable Walk Test Mode
1.
Prepare the site for configuration.
a.
Make certain the sensor and lighting loads are powered and
connected for control by the Elaho controller.
b.
You will need direct access to the Vacancy Sensor in order to
place it into Walk Test mode.
2.
Press the [Walk Test] button on the front of the sensor to enable the
Walk Test feature at the sensor. A green LED will begin to flash,
indicating Walk Test is enabled and the vacancy/no vacancy occupancy
timer will be shortened to ten seconds.
3.
Move throughout the space including corners and areas that may
specifically be obscured from line of sight to the sensor. Each time the
sensor detects movement, the lens will illuminate red.
4.
Adjust the lens masking, if installed, blocking certain areas of the
installed space from sensor detection. See
Lens Masking on the
previous page
.
5.
Walk Test mode will automatically exit after five minutes from the
time it was enabled. To manually exit the Walk Test mode, press
either of the buttons on the sensor.
Elaho Vacancy Sensor
Page 10 of 12
Echoflex Solutions, Inc.