Operating instructions

W3G990-GZ02-91

`

II 2G Ex d e ib IIB T3 Gb

IBExU14ATEX1123 X /05

`

Translation of the original operating instructions

54008-4-8670

5.5 Connection screen

Shading => terminals not assigned

No.

Conn.

Designation

Function / assignment

1

PE

Earth connection, PE connection

1

L1

Mains supply connection, supply voltage 3-phase, 380- 440 VAC, 50/60 Hz

1

L2

Mains supply connection, supply voltage 3-phase, 380- 440 VAC, 50/60 Hz

1

L3

Mains supply connection, supply voltage 3-phase, 380- 440 VAC, 50/60 Hz

1

HZ

Not used (optional: internal heating element)

2

RSA

Bus connection RS485; RSA; MODBUS RTU; double terminal (SELV)

2

RSB

Bus connection RS485; RSB; MODBUS RTU; double terminal (SELV)

2

GND

Signal ground for control interface (SELV)

2

Ain1 U

Analogue input 1, set value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only for use as alternative to input
Ain1; SELV

2

+10 V

Fixed voltage output 10 VDC, +10 V +/-3%, max. 10 mA, short-circuit-proof, power supply for ext. devices
(e.g. potentiometer); SELV

2

Ain1 I

Analogue input 1, set value: 4-20 mA; Ri = 100 Ω, parametrisable curve, only for use as alternative to input
Ain1 U; SELV

2

Din 1

Digital input 1: Enabling of electronics,
Enabling: Pin open or applied voltage 5-50 VDC
Disabling: Bridge to GND or applied voltage <1 VDC
Reset function: Triggers software reset after a level change to <1 VDC; SELV

2

Aout

Analogue output 0-10 VDC, max. 5 mA, output of the current motor level control coefficient / motor speed
parametrisable curve; SELV

2

Din 2

Digital input 2: Parameter set 1/2 switching, depending on EEPROM setting, the valid/used parameter set can
be selected via the bus or via the digital input DIN2.
Parameter set 1: Pin open or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage <1 VDC; SELV

2

Din 3

Digital input 3: Controller function of integrated controller; depending on EEPROM setting, normal / inverse can
be selected for the controller function of the integrated controller via the bus or the digital input
Normal: Pin open or applied voltage 5-50 VDC
Inverse: bridge to GND or applied voltage <1 VDC; SELV

2

Ain2 U

Analogue input 2, actual value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain2; SELV

2

+20 V

Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof, power supply for ext.
devices (e.g. sensors); SELV
Alternatively: +24 V DC input for parametrisation via MODBUS without mains power

2

Ain2 I

Analogue input 2, actual value: 4-20 mA, Ri = 100 Ω, parametrisable curve, only for use as alternative to input
Ain2 U; SELV

2

NO

Status relay; floating status contact; make for failure

2

COM

Status relay, floating status contact, common connection, contact rating 250 VAC / max. 2 A (AC1) / min. 10
mA

2

NC

Status relay; floating status contact; break for failure

Item no. 54008-5-9970 · ENG · Revision 87791 · Release 2016-04-29 · Page 13 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание IBExU14ATEX1123

Страница 1: ...are available in other languages on our website www ebmpapst com 2 2 SAFETY REGULATIONS AND NOTES 2 2 1 Levels of hazard warnings 2 2 2 Staff qualification 2 2 3 Basic safety rules 2 2 4 Electrical vo...

Страница 2: ...efects which impair safety must be rectified immediately Do not make any modifications additions or conversions to the device such as modifying the guard grille or attaching other equipment to the wal...

Страница 3: ...el greater than 70 dB A may arise Danger of noise induced hearing loss Take appropriate technical safety measures Protect operating personnel with appropriate safety equipment e g hearing protection A...

Страница 4: ...with explosion subcategories IIA and IIB and temperature classes T1 to T3 Only using the device in stationary systems Using the device only in resonance free speed ranges to avoid spark formation Pun...

Страница 5: ...g M20x1 5 4 Cable diameter min 10 mm max 14 mm tightening torque 6 0 6 Nm standard value depending on cable 5 Attachment screws for terminal box cover M4x20 tightening torque 3 5 0 5 Nm 6 Earth connec...

Страница 6: ...A Output 20 VDC max 50 mA Output for slave 0 10 V Operation and alarm display Input for sensor 0 10 V or 4 20 mA External 24 V input programming External release input Alarm relay Integrated PID contr...

Страница 7: ...l number Ex identification II 2 G Ex d e ib IIB T3 Gb Element Explanation Ex marking according to 2014 34 EU II Device group II use above ground not mining 2 Category 2 Zone 1 Category 3 Zone 2 G Ex a...

Страница 8: ...ny forces into the device which would cause strain and affect the gaps During installation make sure not to bend or pry the device in order to avoid mechanical tension Verify that all rotating parts c...

Страница 9: ...lish a safe protective earth connection Ensure compliance with the protection rating The seals in the terminal box from ebm papst have been inspected for their suitability The motor must be connected...

Страница 10: ...cting cables with terminals Open the terminal box To do so unscrew the seven attachment screws for tightening torque see chapter 4 1 Product drawing Take care when opening the terminal box cover Do no...

Страница 11: ...onnections and cable glands have been tightened to the specified torque 5 3 3 1 Exchange of screwed cable glands and plug screws If you would like to replace screwed cable glands or plug screws for ex...

Страница 12: ...tings Factory settings with which the device is pre set by ebm papst Control mode parameter set 1 PWM controlling Control mode parameter set 2 PWM controlling Fan device adress 01 Max PWM 100 Min PWM...

Страница 13: ...current motor level control coefficient motor speed parametrisable curve SELV 2 Din 2 Digital input 2 Parameter set 1 2 switching depending on EEPROM setting the valid used parameter set can be select...

Страница 14: ...nd PE are short circuited outside the potentially explosive area e g on the main switch Disconnect the connection line on the device When disconnecting be sure to disconnect the earth wire connection...

Страница 15: ...load back pressure too high Correct the operating point Let the device cool down To reset the error message switch off the mains supply voltage for a min of 25 s and switch it on again Alternatively r...

Страница 16: ...test At least every 3 months Replace the device in the event of noise stiffness or bearing play Have the motor bearings replaced by ebm papst Vibration test See Vibration test section At least every...