11
2.4.3 T1
This setting is used to control how fast the brake coil will get to full voltage (v max).
It is adjustable in steps of 50 ms.
The minimum allowed setting is 100ms and the maximum allowed setting is 5000 ms.
Default setting is 500ms.
2.4.4 T2
This setting is used to control how long the brake coil will stay at full voltage.
It is adjustable in steps of 50 ms.
The minimum allowed setting is 100ms and the maximum allowed setting is 5000 ms.
Default setting is 1500ms.
2.4.5 T3
This setting is used to control how fast the voltage will reduce to V1 level after the T2 time
expires.
It is adjustable in steps of 50 ms.
The minimum allowed setting is 100ms and the maximum allowed setting is 5000 ms.
Default setting is 500ms.
2.4.6 T4
This setting is used to set how fast the brake voltage will reduce to 0v after the BK SIGNAL is
switched off.
It is adjustable in steps of 50 ms.
The minimum allowed setting is 0ms and the maximum allowed setting is 3000 ms.
Default setting is 500ms.