26

Water Filling Valve 

 

 

 

 

 

Figure 17  

In your combi only E.C.A. Room thermostats approved by authorized services 

should be used. Otherwise, it may cause your device to malfunction. In such cases, 

no liability is accepted.. 

The connections of room thermostat, outdoor sensor and timer must be performed 

certainly by qualified person. For Room Thermostat activation, special parameter 

adjustment must be done by qualified person.

10- COMMISSIONING, USE AND TURNING OFF THE BOILER

10.1- Commissioning, Filling Water into Boiler and Heater Installation

First of all, the electrical connection of the boiler is done. The electrical connection of the device must be 

connected to a grounded power supply line that can supply enough voltage (230 VAC, 50 Hz) for the 

device.

- All radiator valves must be opened.

- CH flow and CH return of boiler must be opened. Check them.

- After all these processes, filling valve is slowly opened and filling procedure is initiated.

The filling process continues until the water pressure of 1.5-2 bar is seen on the LCD display and then 

the filling valve is closed.

- When the water pressure increases to 0.8 bar, the LCD will show "AP" and the boiler will switch to 

automatic air vent mode. In this case you should definitely wait for 160 seconds without pressing 

"RESET".

- Check water pressure on pressure indicator frequently and ensure that the pressure is between 1.5 

and 2 bar when system is cold. If the pressure drops frequently, it means that there is a water leak in the 

system. In such case, it is necessary to call a plumber. 

ATTENTION :

 

Always close the water filling valve, the installation water may leak and 

damage the environment.

- To discharge air out of CH installation, purgers of the radiator is loosened and air is discharged until 

water comes out of radiators. This procedure is done for all radiators.

- Pressure is checked again on LCD screen. The filling valve is opened and again pressure is raised to 

1.5 – 2 bar level.

- Radiator purgers are checked again to see if there is any air left inside of heating installation. For full 

efficient heating, all air must be discharged.

- Please repeat AP mode after electricity off and on.

- Finally, check for any leaks in the radiator and piping.

Содержание CONFEO PREMIX P 14 HCH

Страница 1: ...CONFEO PREMIX CONDENSING COMBI BOILER CONFEO PREMIX P 14 20 24 28 30 35 HM HCH HST OPERATING INSTALLATION MANUAL...

Страница 2: ......

Страница 3: ...5 5 Electrical Diagram 13 6 BOILER PACKAGING 14 7 FLUES 15 7 1 Flue Sizes 15 7 2 Flue Types 15 7 3 Distances for Placement of Flues 16 8 INSTALLATION 17 8 1 Selec on of Installa on Loca on of Device 1...

Страница 4: ...IONS 31 13 USEFUL INFORMATION ON PRODUCT 35 13 1 Informa on on the E cient Use of the Combi Boiler in Terms of Safety and Energy Consump on 35 13 2 Clogging in Installa on 35 13 3 Cleaning of Boiler 3...

Страница 5: ...lers are available in this manual Detailed informa on have been provided in the guide regarding the technical speci ca ons of the devices selec on of the boiler loca on ng its water gas ue and electri...

Страница 6: ...la on The boiler must be installed in accordance with na onal and local requirements gas safety regula ons relevant standarts and this manual by quali ed installer The appliance should be mounted agai...

Страница 7: ...iler CAUTION This device is not intended to be used by persons with physical sensory or mental disabili es even children or persons with inadequate experience and knowledge unless the person responsib...

Страница 8: ...n System 170 VAC Thermal Accumala on Protec on System with by pass circuit and pump over run Frost Protec on System for both CH and DHW circuit Domes c Hot Water Flow Control only for HM Model Pump An...

Страница 9: ...4 Fan 5 Motorized Valve 6 Condensing WaterHose 7 Outlet Manifold 8 3 Bar Safety Valve 9 Pressure Sensor 10 Siphon 11 Plated Heat Exchanger 12 Gas Valve 13 Return Manifold 14 Pump 15 Flexible Connec on...

Страница 10: ...10 5 3 1 HM Model 5 3 2 HCH Model 5 3 3 HST Model DHW Supply CH Supply DHW In CH Return CH Supply CH Return STORAGE TANK CH Return CH Supply Storage Tank Outlet Storage Tank Return...

Страница 11: ...cy 90 7 90 7 83 6 83 9 82 8 82 8 Sound Power Level db A 44 46 47 49 50 52 E ciency at Rated Heat Output At High Temperature Regime 4 87 9 87 9 87 9 87 9 87 9 87 9 E ciency at 30 of rated Output At Low...

Страница 12: ...ec on Class Expansion Vessel lt Weight Net kg 32 32 34 Dimesions HxWxD mm C13 60 100 Max m 10 10 10 10 10 10 C13 80 125 Max m 20 20 20 20 20 20 C33 60 100 Max m 10 10 10 10 10 10 C33 80 125 Max m 20 2...

Страница 13: ...13 5 5 Electrical Diagram...

Страница 14: ...and lower styrofoams Figure 4 Figure 5 Moun ng Bracket 3 2 Parts required for installa on of the device wall bracket 5 gaskets for HM and HCH and 6 gaskets for HST water and gas connec ons 2 anchors...

Страница 15: ...inner pipe facing outwards should be inclined upward and the fresh air pipe outer pipe should be inclined downward When the original flue set is installed parallel to the ground the exhaust gas pipe...

Страница 16: ...16 Figure 6 7 3 Distances for Placement of Flues Figure 7...

Страница 17: ...wo ue outlets 100 Table 4 8 INSTALLATION 8 1 Selection of Installation Location of Device The boiler must be installed in accordance with gas safety regulations and relevant standards Addition ally th...

Страница 18: ...ements gas safety regulations and relevant standards IPX4D protection class devices are not suitable for unprotected outdoor installations These devices should be installed inside of the building or i...

Страница 19: ...ondensate Discharge Connec on All condensing boilers generate condensing discharge The amount of the condensate water depends on the working conditions of your appliance This can be up to 1 7 litres c...

Страница 20: ...e CH return cold A suitable valve should be mounted on the gas inlet and CH DHW water circuit In addition a water filter must be mounted on CH 3 4 return and DHW 1 2 inlet A plastic pipe should be fix...

Страница 21: ...el a CH flow hot b Water filling line1 2 c Gas inlet d CH return cold 9 2 3 HST Model a CH flow hot b Boiler supply water hot c Gas inlet d Boiler return cold e Water Filling Line f CH return cold a b...

Страница 22: ...the electrical supply CAUTION If the supply cord is damaged it must be replaced by the manufacture its service agent or similarly qualified person in order to avoid a hazard CAUTION The 2 amp bipolar...

Страница 23: ...Smart Room T6360 Boiler Air Condi oning Thermostat 7006901312 7006907804 7006907531 E C A Digital Room Thermostat Wireless E C A Digital Room Thermostat Programmable CM727 Honeywell DT90 7006902046 7...

Страница 24: ...For the room thermostat the bridged cable connection on the back of the control panel is removed and the outer air sensor is connected to free sockets on the terminal It can be provided as an option a...

Страница 25: ...make the Opentherm room Thermostat connec on That cables are connected to relevant terminal points Storage tank connec on cables are connected to the indicated terminal points Solar system connec on...

Страница 26: ...5 2 bar is seen on the LCD display and then the filling valve is closed When the water pressure increases to 0 8 bar the LCD will show AP and the boiler will switch to automatic air vent mode In this...

Страница 27: ...tart up the boiler after all these processes are completed Commissioning must be strictly performed by authorized service At the end of the commissioning of the device after installation please ask fo...

Страница 28: ...to 80 C thanks to the heating water tempera ture increase button 4 Nu Button Domestic Hot Water Decrease Temperature Button The temperature of the domestic water can be decreased down to 30 C thanks...

Страница 29: ...E PRESSURE INDICATOR TEMPERATURE VALUE 70 100 Modula on 35 70 Modula on 0 35 Modula on FLAME MODULATION ICON 11 2 1 Flame Icon When operating between 0 and 35 capacity range the icon is displayed on t...

Страница 30: ...o the winter position the appliance will heat the water in the heating circuit until the domestic water is needed In the winter mode both the tap and the radiator icon are displayed on the LCD screen...

Страница 31: ...ion helps protect your device it does not protect your installation If device will not be operated for a while in places where there is risk of freezing then it is necessary to drain the water or to u...

Страница 32: ...oiler 2 If the error is s ll present or persists a er switch o on no fy authorized service of E C A 1 Switch o and on the boiler 2 If the error is s ll present or persists a er switch o on no fy autho...

Страница 33: ...or there is no contact 1 No fy authorized service of E C A F42 Water Fillin Auto Not Completed Water lling valve may be failed or mains water pressure may be insu cient 1 No fy authorized service of E...

Страница 34: ...delay Temperature sensors might be defec ve 1 No fy authorized service of E C A F201 Communuca on Fault Between Mainboard and MMI Mainboard MMI may be failed or communuca on cable may be failed 1 No f...

Страница 35: ...ses fuel consumption If you will leave your device in operation late at night keeping water temperature of the heating circuit at low levels will ensure saving If you feel that the room temperature is...

Страница 36: ...low Rate 15 60 14 20 24 28 30 KW 15 70 35 kW 0 00 1 00 2 00 3 00 4 00 5 00 6 00 7 00 8 00 0 00 0 50 1 00 1 50 2 00 2 50 3 00 H m Q m3 h 0 00 1 00 2 00 3 00 4 00 5 00 6 00 7 00 0 00 0 50 1 00 1 50 2 00...

Страница 37: ...37 15 INSTALLATION TEMPLATE 15 1 HM Model...

Страница 38: ...38 15 2 HCH Model...

Страница 39: ...39 15 3 HST Model...

Страница 40: ...5 24360 26100 30450 GJ 44 63 76 87 94 109 Energy efficiency Seasonal space heating 92 92 11 92 21 92 71 92 03 92 85 dB 44 46 47 49 50 52 Space Heating Temperature application Confeo Premix P Combi ERP...

Страница 41: ...8 dB 44 46 47 49 50 52 Annual electric consumption Annual fuel consumption Annual energy consumption Supplier s model identifier Space heating Water heating Efficiency Class Space Heating Temperature...

Страница 42: ...U 8 U O U n n n n n n nmn n n 9 8 1 6 2 00 1 4 0 3 1 6 5 0 2 9 8 6 6 7 00 2 1 0 3 2 6 2 0 1 0 n Bnc8Wn 9cLUFnMan8 Yi n nga n n 81U U8 U BU 4 8aYU8Rna 8 nJ 8cLUFn U Fln E M U ln MUn n n U U U E U UP F...

Страница 43: ......

Страница 44: ...h X EZ4T e i 4lz rlh7 l Y 4 h vR I4Y h5 lh4 Xh _ 7 Xh Xd7XhR VY J4Y h4 Y kFc h4 7 0 Q H4 mv 4T T l Xh T 7Y X Xlh e h9 T 7Xe h Ylk hS lB T rvl8 4 Xh v _ Ylh l 0 X 7XhR h7 4T v 4 vX X4 T lB W v T hS qvR...

Страница 45: ......

Страница 46: ......

Страница 47: ...PRODUCTION Organize Sanayi Bolgesi 3 Kisim Mustafa Kemal Bulvari No 13 45030 MANISA Tel 90 236 213 00 21 Fax 90 236 213 08 59 email emas emas com tr www emas com tr 7006991707 3 0...

Отзывы: