ebm-papst W3G710-DU21-35 Скачать руководство пользователя страница 4

Operating instructions

W3G710-DU21-35

Translation of the original operating instructions

3. TECHNICAL DATA

3.1 Product drawing

All measures have the unit mm.

1

Direction of air flow "A"

2

Cable diameter: min. 4 mm, max. 10 mm; tightening torque: 4±0.6 Nm

3

Tightening torque 3.5 ± 0.5 Nm

Item no. 51479-5-9970 · ENG · Revision 82539 · Release 2014-05-08 · Page 4 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G710-DU21-35

Страница 1: ...y out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installe...

Страница 2: ...NGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WARNING Rotating device Long...

Страница 3: ...ace Minding the operating instructions Improper use Using the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt de...

Страница 4: ...the unit mm 1 Direction of air flow A 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm Item no 51479 5 9970 ENG Revision 82539 Release 2014 05 08 Page 4 1...

Страница 5: ...en on rotor Type of protection IP 54 Insulation class F Humidity class F5 Mounting position Shaft horizontal or rotor on top rotor on bottom on request Condensate discharge holes On the stator side Op...

Страница 6: ...dily harm e g back injuries are possible Two people should remove the device out of its packaging together Check the device for transport damage Damaged devices must no longer be installed Install the...

Страница 7: ...ss section VDE UL VDE mm AWG 3 PE AC 380 480 VAC 16 A 15 A C16A 1 5 16 3 PE AC 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 3 PE AC 380 480 VAC 32 A 30 A C32A 6 0 10 AWG...

Страница 8: ...ble routing No water may penetrate along the cable in the direction of the cable gland Fans installed lying flat Make sure that the cable is routed in the form of a loop water trap Fig 3 Fan installed...

Страница 9: ...n pin or applied voltage 5 50 VDC disabling bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 parameter set s...

Страница 10: ...fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the devi...

Страница 11: ...Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up...

Страница 12: ...ve casing against accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and...

Отзывы: