background image

Operating instructions

W3G710-DU21-35

Translation of the original operating instructions

6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not perform any repairs on your device. Return the device to ebm-
papst for repair or replacement.

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor automatically restarts, e.g. after a power failure.

Danger of injury
→ Keep out of the danger zone of the device.
→ When working on the device, switch off the mains

supply voltage and secure the latter from being switched on
again.

→ Wait until the device stops.
→ After working on the device, remove any used tools or

other objects from the device.

If the device remains out of use for over four months, we
recommend switching the device on for at least three hours at
full speed to allow any condensate to evaporate and to move
the bearings.

Malfunction/error

Possible cause

Possible remedy

Impeller running
roughly

Imbalance in rotating
parts

Clean the device; if
imbalance is still
evident after
cleaning, replace the
device.
If you have
attached any weight
clips during cleaning,
make sure to
remove them
afterwards.

Motor does not turn

Mechanical blockage

Switch off, de-
energise, and
remove mechanical
blockage.

Mains supply
voltage faulty

Check mains supply
voltage,
restore power
supply.
Important! The error
message resets
automatically.
The device starts
up again
automatically without
advance warning.

Faulty connection

De-energise, correct
connection, see
connection diagram.

Motor winding broken Replace device

Insufficient cooling

Improve cooling. Let
the device cool
down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message
by applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.

Ambient temperature
too high

Reduce the ambient
temperature. Let the
device cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message
by applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.

Unacceptable
operating point (e.g.
counterpressure is
too high)

Correct the operating
point. Let the device
cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message
by applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.

If you have any other problems, contact ebm-papst.

Item no. 51479-5-9970 · ENG · Revision 82539 · Release 2014-05-08 · Page 11 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G710-DU21-35

Страница 1: ...y out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installe...

Страница 2: ...NGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WARNING Rotating device Long...

Страница 3: ...ace Minding the operating instructions Improper use Using the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt de...

Страница 4: ...the unit mm 1 Direction of air flow A 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm Item no 51479 5 9970 ENG Revision 82539 Release 2014 05 08 Page 4 1...

Страница 5: ...en on rotor Type of protection IP 54 Insulation class F Humidity class F5 Mounting position Shaft horizontal or rotor on top rotor on bottom on request Condensate discharge holes On the stator side Op...

Страница 6: ...dily harm e g back injuries are possible Two people should remove the device out of its packaging together Check the device for transport damage Damaged devices must no longer be installed Install the...

Страница 7: ...ss section VDE UL VDE mm AWG 3 PE AC 380 480 VAC 16 A 15 A C16A 1 5 16 3 PE AC 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 3 PE AC 380 480 VAC 32 A 30 A C32A 6 0 10 AWG...

Страница 8: ...ble routing No water may penetrate along the cable in the direction of the cable gland Fans installed lying flat Make sure that the cable is routed in the form of a loop water trap Fig 3 Fan installed...

Страница 9: ...n pin or applied voltage 5 50 VDC disabling bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 parameter set s...

Страница 10: ...fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the devi...

Страница 11: ...Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up...

Страница 12: ...ve casing against accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and...

Отзывы: