background image

12 

EP100 Master Instruction 

 

_____________________________________________________ 

 

 

 

D00002-C-04 

7 START-UP 
7.1 General 

First of all, the nameplate should be checked, 
especially with respect to references to Ex / non- Ex, 
input signal, single / double acting. 
Before starting the positioner the EP100 has to be 
mounted to the actuator; an input signal 4 to 20 mA or 
split range have to be available. The supply air 
connection must have sufficient capacity and 
pressure of 1.4 to 6 bar (20 to 90 psig) and should not 
exceed the maximum operating pressure of the 
actuator. 
The EP100 can be adjusted by means of switches 
and potentiometers when the housing cover is 
opened. 
 

Attention:

 Configuration using switches and 

potentiometers may interfere with operation of the 
actual process! During configuration it is 
recommended that there is no flow through the 
valve. 
 
At initial start-up various adjustments have to be set. 
The following procedure is recommended:  
 

  Setting of 

direction of rotation

 of feedback lever 

(chapter 7.2) 

  Setting of 

input signal range

 e.g. 4 to 20 mA or 

split range (chapter 7.3) 

  Setting of 

gain

 (chapter 7.4) 

  Setting of 

zero and span

 (chapter 7.5) 

  Setting of 

damping

 (time constant, chapter 7.6) 

  The 

position indicator

 12 is attached to the 

desired position after selection of the 
transmission at indicator shaft (chapter 7.7) 

  The 

air capacity throttles

 at the pneumatic 

output (screws 17 and 18 underneath of the 
SERVICE openings) are factory-set to the 
operating value and are normally not reset 
(exception see chapter 7.8). 

  When attaching the 

housing cover

 make sure 

that the venting opening points to the bottom 

 
 

Settings via switches and potentiometers 

For the setting of the EP100 and the adjustment of 
various parameters 8 dip switches and 5 
potentiometers are available. 
 
See electronics imprint as follows: 
 
 
 
 
 
 
 
 
 

1) Adjustment of electronic board (in workshop, see page 17) 

 

 
The potentiometers are for the setting of: 

  Zero point (ZERO): P3 

  Span (S): P2 

  Gain (G): P4 

  Damping (D): P5 

  Electronics alignment: P1 

1)

 

 
Single-threaded potentiometers with limited rotation angle to 
set gain (G) and damping (D) are available, where the actual 
position is indicated by an arrow. To set zero point (ZERO), 
span (S) and the electronics alignment

1)

  multiplethreaded 

potentiometers (approx. 30 rotations) without rotation 
limitation are used. 
 
The 

switches

 are for the setting of: 

  Direction of rotation of feedback lever (switches 1, 2) 

  Electronics adjustment (switch 3) 

1)

 

  Signal range (switches 4, 5, 6 and 7) 

  Pneumatic test (switch 8) 

 
The switch numbers (1 through 8) are imprinted on the 

electronics. The possible switch position (“I” and “II”) are 

imprinted below switch 8. The switch positions are defined as 
follows: 
 
Switch Position 

“I”:

                   Switch Position II: 

 

 

Caution! 

Switches 3 and 8 must be during operation in position “I”. 

Prior to resetting switches 1 to 8 it is recommended to shut-
off the respective part of the installation since processes are 
activated influencing and disturbing the current process. 
Therefore, it is recommended that no medium flows through 
the valve during configuration.. 

Содержание EP100

Страница 1: ...tiometers Load 300 Low air consumption Angle range up to 95 degree Supply air pressure up to 6 bar 90 psig Single acting or double acting Mechanical travel indicator Reverse polarity protection and in...

Страница 2: ...ng of Input Signal Range Split Range 14 7 4 Gain G 15 7 5 Zero ZERO and Span S 15 7 6 Damping D 15 7 7 Travel indicator 15 7 8 Air reducing throttles 16 7 9 Basic adjustment of electronics 16 7 10 Pne...

Страница 3: ...ter P5 The resulting internal signal is guided to the analog control circuit 11 the gain of which is adjustable via potentiometer P4 The output of the control circuit drives the electromechanic conver...

Страница 4: ...ge SELV or SELV E Safety precautions taken in the instrument may be rendered ineffectual if the instrument is not operated in accordance with the Master Instructions Limitation of power supplies for f...

Страница 5: ..._________________________________________ D00002 C 04 2 LABELS A Nameplate B Additional label for option Limit switches Nameplate Example EP100 Device specification Model Code SER No Serial number ECE...

Страница 6: ...d 1 4 18 NPT for output II y2 8 Direct connection hole for output I y1 9 Feedback shaft 10 Connection manifold for mounting to linear actuators 11 Connection base for mounting to rotary actuators 12 T...

Страница 7: ...x B x H 101 5 x 60 x 100 5 mm 3x 1 4 18 NPT Code LEXG G Booster for double acting positioner L x B x H 121 x 39 x 81 mm 3x 1 4 18 NPT Code LEXG M Connection manifold for double acting positioner with...

Страница 8: ...d Any unused threaded holes are closed by plugs Caution Prevent accumulation of water in the instrument in this mounting position by sealing cable entry against water Provide a continuous supply of dr...

Страница 9: ...herefore the rotary adaptor 3 must be mounted so that approx 1 mm 0 04 inch of clearance results between the drive shaft 1 and the rotary adaptor 3 This is achieved by placing an appropriate number of...

Страница 10: ...lanation of abbreviatons s Supply air y1 d Output 1 for direct mounting depressurized at currentless electronics When using this output y1 as to be closed by means of hex screw y1 Output 1 depressuriz...

Страница 11: ...oss sections of 0 3 to 2 5 mm2 22 14 AWG Note When connecting shielded cable connect the cable shield only to the system Do not connect the cable shield to the EP100 Connection to terminals pos 3 3 11...

Страница 12: ...VICE openings are factory set to the operating value and are normally not reset exception see chapter 7 8 When attaching the housing cover make sure that the venting opening points to the bottom Setti...

Страница 13: ...opens rotating to the left Actuator opens rotating to the right L R Direction of rotation of feedback shaft of the double acting actuator is a o determined by the mounting side and the tubing of the...

Страница 14: ...e with the standard signal 4 to 20 mA individual valve positions may be allocated to each device which also may overlap if necessary This function is useful if an additional control range is demanded...

Страница 15: ...vior of the actuator at a discontinuous change of the input signal The input signal is provided with an additional time constant for this purpose The time constant is only noticeable in the position c...

Страница 16: ...factory adjusted an adjustment at delivery is not required The potentiometer is secured by means of lacquer against unintentional operating In the event an adjustment of the electronics becomes necess...

Страница 17: ...nnection plugged Exchange filter see page 18 Actuator moves to end position Positioner mounted on wrong side or switch1 2 set faulty R L Check mounting side as per table page 13 Pneumatik test still a...

Страница 18: ...ed Tight fitting plugs can be easily removed by tilting them diagonally inward before pulling them off Connect plugs 41 and 42 to the new electronics unit 40 and attach the new unit by using the 7 scr...

Страница 19: ...4 2 Preamplifier replacement Unscrew the preamplifier 45 from the base plate by removing screws 46 and 47 Replace 4 O rings between preamplifier 45 and base plate1 and install new preamplifier 10 4 3...

Страница 20: ...ted to each other without an intermediate transmission The control vanes are therefore moving simultaneously with the same angle rate as the feedback lever The length of the control vane corresponds w...

Страница 21: ...lights up After 2s both LED s are light up again the value for 20mA is stored Random adjustment of the current values at the end points a Move the actuator to the end position where you want to adjus...

Страница 22: ...in a certain portion of this conduct variable an individual EP100 is to be provided for each actuator The zero and span of which can be set to the respectively desired partial range of the conduct va...

Страница 23: ...o alterations reprinting copying and translation prohibited Products and publications are normally quoted here without reference to existing patents registered utility models or trademarks The lack of...

Отзывы: