Chengdu Ebyte Electronic Technology Co., Ltd.
E831-RTU (6060-ETH) User Manual
Descript
ion:
19 05 21 14 00 13 55 50
The SN
code
of the device and the SN code of the device are not the same.
4.4.3 Network-related functional parameters take effect command (Ethernet restart command).
Modbus RTU protocol write register:
Send
01
06
00 67
00 01
F9 D5
Provision the
ModBus address
Functional
codes
address
Write a value
CRC check digits
Receivin
g
01
06
00 67
00 01
F9 D5
Provision the
ModBus address
Functional
codes
address
Write a value
CRC check digits
Modbus TCP protocol write register:
Send
00 01
00 00
00 06
01
06
00 67
00 01
Transmit
the logo
Protocol
identity
length
Unit
identification
Function
al codes
address
Write a value
Receivin
g
00 01
00 00
00 06
01
06
00 67
00 01
Transmit
the logo
Protocol
identity
length
Unit
identificatio
n
Functiona
l codes
address
Write a value
In particular, the
Ethernet component can be restarted by
writing a value of ox00 01 to the address ox 00 67, and the
restart must be performed after configuring the Ethernet-related parameters
order, otherwise the configured parameters do not take effect.
4. 4.4 WAN port IP information configuration
Modbus RTU protocol write WAN port IP register:
Se
nd
01
10
00 6B
00 07
0E
00 00 C0 A8 04 65 FF FF FF 00 C0 A8 04 01
BE 17
Provision a
ModBus
address
Fun
cti
on
cod
e
addres
s
Regist
er
lengt
h
The
number
of word
sections
Write a value
CRC
Checksum
code
Receivi
ng
01
10
00 6B
00 07
F0 17
Provision the ModBus
address
Functional
codes
address
Register length
CRC check digits
Modbus TCP protocol write register:
Se
nd
00 01
00 00
00
15
01
10
00 6B
00 07
0E
00 00 C0 A8 04 65 FF FF FF 00 C0 A8 04 01
transm
it
logoty
pe
agree
ment
logoty
pe
L
en
gt
h
Unit
logoty
pe
F
un
ct
io
na
l
co
de
addres
s
register
length
The
nu
mb
er
of
by
Write a value