Chengdu Ebyte Electronic Technology Co., Ltd.
E831-RTU (6060-ETH) User Manual
3.1 Register Address Table
Register
address
Number of
registers
Register
properties
Register type Register value
range
The default
value
Support
function code
00017
(0x0010)
1
DO1 switch output
Read/writ
e
0x0000 or
0xFF00 (0x05
Function
Code).
0-1 (0x01,
0x0F function
code).
--
0x01
0x05
0x0F
00018
(0x0011)
1
DO2 switching
output
Read/writ
e
--
00019
(0x0012)
1
DO3 switch output
Read/writ
e
--
00020
(0x0013)
1
DO4 switch output
Read/writ
e
--
00021
(0x0014)
1
DO5 switching
output
Read/writ
e
--
00022
(0x0015)
1
DO6 switch output
Read/writ
e
--
retain
10017
(0x0010)
1
DI1 switch input
read only
0-1
--
0x02
10018
(0x0011)
1
DI2 switch input
read only
--
10019
(0x0012)
1
DI3 switch input
read only
--
10020
(0x0013)
1
DI4 switch input
read only
--
10021
(0x0014)
1
DI5 switch input
read only
--
10022
(0x0015)
1
DI6 switch input
read only
--
retain
40049
(0x0030)
1
DI1 pulse count
value
read only
0-65535
--
0x03
40050
(0x0031)
1
DI2 pulse count
value
read only
0-65535
--
40051
(0x0032)
1
DI3 pulse count
value
read only
0-65535
--
40052
(0x0033)
1
DI4 pulse count
value
read only
0-65535
--
40053
(0x0034)
1
DI5 pulse count
value
read only
0-65535
--
40054
(0x0035)
1
DI6 pulse count
value
read only
0-65535
--
retain
40065
(0x0040)
1
DI 1-DI 6 pulse
count clears
to zero
Write
only
0x00 - 0x3F
--
0x06
retain
40078
(0x004D)
1
The device
address
Read/writ
e
1 - 247
0x01
0x03
0x06
0x10
40079
(0x004E)
1
Potrate rate
Read/writ
e
0 - 7
0x03
Copyright ©2012–2019 , Chengdu Ebyte Electronic Technology Co., Ltd.
14