14
Operation
DIP
switches
Posi-
tion
Function
3
ON
Correction characteristic for adjustment of the
operating characteristic
(linearization of the process characteristic
CHARACT
)
6)
OFF Linear characteristic
4
ON
MANUAL operating state manual
OFF AUTO AUTOMATIC operating state
5)
Factory setting can be changed via communications software.
6)
The characteristic type can be changed via communications
software
Tab. 6: Function of the DIP switches
Information about the communications software:
The switching position of the DIP switch has priority over
the communications software!
If the values of the sealing function (
CUTOFF
) or the cor-
rection characteristic (
CHARACT
) are changed via the
software tool, the corresponding function must be active
(DIP switch set to ON).
The effective direction of the set-point value (
DIR.CMD
) can
be changed via the Dip switches only.
7.2.3 Display of the LEDs
LED 1, green
(MODE
)
display of the operating states
AUTO, MANUAL,
X.TUNE
LED 2, green / yellow
(POSITION
)
display of the actuator state
(open, closed, opens or closes)
LED 3, red (
FAULT
)
fault states
Fig. 5:
LED display
LED 1 (green,
MODE
) and LED 3 (red,
FAULT
)
LED states
Display
green
red
on
off
Acceleration phase when Power ON
flashes slowly
off
AUTO operating state
flashing
flashing MANUAL operating state
alternating
flashes quickly
off
X.TUNE
function
off
on
ERROR (see chapter entitled
“7.3 Error messages”)
flashing
flashing AUTO operating state for sensor
break detection
slow
Tab. 7: LED states, LED 1 and LED 3