background image

ALARM CONTROL UNIT 

 

CPX220NWB 

 

Installation and 

programming manual 

 

Version of the manual:   

 

 

v1.2 

Date of issue:   

 

 

 

2016.10.27 

Firmware version: 

 

 

 

2.6.3 

GPRS transmitter configurator version:   

1.3.64.3 

OSM server version: 

 

 

 

1.3.60.4 

 

Содержание CPX220NWB

Страница 1: ...ONTROL UNIT CPX220NWB Installation and programming manual Version of the manual v1 2 Date of issue 2016 10 27 Firmware version 2 6 3 GPRS transmitter configurator version 1 3 64 3 OSM server version 1...

Страница 2: ...l not be deemed to be providing any warranties either express or implicit including but not limited to any implied warranties of merchantability or fitness for a particular purpose unless it is requir...

Страница 3: ...3 6 4 ADDRESSING DEVICES CONNECTED TO THE KEYPAD BUS 21 3 7 WIRELESS KEYPAD KP1W 22 3 7 1 ADDING KP1W TO THE SYSTEM 22 3 7 2 DESCRIPTION OF KEYPAD ELEMENTS 23 3 7 3 KEYPAD SPECIFICATION 24 3 7 4 KEYP...

Страница 4: ...FAILURES HISTORY WITH SYSTEM DIODE 79 6 4 2 IGNORE ATS FAILURE 79 6 4 3 TURN AUTOMATIC OVERRIDE FOR FAILURE OFF 79 6 4 4 ACCESS TO ALARM AND FAULT MEMORY REQUIRES AUTHORIZATION 79 6 4 5 ALARMS AND INP...

Страница 5: ...DS FOR MANAGING THE PARTITIONS ZONES AND OUTPUTS 114 10 CHANGE HISTORY 123 LIST OF DRAWINGS AND DIAGRAMS DRAWING 1 DESCRIPTION OF PCB ELEMENTS 11 DRAWING 2 DESCRIPTION OF SCREW TERMINALS OF THE CONTRO...

Страница 6: ...e central unit is equipped with 3 outputs and 16 zones with the possibility to be divided into 2 partitions Dedicated KP16 LED keypad was designed in a modern discreet style Portable size large comfor...

Страница 7: ...assign any number of zones to each of them KEYBOARD cooperation with LED keyboard KP16 ability to connect up to three keypads TRANSMISSION Transmission of signals through GPRS SMS module Encryption of...

Страница 8: ...pad no sensors connected 120mA 1100mA 18VAC Average current consumption lack of external supply without keypad with keypad fully charged battery no sensors connected established connection with server...

Страница 9: ...t with additional input FL 10 Wireless Flood Detector Programmers Description GD PROG CPX Controll Panel Programmer SP PROG Universal Programmer SP PROG BT Universal Programmer with Bluetooth module M...

Страница 10: ...e keypad at the core diameter 0 5mm2 cannot exceed 200m 4 Install detectors and door and window reed relays Connect the installed elements with control unit For sample configuration of zones please re...

Страница 11: ...al GSM range The control unit is compatible with GSM antenna with male SMA connector This type of antenna should be install sellotape on nonmetalic surface plastic glass etc in vertical position foto...

Страница 12: ...iption of ERROR LED operation please refer to chapter 7 5 OK LED Green LED diode For the detailed description of OK LED operation please refer to chapter 7 6 CONF programming connector CONF IDC10 conn...

Страница 13: ...X220NWB included two types of antennas internal and external dipole type 433MHz internal antenna Internal antenna can be used wherever required compact size and antenna provides appropriate coverage l...

Страница 14: ...rnal antenna dipol type Antenna should be connected to GND and ANT connector regardings to the color on the endings of the wires Before screw the antenna remove plastic element from GND socket Correct...

Страница 15: ...MANUAL 15 123 3 3 DESCRIPTION OF SCREW TERMINALS OF THE CONTROL UNIT NOTE Any assembly and installation works shall be carried out with power supply off and battery disconnected Drawing 2 Description...

Страница 16: ...ally closed NC or normally open NO as well as with assigned parameters EOL NO or EOL NC using 2 2k resistors or with assigned double parameters DEOL NO or DEOL NC using 1 1k resistors Both resistor ty...

Страница 17: ...ER MANUAL 17 123 3 5 SAMPLE CONNECTION OF SIGNALLING DEVICE 3 5 1 Internal signalling device without independent source of power supply Drawing 4 Sample connection of internal signalling device withou...

Страница 18: ...ARM CONTROL UNIT INSTALLER MANUAL 18 123 3 5 2 External signalling device with independent source of power supply Drawing 5 Sample connection of external signalling device with independent source of p...

Страница 19: ...nd control unit operation After first pressing any button the keypad is backlit After a few second idle time backlight gets automatically dimmed In order to make codes easier to remember buttons are m...

Страница 20: ...normal operation it means that the line it is assigned to was disrupted Flashing LED means the zone was interlocked After activating service functions LEDs display data 7 Screw terminals The connector...

Страница 21: ...ld choose the appropriate screws indywidually 5 Connect cables joining the keypad with the alarm control unit Keypad terminals marked KT KR KP KG shall be connected with KT KR KP KG terminals in the a...

Страница 22: ...he wireless keypad KP1W uses one way transmission and cannot receive communication from the control panel Therefore we suggest to set one of the central panel outputs in arming disarming signalization...

Страница 23: ...ns 0 9 buttons and as well as are intended for keypad and control unit operation After first pressing any button the keypad is backlit After a few second idle time backlight gets automatically dimmed...

Страница 24: ...tion Power supply 1 battery CR123A 3V Working time 3 years Frequency of operation 433 92 MHz Communication range up to 500m open air Communication one way Average current consumption 30 A Operation te...

Страница 25: ...as the battery is inside two LEDs for battery red one for transmission blue one and keys backlight will light up temporarily 5 Put together the front part of the case with the back one starting from t...

Страница 26: ...cation The radio waves are attenuated by walls and other obstacles Lowest attenuation have wallboards and wooden frame Medium attenuation have light concrete and brick walls Reinforced concrete and me...

Страница 27: ...CPX220NWB ALARM CONTROL UNIT INSTALLER MANUAL 27 123 Drawing 11 Signal loss through construction materials...

Страница 28: ...ONS The wireless detectors should be located relative to the panel in such a way as to be on the same side of the control panel as the radio antenna and electronic components In this way you get the b...

Страница 29: ...evant to a given option of the function on off Press 1 to 9 buttons to change the status of LED and the option it corresponds to Options 10 16 may be changed by long press the buttons 0 6 The installe...

Страница 30: ...r the control unit s reset using configured parameters The device will exit test mode automatically after 5 minutes without pressing the buttons and system will restart 4 3 INSTALLER MENU After enter...

Страница 31: ...ettings That function resets the settings to their default configuration accessible from the service mode level Additionally the function sets the default output options and default installer code The...

Страница 32: ...ee access failures If this option is enabled the keypad will be blocked for 90 seconds after entering an invalid code three times After this period another lock will occur after entering a wrong code...

Страница 33: ...ring number 00 will change the parameters for all zones in the system Y number of parameter related to a given zone 0 complex function the initiation of which configures the parameters listed below as...

Страница 34: ...for zone 1 using complex functions zone 1 is to be set as immediate circuit in NC mode to be blocked after 8 violations and generate alarm when violated after arming with the 500ms sensitivity 4 3 7...

Страница 35: ...n arm disarm o 7 chirp on arm disarm and signalling alarm 2 time of output activation in seconds DEC type parameter if 0 is set output will operate in bi stable mode It is possible to configure the ch...

Страница 36: ...eter 4 alarm time in the partition in seconds DEC type parameter 5 partition options BIT type parameter o 1 Quiet signalling of time for entering during counting the time for leaving the buzzer in a k...

Страница 37: ...sed Eg If the auto arming time is set to 2 30 and time was changed forward from 2 00 to 3 00 the control panel will not arm Examples a change of a single parameter assigning 1 2 3 zones to the first p...

Страница 38: ...a sensor After selecting this option you can confirm deleting by pressing key or you can cancel function by pressing key 2 Add a sensor After selecting this option the sabotage button on the sensor h...

Страница 39: ...ignal strength To return to line selecting menu press or To exit the function press or if no key has been selected 4 3 9 3 Delete all wireless sensors To remove all wireless sensors from the system en...

Страница 40: ...remote control o 1 P300 remote control o 2 RC 10 remote control 4 The use to which the remote control is assigned 5 6 7 8 buttons functions o 0 no fuction o 1 arm o 2 disarm o 3 alarm o 4 silent alar...

Страница 41: ...ttern XX Y where XX emergency button 01 fire 02 help 03 panic 00 all buttons above Y enable disable emergency button 0 disable emergency button 1 enable emergency button o 1 output 1 o 2 output 2 o 3...

Страница 42: ...refused access to text messages Choice of installer s permissions can be accepted by pressing the button CPX220NWB can store up to 10 phone numbers and up to 32 text messages If for any reason the SM...

Страница 43: ...PARTITION2 default partitions names they can be changed with the SETNAME command X Y partition states possibile values 0 disarmed 1 armed GETARMED ERROR command rejected by the system Setting the name...

Страница 44: ...ption GETNAME PARTITION NR VALUE partition name GETNAME ERROR command rejected by the system Setting the phone number Command syntax XXXX SETTELNUM ID NUMBER Command description Setting the phone numb...

Страница 45: ...k message description GETTELNUM ID NUMBER information about phone number GETTELNUM ERROR command rejected by the system Setting the content of text message Command syntax XXXX SETMESSAGE ID MESSAGE Co...

Страница 46: ...tting the content of text message under the pointed index XXXX user code ID index of text possible values 1 to 32 Example 1234 GETMESSAGE 30 Feedback message GETMESSAGE ID MESSAGE or GETMESSAGE ERROR...

Страница 47: ...es Each digit counting from the left represents an index of the phone number first digit for the first phone number second digit for the second number and so on 0 message will not be send to this numb...

Страница 48: ...number assigned to the specified event XXXX user code EVENT a short name of the event possible event names are listed at the end of this chapter Example 1234 GETUSERSMS ARM1 Feedback message GETUSERSM...

Страница 49: ...zones 1 16 ended INPUT1 TAMPER to INPUT16 TAMPER Sabotage of zones 1 16 INPUT1 TAMPEREND to INPUT16 TAMPEREND Sabotage of zones 1 16 ended INPUT1 LOCK to INPUT16 LOCK Bypass of zones 1 16 INPUT1 UNLO...

Страница 50: ...BEGIN Help alarm started KEYPAD SILENTALARM BEGIN Panic alarm started KEYPAD FIRE END Fire alarm ended JAMMING BEGIN GSM jamming JAMMING END GSM jamming ended DETECTOR1 LOST to DETECTOR16 LOST Detect...

Страница 51: ...serted before the configuration settings transmission is initiated In this case use either SIM cards with PIN code authorization deactivated or change the PIN code using a mobile phone before the card...

Страница 52: ...ed settings you can use it for programming another equipment First indicate a directory where the file was saved then give the file name User can modify the received data In order to be effective the...

Страница 53: ...onnector of the alarm control unit The connection is executed through a dedicated programming cable using RS 232 serial port To program the equipment or perform other activities i e read the settings...

Страница 54: ...pl Enter the port on which analyser will listen to instructions e g 9000 Click Add button to confirm the setting The connection is saved and moved to the table From that moment the program will enable...

Страница 55: ...ystem is installed with at least one GSM modem connected If the device is registered for the server serial number and SIM card number see OSM 2007 Manual you can use the connection via OSM Provided th...

Страница 56: ...3 and then use it for other devices You can use that function after you define a type and parameters of the connection E g for local connection the following window is displayed where Connection type...

Страница 57: ...uration with default values Upon confirmation the connection definition window will be displayed The operation is possible using local connection only After the operation is completed the equipment pa...

Страница 58: ...the equipment Switch the power off and disconnect the programming cable or switch the programming device into DEBUG mode Insert SIM card Re connect the power supply The equipment is ready for operatio...

Страница 59: ...e server in Equipment tab it will be marked green Start the software and define the options of the equipment for description please refer to chapter 7 Select Send function The window will appear where...

Страница 60: ...on mode Depending on user s preferences the equipment can operate in one of 4 modes to be selected from a drop list GPRS SMS GPRS transmission TCP IP protocol in standard and in case of problems with...

Страница 61: ...as often as in case of GPRS transmission is usually undesirable That parameter allows significant extension of interval between tests time in minutes or disabling that option 6 1 1 5 Telephone number...

Страница 62: ...puter on which Communication server software is installed e g 89 123 115 8 The address can be given as a server s domain name e g modul gprs com In such a case at least one DNS server address is requi...

Страница 63: ...ent will retry to connect with a server in case the previous attempt was unsuccessful 6 1 4 4 Number of attempts of establishing connection with a server You can define how many times the equipment wi...

Страница 64: ...e changed via OSM 2007 Console In such case please send following Custom command SETPARAM 3 1 new_code where new_code should contain from 4 up to 7 digits 6 1 5 3 SIM Card PIN code Since the equipment...

Страница 65: ...e maximum transmission security the data transmitted are encrypted using AES The option can be used for both GPRS and SMS transmissions In case encrypted transmission was selected you can enter own da...

Страница 66: ...figuration types are available NO NC EOL NO EOL NC DEOL NO DEOL NC Wireless NC type input must be closed for the whole time Line interruption causes its induction NO type input remains open It activat...

Страница 67: ...on of the zone event without the alarm In case of trigger when partition is armed it generates violation of the zone event and raises the alarm Interior delay the line can be used when keypad is not i...

Страница 68: ...ll be generated which allows to inform the monitoring station about the problem with the line This lock will last until disarming If the input is selected as the Alarm after time for exit then Interlo...

Страница 69: ...larm is generated 6 3 1 6 Alarm after time for exit When selected the alarm will be generated if the line remains violated when the time to exit is up When deselected alarm will NOT be generated in ab...

Страница 70: ...vent the accidental transmissions from other detectors only one detector cover should be removed during the procedure of adding a new detector In order to add a wireless input click Add Device New win...

Страница 71: ...waiting for a wirells signal to come User has to press for a while the tamper switch on the sensor CPX220NWB will detect the transmission and print sensor s type and ID To bind this sensor with the A...

Страница 72: ...CPX220NWB ALARM CONTROL UNIT INSTALLER MANUAL 72 123 Sensor preferences can be set now in the Inputs tab You can choose the same options as for wired zones excluding sensitivity...

Страница 73: ...eturn will be ignored 6 3 3 2 Entry Exit The parameter allows switching off the indication of time for entry exit displayed by KP16 keypad 6 3 3 3 Time for exit It is time for leaving the partition As...

Страница 74: ...r each input line is available Interlocking after time for exit option If this option is active in the case of arming with violated zone after time for exit will be generated event about blocked zone...

Страница 75: ...ommunication loss Output is activated when information transmission to server is not possible GSM jamming indicator Output is activated when jamming GSM Chirp The output is activated when arming 1 chi...

Страница 76: ...changed only with remote command 6 3 5 Remote controllers Configurator allows adding and configuring remote controllers in the same way as it was done in the Wireless Inputs configuration In order to...

Страница 77: ...rom Button 1 to Button 4 Remote controller can have less then 4 buttons in that case additional Button colums should be left with the None option selected NOTE The selected user number must be activat...

Страница 78: ...unction key support Events associated with emergency buttons will be transmitted to monitoring station only if they are enabled in the Monitoring tab see item 6 6 6 3 6 2 Outputs User can choose which...

Страница 79: ...Selecting this option turns off signaling a loss of communication with the server on KP16 keypad 6 4 3 Turn automatic override for failure off Selecting this option enables the system fault signal whe...

Страница 80: ...ress event Each user has his own duress code NOTE Firmware versions older than 2 1 0 do not support the duress code Upgrading the Firmware to version 2 or newer one has to make sure that there are no...

Страница 81: ...be selected in the writing options Users configuration changes can be made only via programming cable Users update is not possible remotely via GPRS 6 6 MONITORING That option allows determining whic...

Страница 82: ...s Clear button to remove all checked signals Press Reverse to reverse the check into the opposite ones 6 6 1 2 SMS ON OFF In these columns you can check which signals are to be reported to the monitor...

Страница 83: ...ents to monitoring station via GPRS SMS The data may become valuable information about device s work conditions though it may increase amount of bytes sent through GSM network It is possible to define...

Страница 84: ...ly Available options are Restrict all Means no possibility of communication Allow all Means that communication is allowed from any telephone number Allow selected Means that communication is allowed o...

Страница 85: ...m these listed telephone numbers You can define up to 5 numbers When Allow selected box is checked you receive access to an edit box Enter the subsequent numbers in the box and click Add button to mov...

Страница 86: ...important mainly for economic reasons Check the Activate SMS restrictions check box to activate the access to information groups subject to restrictions SMS tests to server SMS events sent to server...

Страница 87: ...6 7 2 Remote commands 6 7 2 1 Users remote management enable Selecting this option allows you to remotely configure user accounts...

Страница 88: ...fy users about occurrence of certain events by text message Before sending the message may occur an additional attempt a voice call see item 6 8 4 Options In order to add user s number to the notifica...

Страница 89: ...e has to typed in the Messages tab These messages can be later assigned to specific events in the Events tab Before sending the message may occur an additional attempt a voice call see item 6 8 4 Opti...

Страница 90: ...he Message column select one of the messages defined before To assign a number to an event a corresponding column from Num 1 to Num 10 has to be checked From now on whenever this event occurs a text c...

Страница 91: ...call the device sends an SMS message Sending a message to the first user the first defined phone number is followed by an attempt to call the next user and send a message And so on A voice call to a...

Страница 92: ...CPX220NWB ALARM CONTROL UNIT INSTALLER MANUAL 92 123...

Страница 93: ...one number can be composed of an empty sequence which means it is applicable to any telephone number Rules are processed in accordance with a pre defined sequence from the beginning to the end i e the...

Страница 94: ...ters defining the equipment s response after leaving GSM network You can define after what time from the moment the connection was lost the equipment shall initiate activities aiming at its restoratio...

Страница 95: ...nd is defined in minutes Then define what activity shall be initiated by the equipment Select by checking an appropriate box at the response description Modem reset Device reset In case the equipment...

Страница 96: ...ow the equipment will operate under the control of a new firmware NOTE The firmware update procedure shall be carried out with special care as improperly performed operation can prevent the correct op...

Страница 97: ...quipment The control unit has an event log memory where about 5 thousand technical events can be recorded You can review the events history via GPRS and RS232 connection In the second situation first...

Страница 98: ...CPX220NWB ALARM CONTROL UNIT INSTALLER MANUAL 98 123...

Страница 99: ...ashing green LED 1 8 blinks The operation mode of the equipment is indicated by green LED which goes on for 2 seconds after the range is indicated In case the LED does not go on for 2 seconds after th...

Страница 100: ...ootloader remains in the equipment and repeated equipment programming is possible Description LEDs OK green ERROR red STATUS yellow No software in the equipment Software update Decryption of firmware...

Страница 101: ...he control panel The battery capacity should be sufficient to operate the system without a power supply for 12 hours In the GPRS Transmitters Configurator see item 6 4 or in the installer menu see ite...

Страница 102: ...arms is available only after user code has been entered information about alarms memory is available only after user code has been entered information about failures is available only after user code...

Страница 103: ...les below The newly configured parameter will be taken into account when the device will need to use it there is no need to restart the unit However there are parameters changes to which will be detec...

Страница 104: ...ress Limitations Data length to 31 characters can be changed by ATS only Description Sets the OSM server address with which the device exchanges data Server_address can be given in the domain format e...

Страница 105: ...e zone 1 bit 2 the zone 2 etc If the zone is impaired the bit is set Examples RLIMIT 6 Removes blocade from zone 1 and zone 2 RLIMIT 2 Removes blocade from zone 1 9 1 1 9 DT Format DT YY MM DD hh mm L...

Страница 106: ...etwork and re registering to GSM and GPRS network when you restart the device and modem 9 1 2 4 DESC Format DESC Limitations Can be executed by ATS only Description Returns a string with a description...

Страница 107: ...equal to 0 or 1 possible to execution only by ATS Description For x 0 it clears the queue of outstanding events to be sent to the OSM server This results in the loss of outstanding events the device...

Страница 108: ...1 2 10 GETPARAM Format GETPARAM parameter Limitations Parameter is equal to APN or UN or PW or Server or PORT or SMS or SMSPERIOD or as id_typu index possible to execution only by ATS Description All...

Страница 109: ...scription Verifies the user code specified as an argument of the command checks whether a user with the specified code exists Password is the password of the user id is the user number partitions are...

Страница 110: ...r of the user whose authorizations are changed the partitions is the bit vector with the partitions to which the user should have the authorization bit 0 corresponds to the partition 1 bit 1 to the pa...

Страница 111: ...user s password Id is the user identifier whose password is changed the password is his new password and the adminPassword is the system administrator password The command returns CPSETUSERPASSWORD E...

Страница 112: ...ADDUSER EOK id partitions When a user is added CPADDUSER EALREADY_EXISTS id partitions If the specified user already exists CPADDUSER EID id partitions If the specified user ID is incorrect CPADDUSER...

Страница 113: ...through an encrypted way you do not need to know the administrator password the user id 0 The command needs the option Allow remote user management to be set active in the Configurator Can be executed...

Страница 114: ...to the tamper keypad 1 bit 2 corresponds to the tamper keypad 2 bit 3 corresponds to the tamper keypad 3 bit 7 corresponds to the alarm from remote controls zoneTampers is a bit vector indicating the...

Страница 115: ...a bit vector indicating detectors power failures in wireless detectors means low battery in wireless detectors Bit 1 counting from 0 corresponds to the zone 1 bit 16 corresponds to the zone 16 partiti...

Страница 116: ...failures of power supply outputs Bit 0 means the output KPOUT bit 1 means the output AUX1 bit 2 means the output AUX2 powerInFailures is a bit vector informing about the failures of power supply Bit...

Страница 117: ...ctor is optional It means that partitions in the bit vector will be armed in stay mode It is not allowed to change arm mode of an already armed partition system will reject an attempt of arming in sta...

Страница 118: ...al to zero has no sense since it does not change anything if the partitions is 0 the user s password is not checked and the status returned by the command is equal to EOK Password is the code of the u...

Страница 119: ...nts to block Bit 1 counting from 0 means the zone 1 Sending a command with the argument of zones equal to 0 has no sense since it does not change anything Password is the system administrator or user...

Страница 120: ...bit vector indicating the zones which one wants to unblock Bit 1 counting from 0 means the zone 1 Sending the commands with the argument of zones equal to 0 has no sense since it does not change anyth...

Страница 121: ...is the system administrator or user password Returns a list of zones assigned to the partition in the format CPPARTITIONSGETZONES P1Zones P2Zones Where P1Zones P2Zones are the bit vectors indicating...

Страница 122: ...em dministrator or user password Returns a list of outputs assigned to the partition in the format CPPARTITIONSGETOUTPUTS P1Outputs P2Outputs Where P1Outputs P2Outputs are the bit vectors indicating w...

Страница 123: ...e Version Firmware Description 2016 08 29 i1 0 2 5 2 First version of the manual 2016 10 21 i1 1 2 6 2 Added information about smoke detector SD 20 and wireless keypad KP1W 2016 10 27 i1 2 2 6 3 Added...

Отзывы: