Ebmpapst IBExU14ATEX1123 Скачать руководство пользователя страница 15

Operating instructions

W3G990-GZ02-91

`

II 2G Ex d e ib IIB T3 Gb

IBExU14ATEX1123 X /05

`

Translation of the original operating instructions

54008-4-8670

Impeller running
roughly

Imbalance in rotating
parts

Clean the device;
replace if unbalance
is still found after
cleaning. Make sure
no weight clips are
moved, damaged or
removed during
cleaning.

Motor does not turn

Mechanical blockage

Switch off, de-
energise, and
remove mechanical
blockage.

Mains supply voltage
faulty

Check mains power,
restore power
supply. Attention! The
error message resets
automatically. The
device starts up
again automatically
without advance
warning.

Faulty connection

De-energise, correct
connection, see
connection diagram.

Motor winding broken Replace device
Insufficient cooling

Improve cooling. Let
the device cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message by
applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.

Ambient temperature
too high

Reduce the ambient
temperature. Let the
device cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message by
applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.

Impermissible
operating point (e.g.
excessive load, back
pressure too high)

Correct the operating
point. Let the device
cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message by
applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.

Mounting screws
of terminal box
broken during
closing

Replace device

If you have any other problems, contact ebm-papst.

7.1 Cleaning

NOTE
Damage to the device during cleaning

Malfunction possible
→ Do not clean the device using a water jet or high-pressure

cleaner.# Do not use any acid, alkali or solvent-
basedcleaning agents.# Do not use any pointed or sharp-
edged objects for cleaning

Regular cleaning of the device prevents unbalance caused by
deposits for example.

7.2 Safety test

NOTE
High-voltage test

The integrated EMC filter contains Y capacitors. Therefore, the
trigger current is exceeded when AC testing voltage is applied.
→ Test the device with DC voltage when you carry out the

high-voltage test required by law. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.

7.3 Maintenance interval

What has to
be tested?

How to test?

Frequency

Which
measure?

Corrosion

Visual inspection At least every

3 months

When there is
strong
corrosion that
impairs the EX
protection, e.g.
in gap
surfaces,
replace the
device.

Item no. 54008-5-9970 · ENG · Revision 87791 · Release 2016-04-29 · Page 15 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание IBExU14ATEX1123

Страница 1: ...are available in other languages on our website www ebmpapst com 2 2 SAFETY REGULATIONS AND NOTES 2 2 1 Levels of hazard warnings 2 2 2 Staff qualification 2 2 3 Basic safety rules 2 2 4 Electrical vo...

Страница 2: ...efects which impair safety must be rectified immediately Do not make any modifications additions or conversions to the device such as modifying the guard grille or attaching other equipment to the wal...

Страница 3: ...el greater than 70 dB A may arise Danger of noise induced hearing loss Take appropriate technical safety measures Protect operating personnel with appropriate safety equipment e g hearing protection A...

Страница 4: ...with explosion subcategories IIA and IIB and temperature classes T1 to T3 Only using the device in stationary systems Using the device only in resonance free speed ranges to avoid spark formation Pun...

Страница 5: ...g M20x1 5 4 Cable diameter min 10 mm max 14 mm tightening torque 6 0 6 Nm standard value depending on cable 5 Attachment screws for terminal box cover M4x20 tightening torque 3 5 0 5 Nm 6 Earth connec...

Страница 6: ...A Output 20 VDC max 50 mA Output for slave 0 10 V Operation and alarm display Input for sensor 0 10 V or 4 20 mA External 24 V input programming External release input Alarm relay Integrated PID contr...

Страница 7: ...l number Ex identification II 2 G Ex d e ib IIB T3 Gb Element Explanation Ex marking according to 2014 34 EU II Device group II use above ground not mining 2 Category 2 Zone 1 Category 3 Zone 2 G Ex a...

Страница 8: ...ny forces into the device which would cause strain and affect the gaps During installation make sure not to bend or pry the device in order to avoid mechanical tension Verify that all rotating parts c...

Страница 9: ...lish a safe protective earth connection Ensure compliance with the protection rating The seals in the terminal box from ebm papst have been inspected for their suitability The motor must be connected...

Страница 10: ...cting cables with terminals Open the terminal box To do so unscrew the seven attachment screws for tightening torque see chapter 4 1 Product drawing Take care when opening the terminal box cover Do no...

Страница 11: ...onnections and cable glands have been tightened to the specified torque 5 3 3 1 Exchange of screwed cable glands and plug screws If you would like to replace screwed cable glands or plug screws for ex...

Страница 12: ...tings Factory settings with which the device is pre set by ebm papst Control mode parameter set 1 PWM controlling Control mode parameter set 2 PWM controlling Fan device adress 01 Max PWM 100 Min PWM...

Страница 13: ...current motor level control coefficient motor speed parametrisable curve SELV 2 Din 2 Digital input 2 Parameter set 1 2 switching depending on EEPROM setting the valid used parameter set can be select...

Страница 14: ...nd PE are short circuited outside the potentially explosive area e g on the main switch Disconnect the connection line on the device When disconnecting be sure to disconnect the earth wire connection...

Страница 15: ...load back pressure too high Correct the operating point Let the device cool down To reset the error message switch off the mains supply voltage for a min of 25 s and switch it on again Alternatively r...

Страница 16: ...test At least every 3 months Replace the device in the event of noise stiffness or bearing play Have the motor bearings replaced by ebm papst Vibration test See Vibration test section At least every...

Отзывы: